MRCOOL - logoPRODIRECT™ Series
PSC Air Handler
Installation & Owner’s Manual
MODELS:
HAH018FPA
HAH024FPA
HAH036FPA
HAH048FPA
HAH060FPAMRCOOL HAH0 Series PSC Air Handler-

Read this manual carefully before installation and keep it where the operator can easily find it for future reference.
Due to updates and constantly improving performance, the information and instructions within this manual are subject to change without notice.
Version Date: 12/30/2024
Please visit www.mrcool.com/documentation to ensure you have the latest version of this manual.

SAFETY

Safety Precautions

Read Before Using
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be followed closely or actions that should be avoided to prevent death, injury, and/or property damage.

MRCOOL HAH0 Series PSC Air Handler- icon WARNING Indicates the possibility of personal injury or loss of life.
MRCOOL HAH0 Series PSC Air Handler- icon1 CAUTION Indicates the possibility of property damage or serious consequences.
MRCOOL HAH0 Series PSC Air Handler- icon WARNING

  1. These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment, and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service, or maintenance possibly resulting in fire, electrical shock, property damage, personal injury, or death.
  2.  This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  3. Children should be supervised to ensure that they do not play with the appliance.
  4. This unit can’t be used outdoors.
  5. Because of possible damage to equipment or personal injury, installation, service, and maintenance should be performed by a trained, qualified service personnel. Consumer service is recommended only for filter cleaning/replacement. Never operate the unit with the access panels removed.
  6. The first 6 inches of supply air plenum and ductwork must be constructed of sheet metal as required by NFPA 90B. The supply air plenum or duct must have a solid sheet metal bottom directly under the unit with no openings, registers or flexible air ducts located in it. If flexible supply air ducts are used, they may be located only in the vertical walls of rectangular plenum, a minimum of 6 inches from the solid bottom. Metal plenum of duct may be connected to the combustible floor base, if not, it must be connected to the unit supply duct exposed to the supply air opening from the downflow unit. Exposing combustible (nonmetal) material to the supply opening of a downflow unit can cause a fire resulting in property damage, personal injury or death.
  7. Exception warning to downflow: Installations on concrete floor slab with supply air plenum and ductwork completely encased must be not less than 2 inches of concrete (See NFPA 90A).

MRCOOL HAH0 Series PSC Air Handler- icon ELECTRICAL WARNINGS

  1. Disconnect power to the unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.
  2. If removal of the blower assembly is required, all disconnect switches supplying power to the equipment must be de-energized and locked (if not in sight of unit) so the field power wires can be safely removed from the blower assembly. Failure to do so can cause electrical shock resulting in personal injury or death.
  3. The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death.

UNIT OVERVIEW

MRCOOL HAH0 Series PSC Air Handler- icon WARNING: PROPOSITION 65

  • This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer.
  • All manufacturer products meet current federal OSHA Guidelines for safety. California Proposition 65 warnings are not required for certain products, which are not covered by the OSHA standards.
  • California’s Proposition 65 requires warnings for products sold in California that contain or produce any of over 600 listed chemicals known to the state of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural vapor.
  • All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know when or if products will be sold in the California market.
  • You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air conditioning equipment, or found in natural vapor used with some of our products. The following are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers: glass wool (fiberglass) insulation, carbon monoxide (CO), formaldehyde, benzene
  • More details are available on the following websites: www.osha.gov and www.oehha.org
  • Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled, and maintained.

2.1 Location Selection
The unit can be positioned for bottom return air in the upflow position, left and right return in the horizontal position, top return in downflow position.
This Air Handler provides the flexibility for installation in any upflow or downflow horizontal application. The direct drive motors provide a selection of air volume to match any application. 3-Speed motors provide selections of air flow to meet desired applications.
Top and side power and control wiring, accessible screw terminals for control wiring all combine to make the installation easy, and minimize installation cost.
Do not install unit in an area where flammable materials are present due to the risk of an explosion resulting in serious injury or death.
The unit should be installed in a level position to ensure proper condensation drainage. Up to an additional 1/4″ rise over the width or depth of the unit is allowed to create additional sloping towards the drain. The unit must be positioned between level and 1/4″ rise, sloping toward the drain connections.
Install the indoor and outdoor unit, power supply wiring and connecting wires at least 3.5 ft. away from televisions or radios in order to prevent image interference or noise.

