Goodman GMES96/GCES96 Single-Stage, Multi-Speed ECM Gas Furnace
Heating Input: 40,000–120,000 BTU/H
AFUE: Up to 96%
ENERGY STAR® Certified
Overview
Standard Features
- Heavy-duty aluminized-steel tubular heat exchanger
- Stainless-steel secondary heat exchanger
- Single-stage gas valve
- Durable Silicon Nitride igniter
- Quiet single-speed induced draft blower
- Self-diagnostic control board with constant memory fault code history output to a LED
- All models comply with California 40 ng/J Low NOx emissions standard
- Note: Installation in California's South Coast Air Quality Management District (SCAQMD) is not permitted on or after October 1, 2019.
- AHRI Certified; ETL Listed
Cabinet Features
- Designed for multi-position installation: GMES96 (upflow, horizontal left or right), GCES96 (downflow, horizontal left or right)
- Certified for direct vent (2-pipe) or non-direct vent (1-pipe)
- Easy-to-install top venting with optional side venting (GMES96/upflow models only)
- Convenient left or right connection for gas and electrical service
- Cabinet air leakage (QLeak) ≤ 2%
- Heavy-gauge steel cabinet with durable finish
- Fully insulated heat exchanger and blower section
- Airtight solid bottom or side return with easy-cut tabs for effortless removal in bottom air-inlet applications
Nomenclature
The model number provides detailed information about the furnace configuration. The structure is:
G - M - E - S - 96 - 060 - 3 - B - N - **
- G: Brand (Goodman® Brand)
- M/C: Configuration (M = Upflow/Horizontal, C = Downflow/Horizontal)
- E: Motor (Multi-Speed ECM)
- S: Gas Valve (Single Stage)
- 96: AFUE (96%)
- 060: MBTU/h (060 = 60,000 BTU/h; other values include 040, 120)
- 3: Maximum CFM (3 = 1200 CFM; other values include 2, 4, 5)
- B: Cabinet Width (B = 17½"; other values include A=14", C=21", D=24½")
- N: NOx (N = Low NOx)
- **: Engineering (Major/Minor Revisions - not used for inventory control)
Product Specifications
GMES96 Series
| Model | Heating Data: High Fire Input¹ (BTU/h) | Heating Data: High Fire Output¹ (BTU/h) | AFUE² (%) | Temperature Rise Range (°F) | Vent Diameter³ | No. of Burners | Circulator Blower: Available AC @ 0.5" ESP | Circulator Blower: Size (D x W) | Circulator Blower: Horsepower @ 1075 RPM | Circulator Blower: Speed | Filter Size (in²) (Qty) | Electrical Data: Min. Circuit Ampacity⁴ (A) | Electrical Data: Max. Overcurrent Device (amps)⁵ | Shipping Weight (LBS) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GMES96 0403AN | 40,000 | 38,440 | 96 | 25-55 | 2"-3" | 2 | 1.5-3 | 11" x 6" | 1/2 | 5 | (1) 16x25 (side) or (1) 14 X 25 (bottom) | 9.3 | 15 | 106 |
| GMES96 0603BN | 60,000 | 57,660 | 96 | 35-65 | 2"-3" | 3 | 1.5-3 | 11" x 8" | 1/2 | 5 | (1) 16x25 (side or bottom) | 9.6 | 15 | 111 |
| GMES96 0803BN | 80,000 | 76,880 | 96 | 35-65 | 2"-3" | 4 | 1.5-3 | 11" x 8" | 1/2 | 5 | (1) 16x25 (side or bottom) | 9.6 | 15 | 114 |
| GMES96 0804CN | 80,000 | 76,880 | 96 | 25-55 | 2"-3" | 4 | 1.5-4 | 11" x 10" | 3/4 | 5 | (1) 16x25 (side or bottom) | 12.8 | 15 | 116 |
| GMES96 0805CN | 80,000 | 76,880 | 96 | 25-55 | 2"-3" | 4 | 3-5 | 11" x 10" | 1 | 5 | (1) 20 x 25 (bottom) or (2) 16 x 25 (side) | 11.7 | 15 | 139 |
| GMES96 1005CN | 100,000 | 96,100 | 96 | 30-60 | 2"-3" | 5 | 3-5 | 11" x 10" | 1 | 5 | (1) 20 x 25 (bottom) or (2) 16 x 25 (side) | 13.7 | 15 | 140 |
| GMES96 1205DN | 120,000 | 115,320 | 96 | 35-65 | 3" | 6 | 3-5 | 11" x 11" | 1 | 5 | (1) 20 x 25 (bottom) or (2) 16 x 25 (side) | 13.7 | 15 | 154 |
GCES96 Series
| Model | Heating Data: High Fire Input¹ (BTU/h) | Heating Data: High Fire Output¹ (BTU/h) | AFUE² (%) | Temperature Rise Range (°F) | Vent Diameter³ | No. of Burners | Circulator Blower: Available AC @ 0.5" ESP | Circulator Blower: Size (D x W) | Circulator Blower: Horsepower @ 1075 RPM | Circulator Blower: Speed | Filter Size (in²) (Qty) | Electrical Data: Min. Circuit Ampacity⁴ (A) | Electrical Data: Max. Overcurrent Device (amps)⁵ | Shipping Weight (LBS) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GCES96 0403BN | 40,000 | 38,440 | 96 | 25-55 | 2"-3" | 2 | 1.5-3 | 11" x 8" | 1/2 | 5 | (2) 10 x 20 or (1) 16 x 25 (top return) | 10.3 | 15 | 113 |
| GCES96 0603BN | 60,000 | 57,660 | 96 | 35-65 | 2"-3" | 3 | 1.5-3 | 11" x 8" | 1/2 | 5 | (2) 10 x 20 or (1) 16 x 25 (top return) | 10.3 | 15 | 116 |
| GCES96 0804CN | 80,000 | 76,880 | 96 | 40-70 | 2"-3" | 4 | 2.5-4 | 11" x 10" | 3/4 | 5 | (2) 10 x 20 or (1) 16 x 25 (top return) | 14.1 | 15 | 141 |
| GCES96 1005CN | 100,000 | 95,000 | 95 | 40-70 | 2"-3" | 5 | 3-5 | 11" x 10" | 1 | 5 | (1) 14 x 20 (bottom) or (1) 20 x 25 (top return) | 16.93 | 20 | 144 |
| GCES96 1205DN | 120,000 | 114,000 | 95 | 45-75 | 3" | 6 | 3-5 | 11" x 11" | 1 | 5 | (1) 14 x 20 (bottom) or (1) 20 x 25 (top return) | 16.93 | 20 | 156 |
Notes for Specifications:
