nVent RAYCHEM - logoFTC-P Power Connection and End Seal Kit
Instruction Manual

FTC-P
XL-Trace Edge, RaySol, and IceStop Power Connection Kit with End Seal Installation InstructionsnVent RAYCHEM FTC-P Power Connection and End Seal Kit

DESCRIPTION

The nVent RAYCHEM FTC-P Power Connection and End Seal Kit is for use with nVent RAYCHEM XL-Trace Edge, RaySol and IceStop heating cables. Materials for one  power connection and one end seal are included in this kit. These installation instructions should be used in conjunction with the XL-Trace Edge, RaySol and IceStop System Installation and Operation Manuals. For technical support contact your nVent representative or call nVent at 800-545-6258.

TOOLS REQUIRED

• Screw driver • Pen
• Needle-nose pliers • Diagonal cutters
• Utility knife • Heat gun or propane torch

ADDITIONAL MATERIALS REQUIRED (NOT PROVIDED IN THIS KIT)

  • UL Listed or CSA Certified junction box suitable for the location, with a clearance hole or threaded hub for 1⁄2 inch NPT. For RaySol applications, the power connection and end seal may be terminated in the same box.

APPROVALS

nVent RAYCHEM FTC-P Power Connection and End Seal Kit - icon 1 With XL-Trace Edge
nVent RAYCHEM FTC-P Power Connection and End Seal Kit - icon 2 With IceStop and Raysol
nVent RAYCHEM FTC-P Power Connection and End Seal Kit - icon 3 With IceStop and RaySol
nVent RAYCHEM FTC-P Power Connection and End Seal Kit - icon 3 With IceStop heating cable only
For Class I, Div. 2, Groups A, B, C, D
Hazardous Locations: GM-1XT and GM-2XT only

WARNING:
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully  follow all the installation instructions.

  • To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of nVent,  agency certifications, and national electrical codes, ground fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
  • Bus wires will short if they contact each other.
    Keep bus wires separated.
  • Keep components and heating cable ends dry before and during installation.
  • The black heating cable core is conductive and can short. It must be properly insulated and kept dry.
  • Component approvals and performance are based on the use of nVent– specified parts only. Do not use substitute parts or vinyl electrical tape.
  • Leave these instructions with end user for reference and future use.

CAUTION:
HEALTH HAZARD: Overheating heatshrinkable tubes will produce fumes that may cause irritation. Use adequate ventilation and avoid charring or burning. Consult MSDS RAY3122 for further information.
CHEMTREC 24-hour emergency telephone: 800-424-9300
Non-emergency health and safety information: 800-545-6258.

KIT CONTENTS

nVent RAYCHEM FTC-P Power Connection and End Seal Kit - KIT

Item Qty Description
A 4 Warning labels
B 1 Pipe mounting bracket
C 1 Lock nut
D 1 Blue grommet
E 1 Sealing fitting
F 3 Wire nuts
G 1 Black heat-shrinkable tube (1/2 in x 11/2 in)
H 1 Green/yellow heat-shrinkable tube (1/4 in x 51/2 in)
I 2 Black heat-shrinkable tubes (1/8 in x 51/2 in)
J 1 #3 pipe strap
K 1 Gel-filled end seal (FTC-E)
L 1 RaySol circuit tag
M 1 Sealing gasket

POWER CONNECTION INSTALLATION

nVent RAYCHEM FTC-P Power Connection and End Seal Kit - INSTALLATIONnVent RAYCHEM FTC-P Power Connection and End Seal Kit - INSTALLATION 2nVent RAYCHEM FTC-P Power Connection and End Seal Kit - INSTALLATION 3nVent RAYCHEM FTC-P Power Connection and End Seal Kit - INSTALLATION 4nVent RAYCHEM FTC-P Power Connection and End Seal Kit - INSTALLATION 5

END SEAL INSTALLATION FOR XL-TRACE EDGE-CR AND -CT, RAYSOL, AND ICESTOP HEATING CABLES

  • Score down and around outer jacket 1 inch from the end.
  • Remove the outer jacket.
  • Do not cut or damage inner jacket. If damaged, remove damaged section and repeat step 1.
    nVent RAYCHEM FTC-P Power Connection and End Seal Kit - CABLES 1
  • Remove exposed braid.
    nVent RAYCHEM FTC-P Power Connection and End Seal Kit - CABLES 2
  • Push end seal completely onto heating cable.
    Note: The end seal is designed to be installed only once; it cannot be removed from the heating cable once installed. Do not use until ready for final installation.
    nVent RAYCHEM FTC-P Power Connection and End Seal Kit - CABLES 3
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com

nVent RAYCHEM - logo

©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-IM-H53514-FTCP-EN-2111
nVent.com/RAYCHEM