MEAN WELL DDR-240B-24 240W DIN Rail Type DC DC Converter Instruction Manual

DDR-240B-24 240W DIN Rail Type DC DC Converter

Specifications

  • Model: DDR-240 series
  • Output Voltage: 24V/48V
  • Input Voltage:
    • B: 16.8~33.6Vdc
    • C: 33.6~67.2Vdc
    • D: 67.2~154Vdc
  • Rated Wattage: 240W
  • Peak Current: Up to 15A
  • Efficiency: Up to 92.5%
  • Operating Temperature: -40°C to +70°C
  • Protections: Short Circuit, Overload, Over Voltage, Over
    Temperature, Input Reverse Polarity, Input Under Voltage
  • Isolation: 4KVdc I/O (Reinforced isolation)
  • Additional Features: DC OK Relay Contact, Remote ON-OFF
    Control
  • Dimensions: Width only 40mm

Product Usage Instructions

Installation

The DC-DC Converter can be installed on DIN rail TS-35/7.5 or 15
for easy mounting in various applications.

Input/Output Connections

Ensure proper connections of the input and output voltages as
per the specified ranges for the model being used (B, C, or D
types).

Protections

Be aware of the various protection mechanisms in place such as
short circuit protection, overload protection, over voltage
protection, over temperature protection, input reverse polarity
protection, and input under voltage protection.

Remote Control

The DC-DC Converter supports remote ON-OFF control. Refer to the
Function Manual for detailed instructions on how to utilize this
feature.

Temperature Considerations

Operate the converter within the specified temperature range of
-40°C to +70°C. Refer to the derating curve for temperature vs.
load de-rating information.

FAQ

Q: What is the maximum power output of the DDR-240 series?

A: The DDR-240 series has a rated wattage of 240W with peak load
capability up to 15A.

Q: Can the DC-DC Converter be used in industrial control
systems?

A: Yes, the DC-DC Converter is suitable for various applications
including industrial control systems.

Q: What are the safety standards met by the DDR-240
series?

A: The DDR-240 series complies with IEC 62368-1, UL 62368-1, EAC
TP TC 004, AS/NZS 62368.1 safety standards.

“`

240W DIN Rail Type DC-DC Converter

DDR-240 series
User’s Manual

UL62368-1 AS/NZS62368-1 TPTC004 IEC62368-1
Features
Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard Width only 40mm 2:1 wide input range -40~+70 wide working temperature 150% peak load capability Current sharing up to 960W(3+1) DC output adjustable Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 Protections: Short circuit / Overload / Over voltage /
Over temperature / Input reverse polarity/ Input under voltage protection 4KVdc I/O isolation(Reinforced isolation) DC OK relay contact Remote ON-OFF control 3 years warranty

Applications
Bus,tram,metro or railway system Industrial control system Semi-conductor fabrication equipment Factory automation Electro-mechanical Wireless network Telecom or datacom system
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description
DDR-240 series is a 240W DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra slim width (40mm), 2:1 wide input voltage, fanless design, -40~+70 wide operating temperature, 4KVdc I/O isolation, 150% peak load, current sharing,DC OK, adjustable output voltage and full protective functions. This series of models has various input options: 16.8~33.6V / 33.6~67.2V / 67.2~154V and two output options: 24V / 48V and can be used for industrial & railway control, security control, communication system and other fields. Suitable applications include to DC buck/boost regulator, increasing system insulation level and voltage drop compensation along cable…etc.
Model Encoding DDR – 240 B – 24

Output voltage(24/48Vdc) Input voltage (B:16.8~33.6Vdc, C:33.6~67.2Vdc, D:67.2~154Vdc) Rated wattage Series name

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter

DDR-240 series

SPECIFICATION

MODEL

DDR-240B-24

DDR-240B-48

DDR-240C-24

DDR-240C-48

DDR-240D-24

DDR-240D-48

OUTPUT

DC VOLTAGE

24V

48V

24V

RATED CURRENT

10A

5A

10A

CURRENT RANGE

0 ~ 10A

0 ~ 5A

0 ~ 10A

RATED POWER

240W

240W

240W

PEAK CURRENT

15A

7.5A

15A

POWER

Note.5 360W (3sec.)

