MEAN WELL EDR-75-12 Single Output Industrial
Features
- Universal AC input/ Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 2 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTlN.aspx
Description
EDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90 VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. EDR-75 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20°C and 60°C under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-75 a very competitive power supply solution for industrial applications.
Model Encoding
SPECIFICATION
MODEL | EDR-75-12 | EDR-75-24 | EDR-75-48 | |
OUTPUT |
DC VOLTAGE | 12V | 24V | 48V |
RATED CURRENT | 6.3A | 3.2A | 1.6A | |
CURRENT RANGE | 0 ~ 6.3A | 0 ~ 3.2A | 0 ~ 1.6A | |
RATED POWER | 75.6W | 76.8W | 76.8W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p | |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load | |||
HOLD UP TIME (Typ.) | 60ms/230VAC 12ms/115VAC at full load | |||
INPUT |
VOLTAGE RANGE Note.6 | 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] | ||
FREQUENCY RANGE | 47 ~ 63Hz | |||
EFFICIENCY (Typ.) | 85.5% | 87.5% | 88.5% | |
AC CURRENT (Typ.) | 1.45A/115VAC 0.9A/230VAC | |||
INRUSH CURRENT (Typ.) | 20A/115VAC 35A/230VAC | |||
LEAKAGE CURRENT | <1mA / 240VAC | |||
PROTECTION |
OVERLOAD | 105 ~ 130% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 14 ~ 17V | 29 ~ 33V | 56 ~ 65V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | |||
ENVIRONMENT |
WORKING TEMP. | -20 ~ +60℃ (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | |||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | |||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | Ul508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS15598-1 approved;(meet BS EN/EN60204-1) | ||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS15936 Class A | |||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),
heavy industry level, EAC TP TC 020 |
|||
OTHERS | MTBF | 2777.2K hrs min. Telcordia SR-332 (Bellcore) ; 506.6K hrs min. MIL-HDBK-217F (25℃) | ||
DIMENSION | 32*125.2*102mm (W*H*D) | |||
PACKING | 0.51Kg; 28pcs/15.3Kg/1.22CUFT | |||
NOTE |
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Documents / Resources
![]() |
MEAN WELL EDR-75-12 Single Output Industrial [pdf] Installation Guide EDR-75-12, EDR-75-24, EDR-75-48, EDR-75-12 Single Output Industrial, EDR-75-12, Single Output Industrial, Output Industrial, Industrial |