neptronic TM220FN Non Spring Return Damper Actuator
Features:
- Clutch for manual adjustments.
- Maintenance free.
- Position indicator.
- Control signal fully programmable.
- Brushless DC driven motor.
- Fail safe by Enerdrive System1 (on model 260 & 280).
- Auxiliary switches (on model 260 & 280).
Technical Data
|
TM200FN | TM220FN | TM260FN | TM280FN | RM200FN | RM220FN | RM260FN |
RM280FN |
Auxiliary switches |
No | Yes (2) | No | Yes (2) | No | Yes (2) | No |
Yes (2) |
Fail safe – Enerdrive |
No | Yes | No |
Yes |
||||
Power consumption | 30 VA | 50 VA Peak, 30 VA | 30 VA | 50 VA Peak, 30 VA | ||||
Torque |
120 in.lb. [13.5 Nm] at rated voltage | 240 in.lb. [27 Nm] at rated voltage | ||||||
Running time through 90º |
20 sec torque dependant |
|||||||
Power supply |
28 to 32 Vdc or 22 to 26 Vac, 220 to 250 Vac 50/60Hz | |||||||
Feedback |
4 to 20 mA or 2 to 10 Vdc adjustable |
|||||||
Electrical connection |
18 AWG [0.8 mm2] minimum | |||||||
Inlet bushing |
2 inlet bushing of 7/8 in [22.2 mm] |
|||||||
Control signal |
Analog, Digital or PWM programmable (factory set with analog control signal) | |||||||
Angle of rotation |
0 to 90 degrees, electronically adjustable (factory set with 90º stroke) |
|||||||
Direction of rotation |
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction) |
|||||||
Operating temperature |
0ºF to 122ºF [-18ºC to 50ºC] |
|||||||
Storage temperature |
-22ºF to 122ºF [-30ºC to 50ºC] |
|||||||
Relative Humidity |
5 to 95 % non condensing. |
|||||||
Weight |
5 lbs. [2.3 kg] |
8 lbs. [3.5 kg] |
||||||
Warning: Do not press the clutch when actuator is powered |
Dimensions
Dimension |
Imperial (in) | Metric (mm) |
A | 5.20 |
132.1 |
B |
1.33 | 33.8 |
C | 9.13 |
231.9 |
D |
3.55 |
90.2 |
Caution
We strongly recommend that all Neutronic® products be wired to a separate transformer and that transformer shall service only Neutronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
Mechanical Installation
![]() |
|
Wiring Diagrams
Digital signal from internal source
Digital signal
Input Signal and Feedback setup
Input Signal | Feedback | |
Analog Mode | Input Signal is set with Dipswitch # 3 DS1-3 at OFF = 2 – 10Vdc (default setting) DS1-3 at ON = 4 – 20mA | Feedback is set with Dipswitch #4 DS1-4 at OFF = 4 – 20mA (default setting) DS1-4 at ON = 2 – 10Vdc |
Digital & PWM Mode | No Input Signal Setting![]() |
PC Board
Stroke adjustment – No control signal change
- Apply power and, WAIT FOR LED TO BE OFF (around 10 seconds).
- Press and release the reset button to start the auto-stroke process.
The LED should be illuminated.
- First option:
The actuator will then travel in both directions to find its limit and position itself according to the demand.
The LED will extinguish, the process is complete. - Second option:
When the desired start position is reached, press and release the reset button. The actuator will now go the end position. (you can also press and release the reset button when it reaches the end position)
The LED will extinguish, the process is complete
Programming – Change of control signal & PWM pulse setting
- Remove power and put all dip switches “OFF”. (factory preset).
- Apply power and, within 10 seconds, press and release the reset button. The LED should be blinking.
- Select the control signal with dip switches:
Digital or Analog Modes PWM Mode Move switch No1 “ON” and then “OFF”. Digital (On/Off or 3 point floating) 5 sec. pulse (factory preset)
Move switch No2 “ON” and then “OFF”.
Analog (Default) 25 sec. pulse
- Stroke adjustment see the stroke adjustment section above.
Enabling or disabling PWM mode
- Remove power supply to actuator
- Install jumper between pin 3 & 4 of J3
- Select the desired action using the dipswitches (DS1):
DS1-1 DS1-2 Action OFF ON Enable PWM Mode ON OFF Disable PWM Mode - Re-apply power supply to actuator
- Wait 5 seconds
- Remove power supply to actuator
- Remove jumper between pin 3 & 4 of J3, re-install it between pin 4 & 5.
- Re-apply power supply to actuator
PWM is factory preset at 5 sec. pulse, refer to programming section above to change pulse setting.
When not used for programming, jumper is placed between pin 4 & 5
Wiring Diagrams for auxiliary switches (on model 220 & 280)
![]() |
Auxiliary switch rating: 5 Amp resistive, 250 Vac |