RIPPLE & NOISE (max.) Note.2 80mVp-p

100mVp-p

80mVp-p

VOLTAGE ADJ. RANGE

24 ~ 28V

48 ~ 56V

24 ~ 28V

VOLTAGE TOLERANCE Note.3 ±1.0%

±1.0%

±1.0%

LINE REGULATION

±0.5%

±0.5%

±0.5%

LOAD REGULATION

±1.0%

±1.0%

±1.0%

SETUP, RISE TIME

500ms, 60ms

HOLD UP TIME (Typ.)

Please refer to page 6 Hold up Time( Load de-rating curve )

48V 5A 0 ~ 5A 240W 7.5A
100mVp-p 48 ~ 56V ±1.0% ±0.5% ±1.0%

24V 10A 0 ~ 10A 240W 15A
80mVp-p 24 ~ 28V ±1.0% ±0.5% ±1.0%

48v 5A 0 ~ 5A 240W 7.5A
100mVp-p 48~ 56V ±1.0% ±0.5% ±1.0%

INPUT

VOLTAGE

CONTINUOUS

RANGE Note.4 100ms

EFFICIENCY (Typ.)

90%

16.8 ~ 33.6Vdc 14.4 ~ 16.8Vdc
90%

33.6 ~ 67.2Vdc

28.8 ~33.6Vdc

91%

92%

67.2 ~ 154Vdc

66 ~ 67.2Vdc

92%

92.5%

DC CURRENT (Typ.)

11.2A @24Vdc

5.6A @48Vdc

2.5A @110Vdc

INRUSH CURRENT (Typ.) 30A

INTERRUPTION OF VOLTAGE SUPPLY EN50155:2021-Comply with S1 level

OVERLOAD

Normally works within 150% rated output power for more than 3 seconds and then constant current protection 105~135% Note.5 rated output power with auto-recovery

OVER VOLTAGE PROTECTION
OVER TEMPERATURE

28.8 ~ 35V

57.6 ~ 65.0V

28.8 ~ 35V

Protection type : Shut down o/p voltage, re-power on to recover

Shut down o/p voltage, re-power on to recover

57.6 ~ 65V

28.8 ~ 35V

57.6 ~ 65V

UNDER VOLTAGE LOCKOUT

24Vin (B – type) :Power ON16.8V , OFF16.5V

48Vin (C – type) :Power ON33.6V , OFF33V

110Vin (D – type):Power ON67.2V , OFF65V

DC OK REALY CONTACT RATINGS (max.) 30Vdc/1A resistive load

FUNCTION CURRENT SHARING

Up to 960W (3+1 units). Please refer to the Function Manual

REMOTE ON-OFF CONTROL Please refer to the Function Manual

WORKING TEMP.

-40 ~ +70 (Refer to “Derating Curve”)

WORKING HUMIDITY

5 ~ 95% RH non-condensing

ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 5 ~ 95% RH non-condensing

TEMP. COEFFICIENT

±0.03%/ (0 ~ 55)

VIBRATION

Component:10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC61373

OPERATING ALTITUDE Note.7 5000 meters

SAFETY STANDARDS

IEC 62368-1, UL 62368-1, EAC TP TC 004, AS/NZS 62368.1 approved

WITHSTAND VOLTAGE

I/P-O/P:4KVdc I/P-FG:2.5KVdc O/P-FG:0.71KVdc

ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500Vdc / 25/ 70% RH

Parameter

Standard

Test Level / Note

Conducted

BS EN/EN55032

Class B

EMC EMISSION

Radiated

BS EN/EN55032

Class B

SAFETY &
EMC (Note 6)

Voltage Flicker

BS EN/EN61000-3-3

—–

Harmonic Current

—–

—–

BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)

Parameter

Standard

Test Level / Note

ESD

BS EN/EN61000-4-2

Level 3, 8KV air ; Level 3, 6KV contact; criteria A

Radiated

BS EN/EN61000-4-3

Level 3, 10V/m ; criteria A

EMC IMMUNITY

EFT / Burst Surge

BS EN/EN61000-4-4 BS EN/EN61000-4-5

Level 3, 2KV ; criteria A Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A

Conducted

BS EN/EN61000-4-6

Level 3, 10V ; criteria A

Magnetic Field

BS EN/EN61000-4-8

Level 4, 30A/m ; criteria A

RAILWAY STANDARD

Compliance to BS EN/EN45545-2 for fire protection ; Meet BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC

MTBF

1415.6K hrs min. Telcordia SR-332 (Bellcore) ; 189.9K hrs min. MIL-HDBK-217F (25)

OTHERS DIMENSION

40*125.2*113.5mm (W*H*D)

PACKING

0.76Kg;20psc/16.2Kg/1.0CUFT

1. All parameters NOT specially mentioned are measured at normal input (B:24Vdc , C:48Vdc , D:110Vdc ) , rated load and 25 of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1F & 47F parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. Derating may be needed under low input voltage. Please check the derating curve for more details.

