MEAN WELL DDR-240 Series 240W DIN Rail Type DC-DC Converter

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-PRODUCT-IMAGE

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard
  • Width only 40mm
  • 2:1 wide input range
  • -40-+70C wide working temperature
  • 150% peak load capability
  • Current sharing up to 960W(3+1)
  • DC output adjustable
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Protections: Short circuit/ Overload/Over voltage / Over temperature/ Input reverse polarity/ Input under voltage protection
  • 4KVdc /O isolation(Reinforced isolation)
  • DC OK relay contact
  • Remote ON-OFF control
  • 3 years warranty

Applications

  • Bus,tram, metro or railway system
  • Industrial control system
  • Semi-conductor fabrication equipment
  • Factory automation
  • Electro-mechanical
  • Wireless network
  • Telecom or datacom system

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTiIN.asp

Description

DDR-240 series is a 240W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (40mm), 2:1 wide input voltage, finless design, -40~+70C wide operating temperature, 4KVdc /O isolation, 150% peak load, current sharing. DC OK, adjustable output voltage and full protective functions. This series of models has various input options: 16.8-33.6V /33.6-67.2V / 67.2-154V and two output options: 24V/48V and can be used for industrial & railway control, security control, communication system and other fields. Suitable applications include to DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.

Model encoding

 

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-01

Specification

MODEL DDR-240B-24 DDR-240B-48 DDR-240C-24 DDR-240C-48 DDR-240D-24 DDR-240D-48
 

 

 

 

 

 

OUTPUT

DC VOLTAGE 24V 48V 24V 48V 24V 48v
RATED CURRENT 10A 5A 10A 5A 10A 5A
CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 10A 0 ~ 5A 0 ~ 10A 0 ~ 5A
RATED POWER 240W 240W 240W 240W 240W 240W
PEAK CURRENT 15A 7.5A 15A 7.5A 15A 7.5A
POWER                Note.5 360W (3sec.)
RIPPLE & NOISE (max.) Note.2 80mVp-p 100mVp-p 80mVp-p 100mVp-p 80mVp-p 100mVp-p
VOLTAGE ADJ. RANGE 24 ~ 28V 48 ~ 56V 24 ~ 28V 48 ~ 56V 24 ~ 28V 48~ 56V
VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 500ms, 60ms
HOLD UP TIME (Typ.) Please refer to page 6 Hold up Time( Load de-rating curve )
 

 

INPUT

VOLTAGE RANGE Note.4 CONTINUOUS 16.8 ~ 33.6Vdc 33.6 ~ 67.2Vdc 67.2 ~ 154Vdc
100ms 14.4 ~ 16.8Vdc 28.8 ~33.6Vdc 66 ~ 67.2Vdc
EFFICIENCY (Typ.) 90% 90% 91% 92% 92% 92.5%
DC CURRENT (Typ.) 11.2A @24Vdc 5.6A @48Vdc 2.5A @110Vdc
INRUSH CURRENT (Typ.) 30A
INTERRUPTION OF VOLTAGE SUPPLY EN50155:2007-B/C- type comply with S2 level (10ms)@ 70% load ; D-type comply with S2 level (10ms)@ full load
EN50155:2017-Comply with S1 level
 

 

 

PROTECTION

OVERLOAD                         Note.5 Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135% rated output power with auto-recovery
OVER VOLTAGE 28.8 ~ 35V 57.6 ~ 65.0V 28.8 ~ 35V 57.6 ~ 65V 28.8 ~ 35V 57.6 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE Shut down o/p voltage, re-power on to recover
UNDER VOLTAGE LOCKOUT 24Vin (B – type) :Power ON≥16.8V ,

OFF≤16.5V

48Vin (C – type) :Power ON≥33.6V ,

OFF≤33V

110Vin (D – type):Power ON≥67.2V ,

OFF≤65V

 

FUNCTION

DC OK REALY CONTACT RATINGS (max.) 30Vdc/1A resistive load
CURRENT SHARING Up to 960W (3+1 units). Please refer to the Function Manual
REMOTE ON-OFF CONTROL Please refer to the Function Manual
 

 

ENVIRONMENT

WORKING TEMP. -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 5 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85, 5 ~ 95% RH non-condensing
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 55℃)
VIBRATION Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373
OPERATING ALTITUDE Note.7 5000 meters
 

 

 

 

 

 

SAFETY & EMC

(Note 6)

SAFETY STANDARDS IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved
WITHSTAND VOLTAGE I/P-O/P:4KVdc  I/P-FG:2.5KVdc  O/P-FG:0.71KVdc
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25℃/ 70% RH
 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted BS EN/EN55032 Class B
Radiated BS EN/EN55032 Class B
Voltage Flicker BS EN/EN61000-3-3 —–
Harmonic Current —– —–
 

 

 

 

EMC IMMUNITY

BS EN/EN55024 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 3, 8KV air ; Level 3, 6KV contact; criteria A
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
RAILWAY STANDARD Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC
 