MRCOOL HAH0 Series PSC Air Handler- Location Selection

MRCOOL HAH0 Series PSC Air Handler- icon WARNING
If the supporting structural members are not strong enough to support the unit’s weight, the unit could fall out of place and cause serious injury.
If a return-air duct is not installed, carefully select the place and method of product installation so that airflow into the product will not be blocked.
When the unit is installed in a hot and humid place, if the humidity inside the installation space might exceed 86°F (30°C) and RH 80%, it is recommended to insulate the cabinet exterior.
Use glass wood or polyethylene foam as insulation so that the thickness is more than 2 in. and fits inside the installation space opening.
Respectively, condensation may form on the surface of the insulation.
Be sure to use insulation that is designed for use with HVAC Systems.
Condensation may form on the product during cool operation.
It is also recommended to use the second drain pan and secure the unit firmly to prevent it from falling.

MRCOOL HAH0 Series PSC Air Handler- falling

2.2 Unit Dimensions

MRCOOL HAH0 Series PSC Air Handler- Unit Dimensions

Unit Dimensions
Model Height (in. [mm]) Width (in. [mm]) Length (in. [mm]) Supply Duct “A” Unit Weight (lbs. [kg])
18 41-3/8″ [1050] 18-1/8 [460] 20-1/2 [520] 16″ [406] 106 [48]
24 46-1/2″ [1180] 19-5/8″ [500] 21-5/8″ [550] 18″ [456] 128 [58]
30 46-1/2″ [1180] 19-5/8″ [500] 21-5/8″ [550] 18″ [456] 128 [58]
36 46-1/2″ [1180] 19-5/8″ [500] 21-5/8″ [550] 18″ [456] 128 [58]
42 54-1/2″ [1385] 22″ [560] 24″ [610] 19-1/2″ [496] 157 [71]
48 54-1/2″ [1385] 22″ [560] 24″ [610] 19-1/2″ [496] 157 [71]
60 54-1/2″ [1385] 22″ [560] 24″ [610] 19-1/2″ [496] 161 [73]

INSTALLATION

3.1 Vertical Upflow
Vertical Upflow configuration is the default factory setting on all models.
If return air is to be ducted, install the duct flush with the floor. Use a fireproof resilient gasket 1/8 to 1/4 in.
thick between the ducts, unit, and floor. Set the unit on the floor over the opening.
Torque applied to drain connections should not exceed 15ft.lbs.

MRCOOL HAH0 Series PSC Air Handler- connections

3.2 Vertical Downflow
Conversion to Vertical Downflow: A vertical upflow unit may be converted to vertical downflow. Remove the door and indoor coil and reinstall 180° from original position.
IMPORTANT: To comply with certification agencies and the National Electric Code for downflow application, the circuit breaker(s) on field-installed electric heater kits must be re-installed per procedure below so that the breaker switch’s “on” position and marking is up and its “off” position and marking is down.

  • To rotate breaker(s): rotate one breaker set (circuit) at a time starting with the one on the right. Loosen both lugs on the load side of the breaker. (Make sure that wires are identified and are reinstalled into the proper breaker.) Wires are bundled with wire ties, one bundle going to the right lug and one bundle going to the left lug.
  • Using a screwdriver or pencil, lift the white plastic tab with hole away from the breaker until the breaker releases from the mounting opening.
  • With breaker held in hand, rotate the breaker so that its “on” position is up, and its “off” position is down with the unit in its planned vertical mounting position. Insert right wire bundle into the top right breaker lug, ensuring all strands of all wires are inserted fully into the lug, and no wire insulation is in the lug.
  • Tighten lug as tight as possible while holding the circuit breaker. Check the wires and ensure each wire is secure and none are loose. Repeat for left wire bundle in the left top circuit breaker lug.
  • Replace breaker by inserting breaker mounting tab opposite the white pull tab in the opening. Hook the mounting tab over the edge in the opening.
  • With a screwdriver or pencil, pull the blue tab with hole away from the breaker while placing that side of the breaker into the opening. When breaker is in place, release the tab, locking the circuit breaker into place in the opening.
  • Repeat above operation for remaining breaker(s) (if more than one is provided).
  • Replace the single point wiring jumper bar, if it is used, on the line side of the breaker and tighten it securely.
  • Double-check all wires and lugs to make sure all are secure and tight. Check to make sure the unit wiring and circuit breaker load lugs match what is shown on the unit wiring diagram.

