Parallel Operation with Remote Sensing
- Parallel operation is available by connecting the units shown as below (+S,-S and P are connected mutually in parallel) :
- The voltage difference among each output should be minimized that less than 0.2V is required.
- The total output current must not exceed the value determined by the following equation (Output current at parallel operation) =(The rated current per unit) x (Number of unit) x 0.9.
- In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
- When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
- When in parallel operation, the minimum output load should be greater than 3% of total output load. (Min. load > 3% rated current per unit x number of unit)