MEAN WELL NDR-120-12 Series 120W Single Output Industrial DIN RAIL
Product Information
The NDR-120 series is a 120W Single Output Industrial DIN RAIL power supply. It is designed for industrial applications and meets safety standards such as TPTC004 BS EN/EN62368-1 IEC62368-1. The power supply has three models: NDR-120-12 (12V), NDR-120-24 (24V), and NDR-120-48 (48V). It provides a rated current of 10A, 5A, and 2.5A respectively.
The power supply has a wide input voltage range of 90 ~ 264VAC or 127 ~ 370VDC, allowing for DC input operation by connecting AC/L(+) and AC/N(-). It has a frequency range of 47 ~ 63Hz and an efficiency of 85.5% to 89% depending on the model. The power supply is equipped with protection features such as over-load protection (OLP), over-temperature protection (OTP), over-current protection (OCP), and over-voltage protection (OVP).
Product Usage Instructions
- Choose the appropriate model of the NDR-120 series power supply based on your application requirements.
- Ensure that the input voltage is within the specified range of 90 ~ 264VAC or 127 ~ 370VDC.
- Connect the AC/L(+) and AC/N(-) terminals for AC input operation or connect the DC terminals for DC input operation.
- Make sure to follow the correct wiring assignment for the terminal pins. For TB1, connect Pin 1 to FG, Pin 2 to AC/N or DC, and Pin 3 to AC/L or DC+. For TB2, connect Pins 1 and 2 to DC OUTPUT -V and Pins 3 and 4 to DC OUTPUT +V.
- Mount the power supply on a DIN rail TS35/7.5 or TS35/15 using the provided mechanical specifications as a reference. Refer to the installation details in the instruction manual for proper installation.
- Refer to the provided link for the installation manual for additional guidance: http://www.meanwell.com/manual.html
Please note that this response is based on the information provided in the user manual extract. For complete and accurate instructions, it is recommended to refer to the full user manual or contact the manufacturer directly.
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/ServiceGiN.aspx
Description
NDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90 VAC to 264 VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-120 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between -20°C and 70°C under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make NDR-120 a very competitive power supply solution for industrial applications.
SPECIFICATION
MODEL | NDR-120-12 | NDR-120-24 | NDR-120-48 | |
OUTPUT |
DC VOLTAGE | 12V | 24V | 48V |
RATED CURRENT | 10A | 5A | 2.5A | |
CURRENT RANGE | 0 ~ 10A | 0 ~ 5A | 0 ~ 2.5A | |
RATED POWER | 120W | 120W | 120W | |
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 120mVp-p | 150mVp-p | |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load | |||
HOLD UP TIME (Typ.) | 16ms/230VAC 10ms/115VAC at full load | |||
INPUT |
VOLTAGE RANGE Note.6 | 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] | ||
FREQUENCY RANGE | 47 ~ 63Hz | |||
EFFICIENCY (Typ.) | 85.5% | 88% | 89% | |
AC CURRENT (Typ.) | 2.25A/115VAC 1.3A/230VAC | |||
INRUSH CURRENT (Typ.) | 20A/115VAC 35A/230VAC | |||
LEAKAGE CURRENT | <1mA / 240VAC | |||
PROTECTION |
OVERLOAD | 105 ~ 130% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 14 ~ 17V | 29 ~ 33V | 56 ~ 65V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | |||
ENVIRONMENT |
WORKING TEMP. | -20 ~ +70℃ (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | |||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | |||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | UL508, TUV BS EN/EN62368-1, EAC TP TC 004 approved;(meet BS EN/EN60204-1) | ||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020 | |||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),
BS EN/EN61204-3, heavy industry level, EAC TP TC 020 |
|||
OTHERS |
MTBF | 2636.8K hrs min. Telcordia SR-332 (Bellcore) ; 453.3K hrs min. MIL-HDBK-217F (25℃) | ||
DIMENSION | 40*125.2*113.5mm (W*H*D) | |||
PACKING | 0.6Kg; 20pcs/13Kg/1.16CUFT | |||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0. 1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7. The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft). % Product Liability Disclaimer : For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specifications
Terminal Pin No. Assignment (TB1)
Pin No. | Assignment |
1 | FG |
2 | AC/N or DC – |
3 | AC/L or DC + |
Terminal Pin No. Assignment (TB2)
Pin No. | Assignment |
1,2 | DC OUTPUT -V |
3,4 | DC OUTPUT+V |
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
Installation Manual
Please refer to http://www.meanwell.com/manual.html
Documents / Resources
![]() |
MEAN WELL NDR-120-12 Series 120W Single Output Industrial DIN RAIL [pdf] Owner's Manual NDR-120-12 Series 120W Single Output Industrial DIN RAIL, NDR-120-12 Series, 120W Single Output Industrial DIN RAIL, Single Output Industrial DIN RAIL, Output Industrial DIN RAIL, Industrial DIN RAIL |