MEAN WELL logoDDR-30 series
30W DIN Rail Type DC-DC ConverterMEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC ConverterMEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Icon

Feature

  • Width only 35mm (2SU)
  • 4:1 ultra wide input range
  • -40-1-135°C wide working temperature
  • No minimum load required
  • DC output adjustable (±10%)
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit / Overload / Over voltage / Input reverse polarity / Input under voltage protection
  • 4KVdc I/O isolation(Reinforced isolation)
  • 3 years warranty

Applications

  • Industrial control system
  • Semi-conductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE
MW Search: http://www.meanuwell

Description

DDR-30 series is a 30W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (35mm), 4:1 ultra wide input voltage, -40-+85°C wide operating temperature, 4KVdc I/O isolation, adjustable output voltage (± 10%) and full protective functions…etc.
This series has two input options: 9-36V /18-75V and various output options: 5V / 12V / 15V / 24V and can be used for industrial control, security control, communication system and other fields. Suitable applications are DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.

Model Encoding

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Fig

MODEL DDR-30G-5 DDR-30G-12 DDR-30G-15 DDR-30G-24 DDR-30L-5 DDR-30L-12 DDR-30L-15 DDR-30L-24
OUTPUT DC VOLTAGE 5V 12V 15V 24V 5V 12V 15V 24V
RATED CURRENT 6A 25A 2A 1.25A 6A 2.5A 2A I.25A
CURRENT RANGE 0 ∼ 6A 0 ∼ 2.5A 0 ∼ 2A 0∼1.25A 0 ∼ 6A 0 ∼ 2.5A 0 ∼ 2A 0∼125A
RATED POWER 30W 30W 30W 30W 30W 30W 30W 30W
RIPPLE & NOISE (max.) Note.2 60mVp-p 75mVp-p 75mVp-p 100mVp-p 60mVp-p 75mVpb 75mVp-p 100mVp-p
VOLTAGEADJ. RANGE 4.5- 5.5V 9- 13.2V 13.5 – 16.5V 21.6 – 28V 4.5- 5.5V 9- 13.2V 13.5 – 16.5V 21.6- 28V
VOLTAGE TOLERANCE Nott3 ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0%
LINE REGULATION ±0.5% ±05% ±0.5% ±0.5% ±05% ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.5% ±05% ±0.5% ±0.5% ±15% ±0.5% ±0.5% ±0.5%
SETUP, RISE TIME 120ms, 85ms at full load
HOLD UP TIME (lyp.) G-type:7ms@24Vdc input L-type: 18ms@48Vdc input
EXTERNAL CAPACITANCE LOAD (Max.) 3300 μF 2200 μF 1500 μF 1000 μF 3300 μF 2200 μF 1500 μF 1000 μF
INPUT VOLTAGE RANGE Note.4 9∼36Vdc 18∼75Vdc
EFFICIENCY (Typ.) 85% 186% I87% 89% 86% I89% I90% I91%
DC CURRENT (Typ.) 1.5A/24Vdc 0.8A/48Vdc
INRUSH CURRENT (Typ.) 15A /24Vdc 15A /48Vdc
PROlECION OVERLOAD 110 – 150% rated output power
Protection type : Constait current limiting, recovers autanaticaly after fait condition is removed
OVER VOLTAGE 5.75∼7V 113.8∼16.2V 117 25∼20.29/ 128.8∼ 34V I S75 – 7V 113.8∼162V 117.25∼2025V 128.8∼34V
Protection type : Shutdown o/p voltage, re-power on to recover
REVERSE POLARITY By internal MOSFET, no damage, recovers automaticaly after fault coma lion removed
UNDER VOLTAGE LOCKOUT 24Vin (G-type):Power ON ≥ 9V , OFF ≥ 8.5V
48Vin (L-type):Power ON ≥ 18V , OFF ≥ 17V
ENYIKSMENT WORKING TEMP. -40 ∼ +85ºC (Refer to ‘Derating Curve,
WORKING HUMIDITY 5 ∼ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ∼ +85ºC .5 ∼ 95% RH non-condensng
TEMP. COEFFICIENT ±0.03%/ºC (0 ∼ 60ºC )
VIBRATION Component:10 -500Hz, 2G 1Ortin./1cyde, 60mki. each along X, Y, 2 axes; Mounting: Compiance to IEC600684-6
OPERATING ALTITUDE 5000 meters
SAFETY &
EMC (Note 5)
SAFETY STANDARDS HUI EC 62368-1 ,AS!NZS 62368.1 approved; Desigi refer to UL508
WITHSTAND VOLTAGE I/P-0/P:4KVdc
ISOLATION RESISTANCE I/P-01P>100M Ohms/ 500Vdc/ 25ºC/70% RH
EMC EMISSION Parameter Standard Test Level! Note
Conducted BS EN/EN55032 Class B
Radiated BS E N/E N55032 Class B
Voltage Flicker BS EN/EN61000-3-3
EMC IMMUNITY BS E N/E N55035 . BS E N/E N61000-6-2(BS EN/EN50382-2)
Parameter Standard Test Level! Note
ESD BS EN/EN61030-4.2 Level 3. 8IW air : Level 3. 6IW contact: criteriaA
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ;criteria A
EFT/ Burst BS E N/E N61030-4-4 Level 3. 2KV; criteria A
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line;criteria A
Conducted BS E N/E N61030-4-6 Level 3, WV ; critenaA
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ;criteria A
OTHERS MTBF 2780.3K hrsmn. Telcordia SR-332 (Be core) ;483.8K hrs min. MIL-HDBK-217F (25(:)
DIMENSION 35’90’54.5mrn (WH’D)
PACKING 0.12K9;96pcs/12.5K9/1.1CUFT
NOTE 1. All parameters NOT specially mentioned are measured at normal input (G24Vdc, L:48Vdc), rated load and 25’C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 of & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Denting may be needed under low input voltage. Please check the denting curve for more details
5. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives For guidance on how to perform these EMC tests, please refer to ‘EMI testing of component power supplies.” (as available on http://www.meanwell.com)
6. The ambient temperature denting of 3.5t/1000m with fanless models and of 5t/1000m with fan models for operating altitude higher than 2000m(6500ft).
Product Liability Disclaimer: For detailed information. please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Fig 1

Derating Curve

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Fig 2

Output derating VS input voltage

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Fig 2

Mechanical Specification
(Unit: mm , tolerance ± 0.5mm)

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Fig 4

Terminal Pin No. Assignment

Pin No. Assignment
1 DC Output   +Vo
2 DC Output   -Vo
3 DC Input     -Vin
4 DC Input     +Vin

Installation Manual
Please refer to: http://www.meanwell.com/manual.html

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - QR.https://www.meanwell.com/Upload/PDF/DDR%20DIN%20rail%20power%20supply.pdf

MEAN WELL logoDownloaded from Arrow.com.
File Name:DDR-30-SPEC 2022-09-20MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter - Icon 1

Documents / Resources

MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter [pdf] Instruction Manual
DDR-30 Series 30W DIN Rail Type DC-DC Converter, DDR-30 Series, 30W DIN Rail Type DC-DC Converter, Rail Type DC-DC Converter, DC-DC Converter, Converter
MEAN WELL DDR-30 Series 30W DIN Rail Type DC-DC Converter [pdf] Owner's Manual
DDR-30 Series 30W DIN Rail Type DC-DC Converter, DDR-30 Series, 30W DIN Rail Type DC-DC Converter, DIN Rail Type DC-DC Converter, Rail Type DC-DC Converter, DC-DC Converter, Converter

References

Leave a comment

Your email address will not be published. Required fields are marked *