NOTE

5. 3 seconds max., please refer to peak loading curves. 6. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with

the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf ) 7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than2000m(6500ft).

Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter Block Diagram

DC I/P FG
ON/OFF

EMI FILTER

POWER SWITCHING

O.L.P.
Remote Control

PWM CONTROL

DDR-240 series

RECTIFIERS &
FILTER
O.V.P.
DETECTION CIRCUIT
CURRENT SHARE

fosc : 80KHz DC OK +Vo -Vo
P+ P-

Derating Curve

150

120

For 3 sec. (typ.)

100

Continuous 40

-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 (VERTICAL)
AMBIENT TEMPERATURE ()

Output derating VS input voltage

100

90

80

C/D Type

70

B Type

60

50

40

B Type: 16.8

21.6

33.6

C Type: 33.6

43.2

67.2

D Type: 67.2

86.4

154

INPUT VOLTAGE (V)

LOAD (%) LOAD (%)

Peak Loading
( 1 ) 360W (150% load)

240W (100% load)

100 sec.

3 sec.

( 2 ) 360W (150% load)
120W (50% load) 10 sec. 3 sec.

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter

DDR-240 series

DC OK Relay Contact

Contact Close Contact Open Contact Ratings (max.)

PSU turns on / DC OK. PSU turns off / DC Fail. 30V/1A resistive load.

Function Manual
1. Current sharing (1) Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel) : (2) The voltage difference among each output should be minimized that less than 0.2V is required. (3) The total output current must not exceed the value determined by the following equation (Output current at parallel operation) =(The rated current per unit) x (Number of unit) x 0.9. (4) In parallel operation 4 units is the maximum, please consult the manufacture for other applications. (5) When in parallel operation, the minimum output load should be greater than 3% of total output load. (Min. load > 3% rated current per unit x number of unit)

+ LOAD –

+V DC OK
-V P- P+ Vo Adj. + DC OK
PSU

+V DC OK
-V P- P+ Vo Adj. + DC OK
PSU

+V DC OK
-V P- P+ Vo Adj. + DC OK
PSU

+V DC OK
-V P- P+ Vo Adj. + DC OK
PSU

2. Remote ON-OFF Control The power supply can be turned ON-OFF by using the “Remote ON-OFF” function.

Remote ON-OFF (TB1 PIN2,4) Open or 4 ~ 10VDC Short or 0 ~ 0.8VDC

Output Status
power supply ON power supply OFF

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter

DDR-240 series

Input Fuse

There is one fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each model are shown as below.

Type

Fuse Type

B

Time-Lag

C

Time-Lag

D

Time-Lag

Reference and Rating Conquer MST, 10A, 250V *2 Conquer MST, 6.3A, 250V *2 Conquer MST, 6.3A, 250V *1

Input Under-Voltage Protection
If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input voltage reaches above Vimin,please refer to the cruve below.

DDR-240B-24 Vo 30
25

20

15

Turn On

Turn Off 10

5

16.5

16.8

0

Vin

15 16 17 18 19 20

DDR-240C-24 Vo 30
25

20

15

Turn On

Turn Off 10

5

33.6

0

Vin

31 33 34 35 36 37

DDR-240D-24

Vo 30 25

20

15

Turn On

Turn Off 10

5

65

67.2

0

Vin

65 66 67 68 69 70

Input Reverse Polarity Protection
There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and there will be no output to protect the unit.

Inrush Current
Inrush current is suppressed by a resistor during the initial start-up, and then the resistor is bypassed by a MOSFET to reduce power consumption after accomplishing the start-up.

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter Hold-up Time

DDR-240 series

LOAD

Model

Load

B type (24Vin)

C type (48Vin)

D type (110Vin)

100% load
6ms min. 8ms min. 11ms min.