MRCOOL HAH0 Series PSC Air Handler- icon1 CAUTION
When using the unit with an electrical heater, the switch is used only for the electrical heater on the front of the panel.

3.3 Horizontal
Horizontal right is the default factory configuration for the units.
Horizontal left is not the default factory configuration for the units.
Conversion to Horizontal left: A vertical upflow unit may be converted to horizontal left by removing the indoor coil assembly and reinstalling the coil as shown for a left-hand air supply.

  • Rotate the unit into the downflow position, with the coil compartment on top and the blower compartment on bottom.
  • Reinstall the indoor coil 180° from its original position. Ensure the retaining channel is fully engaged with the coil rail.
  • Secondary drain pan kits are recommended when the unit is configured for the horizontal position over a finished ceiling and/or living space.

MRCOOL HAH0 Series PSC Air Handler- HorizontalMRCOOL HAH0 Series PSC Air Handler- Horizontal1

MRCOOL HAH0 Series PSC Air Handler- icon1 CAUTION
Horizontal units must be configured for right hand air supply or left hand air supply. Horizontal drain pan must be located under indoor coil. Failure to use the drain pan can result in property damage.
Conversion in Horizontal Direction: A unit with a horizontal right-hand supply can be changed to a horizontal left-hand supply by removing the indoor coil and reinstalling 180° from the original orientation.
3.4 Installation in an Unconditioned Space
IMPORTANT: There are two pairs of coil rails in the air handler for default and counter-flow application. If the air handler is installed in an unconditioned space, the two unused coil rails should be removed to minimize sweating on the air handler’s surface. The coil rails can be easily removed by taking off the 6 mounting screws from both sides of the cabinet.

ELECTRICAL WIRING

Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local ordinance.
MRCOOL HAH0 Series PSC Air Handler- icon WARNING
Disconnect all power to the unit before performing any installation or service. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.

4.1 Power Wiring
It is important that proper electrical power is available for connection to the unit model being installed. See the unit nameplate, wiring diagram, and electrical data in the installation instructions.

  • If required, install a branch circuit disconnect of adequate size, located within sight of, and readily available to the unit.
  • IMPORTANT: After the Electric Heater is installed, units may be equipped with one, two, or three 3060 amp. circuit breakers. These breaker(s) protect internal wiring in the event of a short circuit and serve as a disconnect. Circuit breakers installed within the  unit do not provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection.
  • Supply circuit power wiring must be 75°C minimum copper conductors only. See Electrical Data in this section for ampacity, wire size, and circuit protector requirement. Supply circuit protective devices may be either fuses or “HACR” type circuit breakers.
  • Power wiring may be connected to either the right side, left side, or top. Three 7/8″, 1-3/8″, 1-3/4″ dia. concentric knockouts are provided for connection of power wiring to unit.
  • Power wiring is connected to the power terminal block in the unit’s electrical cabinet.

4.2 Control Wiring
IMPORTANT: Class 2 low voltage control wiring should not be run in conduit with main power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used.

  • Low voltage control wiring should be 18 AWG colorcoded. For lengths longer than 100ft., 16 AWG wire should be used.
  • Low voltage control connections are made to low voltage pigtails extending from the top of the air handler.
  • Connections for control wiring are made with wire nuts. Control wiring knockouts (5/8″ & 7/8″) are also provided on the right and left side of the unit for a side connection.
  • See wiring diagrams attached to indoor and outdoor sections to be connected.
  • Make sure, after installation, separation of control wiring and power wiring has been maintained.

4.3 Grounding
MRCOOL HAH0 Series PSC Air Handler- icon WARNING
The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death.

  • Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet.
  • Grounding may also be accomplished by attaching the ground wire(s) to the ground lug(s) provided in the unit wiring compartment.
  • Ground lug(s) are located close to the wire entrance on the left side of the unit (upflow). Lug(s) may be moved to marked locations near the wire entrance on the right side of the unit (upflow), if an alternate location is more convenient.
  • Use of multiple supply circuits require grounding of each circuit to the lug(s) provided in the unit.

4.4 Electrical Data

Model Voltage Hertz HP Speeds Circuit Amps. Maximum Circuit Protector
18 208/230 60 1/5 3 1.9 15(A)
24 208/230 60 1/5 3 2.6 15(A)
30/36 208/230 60 1/3 3 3.2 15(A)
42/48 208/230 60 1/2 3 4.3 15(A)
60 208/230 60 3/4 3 4.4 15(A)
4.5 Electric Kit MCA/MOP Data
Heater Kit Model Used Air Handler Model Electric Heat (kW) Minimum Circuit Ampacity Max. Fuse or Breaker (HACR) Ampacity Fan Speed (AC/HP)
240V 208V 240V 208V Low Medium High
HHK-05 18 5 28.1 24.6 30 25
HHK-08 7.5 41.1 35.9 45 40
HHK-10 10 54.1 47.2 60 50
HHK-05 24 5 29 25.5 30 30
HHK-08 7.5 42 36.8 45 40
HHK-10 10 55 48.1 60 50
HHK-05 30 5 29.4 25.9 30 30
HHK-08 7.5 42.4 37.2 45 40
HHK-10 10 55.4 48.5 60 50
HHK-15 15 55.4/26.1 48.5/22.6 60/30 50/25
HHK-05 36 5 29.4 25.9 30 30
HHK-08 7.5 42.4 37.2 45 40
HHK-10 10 55.4 48.5 60 50
HHK-15 15 55.4/26.1 48.5/22.6 60/30 50/25
HHK-20 20 55.4/52.1 48.5/45.2 60/60 60/50
HHK-05 42 5 30.3 26.8 35 30
HHK-08 7.5 43.3 38.1 45 40
HHK-10 10 56.3 49.4 60 50
HHK-15 15 55.4/26.1 49.4/22.6 60/30 50/25
HHK-20 20 55.4/26.1 49.4/45.2 60/60 50/50
HHK-05 48 5 30.3 26.8 35 30
HHK-08 7.5 43.3 38.1 45 40
HHK-10 10 56.3 49.4 60 50
HHK-15 15 56.3/26.1 49.4/22.6 60/30 50/25
HHK-20 20 56.3/52.1 49.4/45.2 60/60 50/50
HHK-05 60 5 31.8 28.3 35 30
HHK-08 7.5 44.8 39.6 45 40
HHK-10 10 57.8 50.9 60 60
HHK-15 15 57.8/26.1 50.9/22.6 60/30 60/25
HHK-20 20 57.8/52.1 50.9/45.2 60/60 60/50
  • Heat kit suitable for AHU 4-way installation.
  • Ampacities for MCA and Fuse/breaker including the blower motor.
  • Heat pump systems require a specified air flow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.

AIRFLOW PERFORMANCE

Electric Heater Kits

No. Kit Description Ref. Air Handler Use
1 HHK-05 5kW Heat Strip 18/24/30/36/42/48/60
2 HHK-08 7.5kW Heat Strip 18/24/30/36/42/48/60
3 HHK-10 10kW Heat Strip 18/24/30/36/42/48/60
4 HHK-15 15kW Heat Strip, double breaker panel 30/36/42/48/60
5 HHK-20 20kW Heat Strip, double breaker panel 36/42/48/60

5 – Airflow Performance
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size.
External static applied to unit allows operation within the minimum and maximum limits shown in the table below for both cooling and electric heat operation.
For the 36K model, in order to achieve the AHRI 14.3 SEER2 system rating, the fan speed must be changed from Medium to High.

