Pacific Ventilation EC-BASIC Room Controller

Pacific-Ventilation-EC-BASIC-Room-Controller-PRODUCT

Specifications

  • Power: 110-240 V~, 50/60 Hz
  • Power consumption:
    • EC BASIC-T: max 0.46 W
    • EC BASIC-H: max 0.46 W
    • EC BASIC-U: max 0.46 W
    • EC BASIC-C02/T: max 1.25 W
  • Inputs (only EC Basic-U): 1 analogue input 0-10 V
  • Outputs:
    • 1 analogue output 0-10 V (max 1mA)
  • Working range:
    • EC BASIC-T, EC BASIC-H: 0-100% RH
    • EC BASIC-U: 0-100%
    • EC BASIC-C02/T: 0-2000 ppm
  • Manual activation: minimum 600 cycles
  • Automatic activation: > 100,000 cycles
  • Dimensions: 88 x 100 x 30.5 mm
  • Installation: wall mounting
  • Impulse voltage: 2.5 kV
  • Pollution degree: 2
  • Classification of unit: type 1
  • Protection class: IP30
  • Insulation class: class II
  • CE standard conformity: EN 60730-1, EN 61000-6-3, EN 61000-6-1, EN 60730-2-9

Product Usage Instructions

The controller compares the room temperature with an adjustable setpoint and controls a 0-10 V output signal using a PI algorithm in direct or reverse action.

  • JP1 closed 1-2: Heating mode (control signal increases if the actual value falls below the setpoint)
  • JP1 closed 2-3 (*): Cooling mode (control signal increases if the actual value exceeds the setpoint)
  • The proportional band and integral time are set using rotary switch SW1.
  • The range of the voltage applied to the ventilator is defined using the MIN and MAX knobs.
  • The controller compares the current room humidity with a setpoint and controls a 0-10 V output signal using a proportional algorithm.
  • JP1 closed 1-2: Humidification mode (control signal increases if the actual value falls below the setpoint)
  • JP1 closed 2-3 (*): Dehumidification mode (control signal increases if the actual value exceeds the setpoint)
  • The controller compares an input signal with a setpoint and controls a 0-10 V output signal using a PI algorithm.

FAQ

  • Q: Can the EC room controller be used with external sensors?
  • A: Yes, the EC BASIC-U version is designed to work with an external sensor that provides a 0-10 V input.
  • Q: What is the minimum and maximum voltage range for ventilator control?
  • A: The MIN knob sets the minimum applicable voltage to the ventilator (0-5 V), while the MAX knob sets the maximum voltage (5-10 V).
  • Q: How is the PI controller operated between MIN and MAX values?
  • A: The PI controller operates within the range defined by the MIN and MAX values set on the controller.

Technical features

  • Power: 110-240 V~, 50/60 Hz
  • Power consumption: EC BASIC-T max 0,46 W
    • EC BASIC-H max 0,46 W
    • EC BASIC-U max 0,46 W
    • EC BASIC-C02/T max 1,25 W
  • Operating temperature: 0-50°C, 10-90%r.H without condensation.
  • Inputs (only EC Basic-U): 1 analogue input 0-10 VPacific-Ventilation-EC-BASIC-Room-Controller-FIG-13
  • Outputs: 1 analogue output 0-10 VPacific-Ventilation-EC-BASIC-Room-Controller-FIG-13 (max 1mA)
  • Working range: EC BASIC-T 0-50°C
    • EC BASIC-H 0-100 % RH
    • EC BASIC-U 0-100 %
    • EC BASIC-C02/T 0-2000 ppm
  • Manual activation: minimum 600 cycles
  • Automatic activation: > 100.000 cycles
  • Dimensions: 88 x 100 x 30,5 mm
  • Installation: *wall mounting
  • Impulse voltage: 2,5 kV
  • Pollution degree: 2
  • Classification of unit: type 1
  • Protection class: IP30
  • Insulation class: class II
  • CE standard conformity: EN 60730-1, EN 61000-6-3, EN 61000-6-1 EN 60730-2

The unit must be installed exclusively in contact with a wall. The installation with a spacer that would allow access to the back of the unit is forbidden.

DESCRIPTION

  • EC room controller in 4 versions for control of temperature, humidity, or CO2 temperature.
  • Also available in a universal version for 0-10 V input via an external sensor.

TECHNICAL DESCRIPTION

EC BASIC-T Temperature version

The controller works by comparing the current room temperature with an adjustable setpoint. It controls a 0-10 V output signal with a PI algorithm in direct or reverse action, based on the setting of jumper JP1. The output signal is applied to a ventilator.