OTHERS

MTBF 1415.6K hrs min.        Telcordia SR-332 (Bellcore) ; 189.9K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION 40*125.2*113.5mm (W*H*D)
PACKING 0.76Kg;20psc/16.2Kg/1.16CUFT
NOTE 1. All parameters NOT specialy mentoned are measured at normal input (B:24Vdc, C:48VdC, D:110VGC), rated ioad and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1 jef & 47 uf paralel capacitor. . lolerance: includes set up tolerance, line regulation and load regulaton. Derating may be needed under low input voltage. Please check the derating curve for more details. .3 seconds max., please reler to peak loading curves. . The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies (as available on http://www.meanwell.com) 7. The ambient temperature derating of 3.5 C/1000m with fanless models and of 5C/1000m with fan models for operating altitude higher than200Om(6500ft) Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
https://www.meanwell.com/serviceDisclaimer.aspx
Arrow .com. File Name:DDR-240-SPEC  2022-03-18

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-02

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
  1. Current sharing
    1. Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel) :
    2. The voltage difference among each output should be minimized that less than 0.2V is required.
    3. The total output current must not exceed the value determined by the following equation (Output current at parallel operation) =(The rated current per unit) x (Number of unit) x 0.9.
    4. In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
    5. When in parallel operation, the minimum output load should be greater than 3% of total output load. (Min. load > 3% rated current per unit x number of unit)
      MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-03
  2. Remote ON-OFF Control
    ※ The power supply can be turned ON-OFF by using the “Remote ON-OFF” function.
Remote ON-OFF (TB1 PIN2,4) Output Status
Open or 4 ~ 10VDC power supply ON
Short or 0 ~ 0.8VDC power supply OFF
Input face

There is one fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each
model are shown as below.

Type Fuse Type Reference and Rating
B Time-Lag Conquer MST, 10A, 250V *2
C Time-Lag Conquer MST, 6.3A, 250V *2
D Time-Lag Conquer MST, 6.3A, 250V *1
Input Under-Voltage Protection

If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input
voltage reaches above Vimin,please refer to the cruve below.

 

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-04

Input Reverse Polarity Protection

There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and
there will be no output to protect the unit.

Inrush Current

Inrush current is suppressed by a resistor during the initial start-up, and then the resistor is bypassed by a MOSFET to reduce power
consumption after accomplishing the start-up.

Hold-up Time

EN50155: 2007 version – B/C- type comply with S2 level (10ms)@ 70% load ; D-type comply with S2 level (10ms)@ full load, Please refer to the table and curves show below for the hold up time specification.

Load

Model

100% load 70% load other load
B type (24Vin) 6ms min. 10ms min. figure 1,2
C type (48Vin) 8ms min. 11ms min. figure 3,4
D type (110Vin) 11ms min. 15ms min. figure 5,6

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-05

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-06

Immunity to Environmental Conditions
Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

Temperature: -40℃ Dwell Time: 2 hrs/cycle No damage
 

Dry Heat Test

EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX)

EN 60068-2-2

Temperature: 70℃ / 85℃ Duration: 6 hrs / 10min  

PASS

 

Damp Heat Test, Cyclic

EN 50155 section 12.2.5

EN 60068-2-30

Temperature: 25℃~55℃ Humidity: 90%~100% RH Duration: 48 hrs  

PASS

Vibration Test EN 50155 section 12.2.11
EN 61373
Temperature: 19℃ Humidity: 65%

Duration: 10 mins

 

PASS

Increased Vibration Test EN 50155 section 12.2.11
EN 61373
Temperature: 19℃ Humidity: 65%
Duration: 5 hrs
 

PASS

 

Shock Test

EN 50155 section 12.2.11
EN 61373
Temperature: 21± 3℃
Humidity: 65 ± 5% Duration: 30ms*18
 

PASS

Low Temperature Storage Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

Temperature: -40℃ Dwell Time: 16 hrs  

PASS

Salt Mist Test EN 50155 section 12.2.10 (Class ST4) Temperature: 35℃±2℃ Duration: 96 hrs  

PASS

EN45545-2 Fire Test Conditions
Test Items Hazard Level
Items Standard HL1 HL2 HL3
 

 

 

R22

 

Oxygen index test

EN 45545-2:2013

EN ISO 4589-2:1996

 

PASS

 

PASS

 

PASS

 

Smoke density test

EN 45545-2:2013

EN ISO 5659-2:2006

 

PASS

 

PASS

 

PASS

 

Smoke toxicity test

EN 45545-2:2013 NF X70-100:2006  

PASS

 

PASS

 

PASS

 

R24

 

Oxygen index test

EN 45545-2:2013

EN ISO 4589-2:1996

 

PASS

 

PASS

 

PASS

 

R25

 

Glow-wire test

EN 45545-2:2013

EN 60695-2-11:2000

 

PASS

 

PASS

 

PASS

 

R26

 

Vertical flame test

EN 45545-2:2013

EN 60695-11:2003

 

PASS

 

PASS

 

PASS

Mechanical Specification

MEAN-WELL-DDR-240-Series-240W-DIN-Rail-Type-DC-DC-Converter-07

Installation Manual

Please refer to : http://www.meanwell.com/manual.html