 Features
Universal AC input / Full range Protections: Short circuit / Overload / Over voltage
/ Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508 (industrial control equipment) approved BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level 100% full load burn-in test 2 years warranty

 Applications
Industrial control system Semiconductor fabrication equipment Factory automation Electro-mechanical apparatus
 GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

 Description
EDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. EDR-75 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20 and 60 under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-75 a very competitive power supply solution for industrial applications.

 Model Encoding EDR - 75 - 12

Output voltage Output wattage Series name

File Name:EDR-75-SPEC 2024-05-06

75W Single Output Industrial DIN RAIL

EDR-75 series

SPECIFICATION

MODEL

EDR-75-12

EDR-75-24

EDR-75-48

DC VOLTAGE

12V

24V

48V

RATED CURRENT

6.3A

3.2A

1.6A

OUTPUT

CURRENT RANGE

0 ~ 6.3A

RATED POWER

75.6W

RIPPLE & NOISE (max.) Note.2 80mVp-p

VOLTAGE ADJ. RANGE

12 ~ 14V

0 ~ 3.2A 76.8W 120mVp-p 24 ~ 28V

0 ~ 1.6A 76.8W 150mVp-p 48 ~ 55V

VOLTAGE TOLERANCE Note.3 ±2.0%

±1.0%

±1.0%

LINE REGULATION

±0.5%

±0.5%

±0.5%

LOAD REGULATION

±1.0%

±1.0%

±1.0%

SETUP, RISE TIME

1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load

HOLD UP TIME (Typ.)

60ms/230VAC 12ms/115VAC at full load

VOLTAGE RANGE

Note.6 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]

FREQUENCY RANGE

47 ~ 63Hz

INPUT

EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

85.5% 1.45A/115VAC 20A/115VAC

0.9A/230VAC 35A/230VAC

87.5%

88.5%

LEAKAGE CURRENT

<1mA / 240VAC

OVERLOAD

105 ~ 130% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed

PROTECTION OVER VOLTAGE

14 ~ 17V

29 ~ 33V

Protection type : Shut down o/p voltage, re-power on to recover

56 ~ 65V

OVER TEMPERATURE

Shut down o/p voltage, re-power on to recover

WORKING TEMP. WORKING HUMIDITY

-20 ~ +60 (Refer to "Derating Curve") 20 ~ 95% RH non-condensing

ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH

TEMP. COEFFICIENT

±0.03%/ (0 ~ 50)

VIBRATION

Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

SAFETY STANDARDS

SAFETY &
EMC (Note 4)

WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC EMISSION

Ul508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS15598-1 approved;(meet BS EN/EN60204-1) I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS15936 Class A

EMC IMMUNITY

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020

MTBF OTHERS DIMENSION

2777.2K hrs min. Telcordia SR-332 (Bellcore) ; 506.6K hrs min. MIL-HDBK-217F (25) 32*125.2*102mm (W*H*D)

PACKING

0.51Kg; 28pcs/15.3Kg/1.22CUFT

NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1F & 47F parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it
still meets EMC directives.(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf ) 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with
full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than
2000m(6500ft).
 Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:EDR-75-SPEC 2024-05-06

75W Single Output Industrial DIN RAIL

EDR-75 series

Block Diagram

EMI FILTER

I/P

&

RECTIFIERS

FG

O.L.P. O.T.P.

POWER SWITCHING
PWM CONTROL

RECTIFIERS &
FILTER

O.C.P.
DETECTION CIRCUIT
O.V.P.

fosc : 85KHz
+V -V

Derating Curve

Static Characteristics

230VAC 100
80 115VAC
60 50 40
20

24V,48V(230VAC)
12V(230VAC) 12V,24V,48V(115VAC)

-20 -10 0 10

20

30

40 45 50

60 70 (VERTICAL)

AMBIENT TEMPERATURE ()

100 90 80 70 60 50 40
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz

LOAD (%) LOAD (%)

File Name:EDR-75-SPEC 2024-05-06

75W Single Output Industrial DIN RAIL
Mechanical Specification

EDR-75 series
Case No. Unit:mm

35 125.2

102 (12V,24V only)
(48V only) Side View
Installation Instruction

Top View 32
1234 TB2
DC OK +V ADJ.
TB1 123 Front View
Bottom View

Side View
Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 AC/N or DC 3 AC/L or DC +
Terminal Pin No. Assignment (TB2) Pin No. Assignment 1,2 DC OUTPUT -V 3,4 DC OUTPUT+V

35

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)

Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html

File Name:EDR-75-SPEC 2024-05-06


Acrobat Distiller 9.0.0 (Windows)