70% load
10ms min. 11ms min. 15ms min.

other load
figure 1,2 figure 3,4 figure 5,6

DDR-240B-24

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms

50ms 60ms 70ms 80ms

TIME (figure 1)

DDR-240C-24

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms

50ms 60ms 70ms 80ms

TIME (figure 3)

DDR-240D-24

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms 50ms 60ms 70ms 80ms 90ms 100ms 110ms 120ms 130ms
TIME
(figure 5)

LOAD

LOAD

LOAD

DDR-240B-48

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms

50ms 60ms 70ms 80ms

TIME (figure 2)

DDR-240C-48
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms 50ms 60ms 70ms 80ms90ms 100ms
TIME (figure 4)
DDR-240D-48

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
0ms 10ms 20ms 30ms 40ms 50ms 60ms 70ms 80ms 90ms 100ms 110ms 120ms
TIME (figure 6)

LOAD

LOAD

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter

DDR-240 series

Efficiency vs Load & Vin Curve
The efficiency vs load & Vin curves of each model are shown as below.

EFFICIENCY

DDR-240B-24

94% 92% 90% 88% 86% 84% 82% 80%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

33.6Vdc 24Vdc 16.8Vdc

EFFICIENCY

DDR-240B-48

94% 92% 90% 88% 86% 84% 82% 80%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

33.6Vdc 24Vdc 16.8Vdc

EFFICIENCY

DDR-240C-24

95% 90% 85% 80% 75% 70%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

6 7 .2 V dc 48Vdc 3 3 .6 V dc

EFFICIENCY

DDR-240C-48

95% 90% 85% 80% 75% 70%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

6 2 .4 V dc 48Vdc 3 3 .6 V dc

EFFICIENCY

DDR-240D-24

95% 90% 85% 80% 75% 70% 65%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

154Vdc 110Vdc 6 7 .2 V dc

EFFICIENCY

DDR-240D-48

95% 90% 85% 80% 75% 70%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

154Vdc 110Vdc 67.2V dc

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter

Immunity to Environmental Conditions
Test method

Standard

Dry Heat Test

EN 50155 section 13.4.5

Damp Heat Test, Cyclic

EN 50155 section 13.4.8

Vibration Test

EN 50155 section 13.4.10

Shock Test

EN 50155 section 13.4.10

Low Temperature Storage Test EN 50155 section 13.4.6

Salt Mist Test

EN 50155 section 13.4.13

DDR-240 series

Test conditions
Temperature: 70 / 85 Duration: 6 hrs / 10min
Temperature: 25~55 Humidity: 90%~100% RH Duration: 48 hrs Temperature: 19 Humidity: 65% Duration: 10 mins Temperature: 21± 3 Humidity: 65 ± 5% Duration: 30ms*18
Temperature: -40 Dwell Time: 16 hrs
Temperature: 35±2 Duration: 96 hrs

Status PASS PASS PASS PASS PASS PASS

EN45545-2 Fire Test Conditions

PCB
Potting Termina; block

Test Items

Items

Standard

Oxygen index test

EN 45545-2:2020 EN ISO 4589-2:2017

R22 Smoke density test

EN 45545-2:2020 EN ISO 5659-2:2017

Smoke toxicity test

EN 45545-2:2020 EN 17084:2018

R24 Oxygen index test R25 Glow-wire test

EN 45545-2:2020 EN ISO 4589-2:2017
EN 45545-2:2020 EN 60695-2-11:2014

R24 Oxygen index test

EN 45545-2:2020 EN ISO 4589-2:2017

R26 Vertical flame test

EN 45545-2:2020 EN 60695-11-10:2013

HL1 PASS PASS PASS PASS PASS PASS PASS

Hazard Level HL2 PASS PASS PASS PASS PASS PASS PASS

HL3 PASS PASS PASS PASS PASS PASS PASS

File Name:DDR-240-SPEC 2025-07-18

240W DIN Rail Type DC-DC Converter
Mechanical Specification
(Unit: mm , tolerance ± 1mm)

DDR-240 series
Case No.265A-D

35
125.2

113.5
Side View
Installation Instruction

Top View
40
1234 5678

Vo Adj. + DC OK

TB2 TB3

Terminal Pin No. Assignment (TB2,TB3) Pin No. Assignment 1,2 DC output +Vo 5,6 DC output -Vo 3,4 DC OK Relay Contact 7,8 P+,P-

TB1 123 4
Front View

Side View
Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 DC input -Vin 3 DC input +Vin 4 Remote ON/OFF

Bottom View

35

This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)

Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html

File Name:DDR-240-SPEC 2025-07-18