  • JP1 closed 1-2: Heating (control signal increases if the actual value falls below the setpoint)
  • JP1 closed 2-3 (*): Cooling (control signal increases if the actual value exceeds the setpoint)

The setpoint is adjusted by a knob in the range of 5-30°C.
Proportional band and integral time are set using rotary switch SW1:

SW1 0 1 2 3 4 5 6 7
Prop. band (°C) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral time (s) 1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop. band (°C) 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral time (s) 1000 900 800 700 600 500 400 300

factory settings

The range of the voltage applied to the ventilator is defined using the MIN and MAX knobs. MIN is used to define the minimum applicable voltage to the ventilator (0-5 V), while MAX defines the maximum voltage (5-10 V). The PI controller will then operate between the relevant MIN and MAX values.

  • Example 1: If the MIN value is set to the minimum position and MAX to the maximum position, the PI controller will work from 0-10 V.
  • Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller works from 2 to 7 V.

EC BASIC-H Humidity version

TECHNICAL DESCRIPTION
The controller works by comparing the current room humidity with an adjustable setpoint. It controls a 0-10 V output signal with a proportional algorithm in direct or reverse action, based on the setting of jumper

  • JP1. The output signal is applied to a ventilator.
  • JP1 closed 1-2: Humidification (control signal increases if the actual value falls below the setpoint)
  • JP1 closed 2-3 (*): Dehumidification (control signal increases if the actual value exceeds the setpoint)

The humidity setpoint is set using rotary switch SW1:

SW1 0 (*) 1 2 3 4 5 6 7
Setpoint (% RH) 20 25 30 35 40 45 50 55
SW1 8 9 A B C D E F
Setpoint (% RH) 60 65 70 75 80 85 90 90

factory settings
The proportional band is set using rotary switch SW2:

SW2 0 1 2 3 4 5 6 7
Prop. band (% RH)  

5

 

10

 

15

 

20

 

25

 

30

 

35

 

40

SW2 8 9 A B C D E F (*)
Prop. band (% RH)  

45

 

50

 

50

 

50

 

50

 

50

 

50

 

50

factory settings
The range of the voltage applied to the ventilator is defined using the MIN and MAX trimmer. MIN trimmer is used to define the minimum applicable voltage to the ventilator (0-5 V), while MAX trimmer defines the maximum voltage (5-10 V). The P controller will then operate between the relevant MIN and MAX values.

  • Example 1: If the MIN value is set to the minimum position and MAX to the maximum position, the P controller will work from 0-10 V.
  • Example 2: If MIN is set to 2 V and MAX is set to 7 V, the P controller works from 2-7 V.

EC BASIC-U Universal version

TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable setpoint. It controls a 0-10 V output signal with a PI algorithm in direct or reverse action, based on the setting of jumper JP1. The output signal is applied to a ventilator.

  • JP1 closed 1-2: Control signal increases if the actual value falls below the setpoint
  • JP1 closed 2-3 (*): Control signal increases if the actual value exceeds the setpoint

The universal setpoint is set using rotary switch SW1:

SW1 0 (*) 1 2 3 4 5 6 7
Setpoint (%) 5 10 20 25 30 35 40 45
SW1 8 9 A B C D E F
Setpoint (%) 50 55 60 65 70 80 90 95

factory settings
Proportional band and integral time are set using rotary switch SW2

SW2 0 1 2 3 4 5 6 7
Prop. band (%) 1 1.5 2 3 5 7 10 14
Integral time (s) 600 462 356 274 211 163 125 97
SW2 8 9 A B C D E F (*)
Prop. band (%) 21 31 45 66 96 140 205 300
Integral time (s) 74 57 44 34 26 20 16 12

factory settings
The range of the voltage applied to the ventilator is defined using the MIN and MAX trimmer. MIN trimmer is used to define the minimum applicable voltage to the ventilator (0-5 V), while MAX trimmer defines the maximum voltage (5-10 V). The PI controller will then operate between the relevant MIN and MAX values.

  • Example 1: If the MIN value is set to the minimum position and MAX to the maximum position, the PI controller will work from 0-10 V.
  • Example 2: If MIN is set to 2 V and MAX is set to 7 V, the PI controller works from 2-7 V.

EC BASIC-CO2/T Temperature + CO2 version

TECHNICAL DESCRIPTION
The controller works by comparing the input signal with an adjustable setpoint. It controls a 0-10 V internal signal with a PI algorithm in direct or reverse action, based on the setting of jumper JP1.