Airflow Performance Data

Model Size Motor Speed CFM Wet Coil Without Filter and Electric Heat
External Static Pressure-Inches W.C. [kPa]
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
 

 

 

 

 

18

 

Low

CFM 666 634 597 558 506 459 407 326 267
Watts 210 206 201 196 191 185 178 167 159
Current/A 0.92 0.89 0.88 0.86 0.84 0.82 0.79 0.75 0.72
 

Medium

CFM 855 835 791 744 705 657 586 528 464
Watts 240 237 232 227 222 215 207 200 191
Current/A 1.04 1.02 1.01 0.98 0.96 0.94 0.91 0.87 0.84
 

High

CFM 980 950 896 869 810 757 687 609 523
Power/W 308 302 298 293 282 273 262 252 240
Current/A 1.34 1.31 1.29 1.27 1.23 1.19 1.16 1.17 1.07
 

 

 

 

 

24

 

Low

CFM 999 953 905 847 757 681 610 543 411
Watts 316 310 306 302 288 279 270 256 240
Current/A 1.38 1.36 1.34 1.32 1.28 1.24 1.21 1.16 1.1
 

Medium

CFM 1176 1127 1086 1028 944 842 746 668 569
Watts 342 336 334 326 315 303 292 281 266
Current/A 1.49 1.47 1.45 1.42 1.38 1.33 1.29 1.25 1.19
 

High

CFM 1409 1359 1306 1253 1192 1108 986 870 743
Power/W 456 446 438 429 419 404 384 368 348
Current/A 2.01 1.96 1.93 1.9 1.86 1.8 1.73 1.67 1.61
 

 

 

 

 

30

 

Low

CFM 1028 985 930 859 781 712 649 571 468
Watts 362 353 345 335 323 313 303 290 276
Current/A 1.64 1.62 1.6 1.57 1.54 1.51 1.49 1.45 1.42
 

Medium

CFM 1315 1266 1208 1146 1065 981 866 775 686
Watts 406 399 392 385 372 361 344 331 320
Current/A 1.82 1.8 1.78 1.75 1.72 1.69 1.65 1.62 1.59
 

High

CFM 1532 1478 1421 1347 1284 1184 1082 932 805
Power/W 524 513 502 491 478 462 446 423 407
Current/A 2.39 2.36 2.34 2.31 2.28 2.23 2.2 2.14 2.11
 

Model Size

 

Motor Speed

CFM Wet Coil Without Filter and Electric Heat
External Static Pressure-Inches W.C. [kPa]
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
 

 

 

 

 

 

36

 

Low

CFM 1028 985 930 859 781 712 649 571 468
Watts 362 353 345 335 323 313 303 290 276
Current/A 1.64 1.62 1.6 1.57 1.54 1.51 1.49 1.45 1.42
 

Medium

CFM 1315 1266 1208 1146 1065 981 866 775 686
Watts 406 399 392 385 372 361 344 331 320
Current/A 1.82 1.8 1.78 1.75 1.72 1.69 1.65 1.62 1.59
 

High

CFM 1532 1478 1421 1347 1284 1184 1082 932 805
Power/W 524 513 502 490 478 462 446 423 407
Current/A 2.39 2.36 2.34 2.31 2.28 2.23 2.2 2.14 2.11
 

 

 

 

 

 

42

 

Low

CFM 1336 1310 1282 1234 1182 1140 1049 925 833
Watts 492 483 474 463 452 443 422 393 374
Current/A 2.24 2.22 2.17 2.13 2.1 1.93 2.03 1.9 1.87
 

Medium

CFM 1654 1610 1569 1510 1461 1394 1350 1265 1034
Watts 550 537 526 512 503 489 475 458 416
Current/A 2.4 2.38 2.35 2.32 2.3 2.18 2.16 2.08 2.04
 

High

CFM 1918 1875 1817 1771 1715 1651 1584 1511 1395
Power/W 717 703 686 670 652 635 617 600 570
Current/A 3.2 3.18 3.14 3.1 3.04 3 2.9 2.87 2.85
 

 

 

 

 

 

48

 

Low

CFM 1336 1310 1282 1234 1182 1140 1049 925 833
Watts 492 483 474 463 452 443 422 393 374
Current/A 2.24 2.22 2.17 2.13 2.1 1.93 2.03 1.9 1.87
 

Medium

CFM 1654 1610 1569 1510 1461 1394 1350 1265 1034
Watts 550 537 526 512 503 489 475 458 416
Current/A 2.4 2.38 2.35 2.32 2.3 2.18 2.16 2.08 2.04
 

