neptronic-LOGO

Medtronic LT000 Actuator Non-Spring Return Damper Actuator

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-PRODUCT

Models

LT000 Actuator: 140 in.lb. (16 Nm) without fail safe

Features

  • Mounts easily on round and square shafts
  • Manual clutch
  • Maintenance-free
  • Position indicator
  • FD5-T 5000 Ohms feedback potentiometer (optional)
  • AC2-T adjustable auxiliary switch (optional)
  • Stroke limiting device (SLD) (optional)

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-1

Description LT000 Actuator
Torque 140 in.lb. [16 Nm] at rated voltage
Motor Type Brush motor
Running Time (for 90° Rotation) 60 to 85 seconds torque dependent
Fail Safe (Enerdrive) No failsafe
Fail Safe Runtime (0° to 90°) None
Capacitor Charge Time on / Power-up None
Power Consumption 6VA
Overload Protection Electronic throughout, 0° to 90° rotation
Power Supply 22 to 26 Vac | 28 to 32 Vdc | 50/60Hz
Transformer Requirements Class 2; 6VA minimum
Cable N/A
Electrical Connection Optional BX conduit connector (BW BXCON-1)
Impedance (Input) N/A
Control Signals On/Off or floating
Feedback Signals Optional add-on FD5-T feedback potentiometer
Angle of Rotation 0° to 90°, mechanically adjustable with SLD (optional) (default: 90° stroke)
Direction of Rotation Reversible, CW: Clockwise, CCW: Counter Clockwise (default: CW)
Noise Produced 45 dB(A)
Ingress Protection IP22 equivalent to Nema type 2
Operating Temperature -22°F to +122°F [-30°C to +50°C]
Storage Temperature -22°F to +122°F [-30°C to +50°C]
Relative Humidity 5 to 95% non-condensing
Weight 4.5 lb. [2kg]
Purpose and Action of Control Type 1 Operating Control, Electric Actuator
Construction of Control Independently Mounted
Pollution Degree 2
Impulse Voltage 330V
Quality Management System ISO 9001:2015
Certification Complies to standards: UL 60730-1 & UL 60730-2-14, CSA E60730-1 & CSA E60730-2-14
Complies to Low Voltage Directive & Electromagnetic Compatibility Directive
Complies to Electrical Equipment (Safety) Regulations & Electromagnetic Compatibility Regulations
WARNING: Risk of mechanical failure. Do NOT press clutch when actuator is in operation.

Dimensions

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-2

  • A = 5.20” (132mm)
  • B = 1.33” (34mm)
  • C = 9.13” (232mm)
  • D = 3.39” (86mm)

Mechanical Installation

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-3

  1. Manually close the damper blades and position the actuator to 0º or 90º.
  2. Slide the actuator onto the shaft.
  3. Tighten the nuts on the “U” bolt to the shaft with a 10mm wrench to a torque of 150 in-lb [17 Nm].
  4. Slide the mounting bracket under the actuator. Ensure free movement of the slot at the base of the actuator. Place the bracket pin at mid-distance of the slot.
  5. Affix the bracket to the ductwork with #8 self-tapping screws.

Wiring

We strongly recommend that all products be wired to a separate grounded transformer and that transformer shall service only these products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.

PCB

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-4

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-5

DIP Switch Settings

# Feature OFF ON
1 Rotation CW * CCW
2 Fail-safe direction N/A N/A

* = default

LED Status

State Description
Flash Normal operation

neptronic-LT000-Actuator-Non-Spring-Return-Damper-Actuator-FIG-6Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.

neptronic.com | 514-333-1433 | contact@neptronic.com

Documents / Resources

neptronic LT000 Actuator Non Spring Return Damper Actuator [pdf] Installation Guide
LT000, LT000-250214, LT000 Actuator Non Spring Return Damper Actuator, LT000, Actuator Non Spring Return Damper Actuator, Non Spring Return Damper Actuator, Return Damper Actuator, Damper Actuator, Actuator

References

Leave a comment

Your email address will not be published. Required fields are marked *