HART Transmitter Power Supply, Input Isolator
LB3005A2
< 4-channel < Power supply for 2-wire transmitters with 4 mA ... 20 mA < Installation in Zone 2 or safe area < Supply circuit 15 V (20 mA) < Input from active signals of 4-wire transmitters < HART communication via field bus or service bus < Simulation mode for service operations (forcing) < Line fault detection (LFD): one LED per channel < Permanently self-monitoring < Module can be exchanged under voltage

Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254700_eng.pdf

Function
The transmitter power supply feeds 2-wire transmitters. Active signals from separately powered field devices and 4-wire transmitters can be connected. Open and short circuit line faults are detected. The inputs are galvanically isolated from the bus and the power supply.
Connection

COM

HART

8-

16-

mA

II 7+ IV 15+

6-

14-

5+

13+

4-

12-

mA

I 3+ III 11+

2-

10-

1+

9+

HART

Technical Data
Slots Occupied slots
Supply Connection Rated voltage Power dissipation Power consumption
Internal bus Connection Interface

Zone 2

2

backplane bus

Ur

12 V DC , only in connection with the power supplies LB9***

1.5 W

2.7 W

backplane bus manufacturer-specific bus to standard com unit

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group www.pepperl-fuchs.com

USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com

Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com

Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com

1

HART Transmitter Power Supply, Input Isolator Technical Data

LB3005A2

Analog input Number of channels Suitable field devices Field device Field device [2] Field device [3] Field device [4] Field device interface Connection Connection [2] Connection [3] Connection
Transmitter supply voltage Input resistance Conversion time Line fault detection
Short-circuit Open-circuit HART communication HART secondary variable Transfer characteristics Deviation After calibration Influence of ambient temperature Resolution Refresh time Indicators/settings LED indication
Coding Directive conformity
Electromagnetic compatibility Directive 2014/30/EU
Conformity Electromagnetic compatibility Degree of protection Environmental test Shock resistance Vibration resistance Damaging gas Relative humidity
Ambient conditions Ambient temperature Storage temperature Relative humidity Shock resistance

4
pressure converter flow converter level converter Temperature Converter
2-wire transmitter 3-wire transmitter 4-wire transmitter 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter:Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16min. 15 V at 20 mA ; 21.5 V at 4 mA 15  max. 100 ms can be switched on/off for each channel via configuration tool , configurable via configuration tool factory setting: > 22 mA configurable between 0 ... 26 mA factory setting: < 1 mA configurable between 0 ... 26 mA yes no
0.1 % of the signal range at 20 °C (68 °F) 0.1 %/10 K of the signal range 12 Bit (0 ... 26 mA) 100 ms
Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) optional mechanical coding via front socket
EN 61326-1:2013
NE 21:2007 IEC 60529:2000 EN 60068-2-14:2009 EN 60068-2-27:2009 EN 60068-2-6:2008 EN 60068-2-42:2003 EN 60068-2-78:2001
-40 ... 60 °C (-40 ... 140 °F) , 70 °C (non-Ex) -40 ... 85 °C (-40 ... 185 °F) 95 % non-condensing shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18

Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254700_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group www.pepperl-fuchs.com

USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com

Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com

Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com

2

HART Transmitter Power Supply, Input Isolator Technical Data

LB3005A2

Vibration resistance

frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance

Damaging gas

designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3

Mechanical specifications

Degree of protection

IP20 when mounted on backplane

Connection

removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)

Mass

approx. 150 g

Dimensions

32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)

Data for application in connection with hazardous areas

Certificate

BVS 12 ATEX E 105 X

Marking

1 II 3 G Ex nA [ic] IIC T4 Gc

Galvanic isolation

Input/power supply, internal bus

safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V

Directive conformity

Directive 2014/34/EU

EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010

International approvals

ATEX approval

BVS 12 ATEX E 105 X

IECEx approval

BVS 12.0055X

Approved for

Ex nA [ic] IIC T4 Gc

General information

System information

The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.

Supplementary information

EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Assembly
Front view

Power LED green
Status LED red per channel

P

I

1

2

3

4

Ex ic

Ex ic

Diagnostic LED red/white

Release date: 2021-12-01 Date of issue: 2021-12-01 Filename: 254700_eng.pdf

8 16 7 15 6 14 5 13 4 12 3 11 2 10 19

Sockets for removable plugs green (accessory)

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

Pepperl+Fuchs Group www.pepperl-fuchs.com

USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com

Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com

Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com

3