High

CFM 1918 1875 1817 1771 1715 1651 1584 1511 1395
Power/W 717 703 686 670 652 635 617 600 570
Current/A 3.2 3.18 3.14 3.1 3.04 3 2.9 2.87 2.85
 

 

 

 

 

 

60

 

Low

CFM 1726 1693 1655 1637 1584 1500 1421 1328 1217
Watts 678 658 639 619 602 576 553 526 495
Current/A 2.95 2.87 2.78 2.69 2.62 2.52 2.42 2.31 2.18
 

Medium

CFM 1983 1933 1879 1828 1760 1685 1597 1507 1403
Watts 695 675 655 635 615 596 574 550 522
Current/A 3.02 2.93 2.85 2.76 2.67 2.59 2.5 2.4 2.28
 

High

CFM 2138 2086 2024 1952 1873 1797 1722 1646 1516
Power/W 793 773 751 726 702 679 658 638 604
Current/A 3.45 3.7 3.27 3.17 3.06 2.97 2.88 2.79 2.65
  • Shaded boxes represent airflow outside the required 300-450 cfm/ton, which are not recommended.
  • Airflow based on cooling performance at 230V with no electric heat and no filter.
  • The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures.
  • Heat pump systems require a specified airflow for electric heating to operate. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
  • Duct design and construction should be carefully completed. System performance can be lowered dramatically through bad planning or workmanship.
  • Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space.
    If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
  • The installers should balance the air distribution system to ensure proper  quiet airflow to all rooms in the home. This ensures a comfortable livingspace.
  • An air velocity meter or airflow hood can be used to balance and verify branch and system airflow (CFM).
  • IMPORTANT: If the 18K model is converted to downflow, the airflow must be between 350 and 450 cfm/ton. When used in a mobile home, the 42K model air volume should be no less than 1335 CFM. When used in a mobile home, the 48K model air volume  hould be no less than 1584 CFM.

DUCTWORK

Field ductwork must comply with the National Fire Protection Association NFPA 90A, NFPA90B, and any applicable local ordinance.

MRCOOL HAH0 Series PSC Air Handler- icon WARNING

  • Do not, under any circumstances, connect return ductwork to any other heat producing device such as a fireplace insert, stove, etc.
  • Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury, or property damage.

Sheet metal ductwork in unconditioned spaces must be insulated and covered with a vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance with SMACNA Construction Standard on Fibrous Glass Ducts. Ductwork must comply with National Fire Protection Association as tested by UL Standard 181 for Class I Air Ducts. Check local codes for requirements on ductwork and insulation.

  • The duct system must be designed within the range of external static pressure that the unit is designed to operate against. It is important that the system has adequate airflow. Make sure all supply and return ductwork, grills, special filters, accessories, etc. are accounted for in total resistance. See airflow performance tables in this manual.
  • Design the duct system in accordance with “ACCA” Manual “D” Design for Residential Winter and Summer Air Conditioning Equipment Selection. Latest editions are available from: “ACCA” Air Conditioning Contractors of America, 1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure pressure drop information (straight length plus all turns) shown in “ACCA” Manual “D” is accounted for in the system.
  • Supply plenum is attached to the 3/4″ duct flanges supplied with the unit. Attach flanges around the blower outlet.

IMPORTANT: If an elbow is included in the plenum close to the unit, it cannot be smaller than the dimensions of the supply duct flange on the unit.
IMPORTANT: The front flange on the return duct if connected to the blower casing must not be screwed into the area where the power wiring is located. Drills or sharp screw points can damage insulation on wires located inside the unit.

  • Secure the supply and return air ductwork to the unit flanges, using proper fasteners for the type of duct used and tape the duct-to-unit joint as required to prevent air leaks.

REFRIGERANT CONNECTIONS

Keep the coil connections sealed until refrigerant connections are made. See the installation instructions for the outdoor unit for details on the line sizing, tubing installation, and charging information.
Coil is shipped with nitrogen. Evacuate the system before charging with refrigerant.
Install refrigerant tubing so that it does not block service access to the front of the unit.
Nitrogen should flow through the refrigerant lines while brazing.
Use a brazing shield to protect the cabinet’s paint and a wet rag to protect the rubber grommet and input pipe’s piston seal ring from being damaged by torch flames. After the refrigerant connections are made, seal the gap around the connections with a pressure sensitive gasket.
After the work is finished, make sure to check that there is no vapor leak. After checking for vapor leaks, be sure to insulate the piping connections.