  • JP1 closed 1-2: Heating (control signal increases if the actual value falls below the setpoint)
  • JP1 closed 2-3 (*): Cooling (control signal increases if the actual value exceeds the setpoint)

The controller also compares current CO2 levels with an adjustable setpoint and controls a 0..10 V proportional, secondary internal signal in direct action.
The output signal applied to the ventilator constitutes the maximum between internal signal # 1 and internal signal # 2.
The setpoint is adjusted by a knob in the range of 5-30°C.
The temperature proportional band and integral time are set using rotary switch SW1:

SW1 0 1 2 3 4 5 6 7
Prop. band (°C) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Integral time (s) 1800 1700 1600 1500 1400 1300 1200 1100
SW1 8 9 A B C D E F (*)
Prop. band (°C) 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Integral time (s) 1000 900 800 700 600 500 400 300

factory settings
The CO2 proportional band is set using rotary switch SW2:

SW2 0 1 2 3 4 5 6 7
Prop. band (ppm)  

10

 

25

 

50

 

75

 

100

 

125

 

150

 

175

SW2 8 9 A B (*) C D E F
Prop. band (ppm)  

200

 

300

 

400

 

500

 

600

 

700

 

800

 

1000

factory settings
The CO2 setpoint is set using rotary switch SW3:

SW3 0 (*) 1 2 3 4 5 6 7
Setpoint (ppm) 350 400 450 500 550 600 650 700
SW3 8 9 A B C D E F
Setpoint (ppm) 750 800 850 900 950 1000 1200 1500

factory settings
The range of the voltage applied to the ventilator is defined using the MIN and MAX trimmer. MIN trimmer is used to define the minimum applicable voltage to the ventilator (0-5 V), while MAX trimmer defines the maximum voltage (5-10 V). The PI controller will then operate between the relevant MIN and MAX values.

  • Example 1: If the MIN value is set to the minimum position and MAX to the maximum position, the controller will work from 0-10 V.
  • Example 2: If MIN is set to 2 V and MAX is set to 7 V, the controller works from 2-7 V.

Installation Instructions

EC BASIC-T
(Temperature version / Temperaturversion)

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-1

  • SW1: Temperature proportional band (0.5-8.0°C)
  • JP1 closed 1-2: Heating
  • JP1 closed 2-3: Cooling
  • R23: Temperature setpoint (5-30°C)
  • R28: EC fan min. limit speed
  • R29: EC fan max. limit speed

EC BASIC-H
(Humidity version / Fuktstyrningssversion)

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-2

  • SW1: Humidity setpoint (20-90 % RH)
  • SW2: Humidity proportional band (5-50 % RH)
  • JP1 closed 1-2: Humidification
  • JP1 closed 2-3: Dehumidification
  • R28: EC fan min. limit speed
  • R29: EC fan max. limit speed

EC BASIC-U
(Universal version / Universal version)

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-3

  • SW1: Setpoint (5-95 %)
  • SW2: Proportional band (1-300 %)
  • JP1 closed 1-2: Reverse action
  • JP1 closed 2-3: Direct action
  • R28: EC fan min. limit speed
  • R29: EC fan max. limit speed

EC BASIC-CO2/T
(Temperature + CO2 version / Temperatur- + CO2-version)

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-4

  • SW1: Temperature proportional band (0.5-8.0°C)
  • SW2: CO2 proportional band (10-200 ppm)
  • SW3: CO2 setpoint (350-1500 ppm)
  • JP1 closed 1-2: Heating
  • JP1 closed 2-3: Cooling
  • R23: Temperature setpoint (5-30°C)
  • R28: EC fan min. limit speed
  • R29: EC fan max. limit speed

Temperature and temperature + CO2 version / Temperatur- och temperatur- + CO2-version

  • Temperature setpoint

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-5

Mounting

  • To remove the front cover, use a 3 mm flat-blade screwdriver to depress the locking tongue in the lower part of the casing.

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-6

  • Press and twist the screwdriver, and at the same time pull the bottom part of the front outwards.

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-7

  • When the bottom end of the front cover is free from the bottom part of the casing, slide the cover towards the top of the casing to free the hooks holding the upper edge of the front cover.

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-8

  • Perform the connections according to the electrical wiring diagram. Cables must be fixed using the 2 cable ties supplied as indicated on the picture above.
  • Screw the bottom part of the casing to the wall.

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-9

Dimensions

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-10

Wiring

Version

  • EC Basic-T: Temperature / temperatur
  • EC Basic-CO2/T: Temperature + CO2 / temperatur + CO2
  • EC Basic-H: Humidity / luftfuktighet

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-11

Version

  • EC Basic-U: Universal / universell

Pacific-Ventilation-EC-BASIC-Room-Controller-FIG-12

All installation, setting, or maintenance of this unit must be performed with the supply voltage switched off and without any external loads on the unit! These operations should only be carried out by skilled workers. The manufacturer is not responsible for any damages caused by inadequate skills during installation and/or by any safety devices having been removed or tampered with.
Subject to change without notice.