7.1 Condensate Drain Tubing
Consult local codes for specific requirements.

MRCOOL HAH0 Series PSC Air Handler- Tubing

MRCOOL HAH0 Series PSC Air Handler- icon WARNING
Use a wet rag to protect the two seal rings in the input pipe from being damaged by torch flames while brazing.

MRCOOL HAH0 Series PSC Air Handler- torch flames

IMPORTANT:

  1. When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, silicone, or Teflon tape and install. Hand tighten.
  2. When making drain fitting connections to the drain pan, do not over-tighten. Over-tightening fittings can split the pipe connections on the drain pan.
    • Install drain lines so they do not block service access to the front of the unit. Minimum clearance of 24 inches is requires for filter, coil, or blower removal and service access.
    • Make sure the unit is level or pitched slightly toward the primary drain connection so that water will drain completely from the pan.
    • Do not reduce drain line size less than the connection size provided on the condensate drain pan. Use 3/4″ PVC piping for drain piping connections.
    • All drain lines must be pitched downward away from the unit a minimum of 1/8″ per foot of line to ensure proper drainage.

AIR FILTER

  • Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or run the line to a safe outdoor area.
  • The drain line should be insulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line.
  • Make provisions for disconnecting and cleaning of the primary drain line, should it become necessary. Install a 3 inch trap in the primary drain line as close to the unit as possible. Make sure that the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
  • The auxiliary drain line should be run to a place where it will be noticeable if it becomes operational. The homeowner should be warned that a problem exists if water should begin running from the auxiliary drain line.
  • Plug the unused drain connection with the plugs provided in the parts bag, using a thin layer of Teflon paste, silicone, or Teflon tape to form a water tight seal.
  • Test condensate drain pan and drain line after installation is complete. Pour water into the drain pan, enough to fill the drain trap and line. Check to make sure the drain pan is draining completely, no leaks are found in the drain line fittings, and water is draining from the termination of the primary drain line.
  • Be sure to insulate the drain piping and drain socket since condensation may cause water leakage.
  • Be sure to install a drain trap at the drain outlet since the inside of the unit is at negative pressure to atmospheric pressure during operation.

8 – Air Filter
External filter or other means of filtration is required. Units should be sized for a maximum of 300 feet/min air velocity or what is recommended for the type of filter installed.
Filter application and placement are critical to airflow, which may affect the heating and cooling system performance.
Reduced airflow can shorten the life of the system’s major components, such as motor, limits, elements, heat relays, evaporator coil or compressor. Consequently, we recommend that the return air duct system have only one filter location. Systems with a return air filter grill or multiple filter grills can have a filter installed at each of the return air openings.
If adding high efficiency filters or electronic air filtration systems, it is very important that the air flow is not reduced. If air flow is reduced, the overall performance and efficiency of the unit will also be reduced. It is strongly recommended that a professional installation technician is contacted to ensure installation of these such filtration systems is performed correctly.
IMPORTANT: Do not double filter the return air duct system. Do not filter the supply air duct system. This will change the performance of the unit and reduce airflow.

MRCOOL HAH0 Series PSC Air Handler- icon WARNING
Do not operate the system without filters. A portion of the dust entrained in the air may temporarily lodge in the duct and run at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler elements. This residue could soil ceilings, walls, drapes, carpets, and other articles in the house.
Soot damage may occur with filters in place, when certain types of candles, oil lamps, or standing pilots are burned.

Filter Installation Dimensions

MRCOOL HAH0 Series PSC Air Handler- Filter

Model Filter Size in (mm) “W” in (mm) “D” in (mm) “H” in (mm) Return Width “A” in (mm) Return Length “B” in (mm)
18K 16X20 [406X508] 16.8[426] 20.4[518] 1[25.4] 19.6 14.8
24K/30K/36K 18X20[457X508] 18.3[466] 21.6[548] 1[25.4] 20.8 16.3
42K/48K/60K 20X22[508X559] 20.7[526] 23.9[608] 1[25.4] 23 18.8

Air Filter Removal

  1. Remove the bolts manually, and remove the air filter cover.
  2. Hold the edge of the air filter and extract out.
  3. Clean the air filter (A vacuum cleaner or plain water may be used to clean the air filter. If the dust accumulation is too heavy, use a soft brush and mild detergent to clean it and allow it to dry in a cool place.)
  4. Install the new filter so that the arrow on the filter is in the same direction as airflow.

MRCOOL HAH0 Series PSC Air Handler- Filter1

WIRING DIAGRAMS

9 – Wiring Diagram

MRCOOL HAH0 Series PSC Air Handler- Wiring Diagram

MRCOOL HAH0 Series PSC Air Handler- icon WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.

MRCOOL HAH0 Series PSC Air Handler- WIRING DIAGRAMS

Note: Description of Fan Speed Switch with PSC Motor

  1. The unit is factory-defaulted to medium speed.
  2. High Speed Wiring: Switch to high speed (black wire) and connect with FAN terminal, while medium speed (red wire) connects with the M2 terminal.
  3.  Low Speed Wiring: Switch to low speed (blue wire) and connect with FAN terminal, while medium speed (red wire) connects with the M1 terminal.
  4. For the 36K model, in order to make the AHRI 14.3 SEER2 system rating the fan speed must be changed from medium to high.
Fan Speed Terminal
Fan M1 M2
Medium Red Blue Black
High Black Blue Red
Low Blue Red Black

MRCOOL HAH0 Series PSC Air Handler- WIRING DIAGRAMS1

Note: When the unit does not contain PCB boards, the short lines in the accessory bag are not needed.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up to date wiring.

PISTON/TXV INSTALLATION

11 – Piston/TXV Installation
The coil comes with a factory-installed piston metering device. Some system combinations will require a different sized piston to be field-installed.

  • Contact MRCOOL support at 270-366-0457 to order the appropriate piston kit for your system combination.

A TXV may be required to achieve minimum efficiency ratings or for long refrigerant line set applications. Reference AHRI for system combination ratings.
The following table shows the factory-installed piston size for each model. Additional piston sizes are provided with the included accessories as necessary.

Model 50 52 56 58 60 64 68 70 73 75 80 83 90
18K X*
24K X*
30K X X X*
36K X X X*
42K X X*
48K X X*
60K X*

MRCOOL HAH0 Series PSC Air Handler- icon WARNING
Failure to install the proper piston can lead to poor system performance and possible compressor damage.

* means that this piston is pre-installed
The following table shows the optional TXV kit part numbers. Some combinations may require a TXV. See AHRI for system combination ratings.

Outdoor Unit Capacity (Tons) R410a TXV Kit
1.5-3 MHTXV1836
3.5-4 MHTXV4248
5 MHTXV6000

Charge the system by superheat when using a piston. Reference the outdoor unit installation guide to charge the system by subcooling when using a TXV.

Outdoor Temp (°F) Indoor Temperature (°F) Dry Bulb/Wet Bulb
95/79 90/75 85/71 80/67 75/63 70/58
Superheat (°F)
115 23 16 7 6 5 5
110 24 17 9 6 5 5
105 26 19 11 6 5 5
100 27 21 13 7 6 5
95 29 23 14 9 6 5
90 30 25 18 12 7 5
85 32 26 20 15 9 6
80 34 28 22 17 11 6
75 35 30 24 19 13 7
70 37 32 26 21 16 10
65 38 34 29 24 19 13
60 40 36 31 27 22 17
55 41 37 34 30 26 21

MRCOOL - logoPRODIRECT™ Series
PSC Air Handler
The design and specifications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.
mrcool.com

Documents / Resources

MRCOOL HAH0 Series PSC Air Handler [pdf] Owner's Manual
HAH018FPA, HAH024FPA, HAH036FPA, HAH048FPA, HAH060FPA, HAH0 Series PSC Air Handler, HAH0 Series, PSC Air Handler, Air Handler, Handler

References

Leave a comment

Your email address will not be published. Required fields are marked *