1. Natural Gas BTU/h.
2. DOE AFUE based upon Isolated Combustion System (ICS).
3. Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2" or 3" in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2" or 3" diameter PVC.
4. Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
5. Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size. May use fuses or HACR-type circuit breakers of the same size as noted.
All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply. Gas Service Connection is 1½" FPT.
Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all existing local codes.
For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance and noise issues.
For servicing or cleaning, a 24" front clearance is required. Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above. In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.
Dimensions
The following diagrams illustrate the dimensions and clearances for the GMES96 and GCES96 furnaces.
GMES96 Dimensions
Diagram Description: The diagrams show the Left Side View, Front View, and Right Side View of the GMES96 furnace, indicating dimensions for air discharge, air intake, electrical outlets, gas supply, and drain trap connections. Key dimensions A, B, C, D, E are labeled on the Front View.
| Model | Heating Capacity (Input BTU/h) | Heating Capacity (Output BTU/h) | AFUE % | Tons A/C 2 | Dimensions: W" | Dimensions: D" | Dimensions: H" | Ship Weight (LBS) |
|---|---|---|---|---|---|---|---|---|
| GMES960403AN | 40,000 | 38,400 | 96 | 3 | 14" | 28% | 34% | 108 |
| GMES960603BN | 60,000 | 57,600 | 96 | 3 | 17% | 28% | 34% | 118 |
| GMES960803BN | 80,000 | 76,800 | 96 | 3 | 17% | 28% | 34% | 118 |
| GMES960804CN | 80,000 | 76,800 | 96 | 4 | 21" | 28% | 34% | 141 |
| GMES960805CN | 80,000 | 76,800 | 96 | 5 | 21" | 28% | 34% | 142 |
| GMES961005CN | 100,000 | 96,000 | 96 | 5 | 21" | 28% | 34% | 144 |
| GMES961205DN | 120,000 | 115,200 | 96 | 5 | 24% | 28% | 34% | 156 |
GMES96 Minimum Clearances to Combustible Materials
| Position | SIDES | REAR | FRONT | BOTTOM | FLUE | TOP |
|---|---|---|---|---|---|---|
| Upflow | 0" | 0" | 3" | C | 0" | 1" |
| Horizontal | 6" | 0" | 3" | C | 0" | 6" |
Note: C = If placed on combustible floor, the floor MUST be wood ONLY.
GCES96 Dimensions
Diagram Description: The diagrams show the Left Side View, Front View, and Right Side View of the GCES96 furnace, indicating dimensions for air discharge, air intake, electrical outlets, gas supply, and drain trap connections. Key dimensions A, B, C, D, E are labeled on the Front View.
| Model | Heating Capacity (Input BTU/h) | Heating Capacity (Output BTU/h) | AFUE % | Tons A/C 2 | Dimensions: W" | Dimensions: D" | Dimensions: H" | Ship Weight (LBS) |
|---|---|---|---|---|---|---|---|---|
| GCES960403BN | 40,000 | 38,440 | 96 | 2 | 17% | 28% | 34% | 113 |
| GCES960603BNA | 60,000 | 57,660 | 96 | 3 | 17% | 28% | 34% | 116 |
| GCES960804CN | 80,000 | 76,880 | 96 | 4 | 21" | 28% | 34% | 141 |
| GCES961005CN | 100,000 | 95,000 | 95 | 5 | 21" | 28% | 34% | 144 |
| GCES961205DN | 120,000 | 114,000 | 95 | 5 | 24% | 28% | 34% | 156 |
GCES96 Minimum Clearances to Combustible Materials
| Position | SIDES | REAR | FRONT | BOTTOM | FLUE | TOP |
|---|---|---|---|---|---|---|
| Downflow | 0" | 0" | 3" | NC | 0" | 1" |
| Horizontal | 6" | 0" | 3" | C | 0" | 6" |
Note: C = If placed on combustible floor, the floor MUST be wood ONLY. NC = For installation on non-combustible floors only. A combustible floor sub-base must be used for installations on combustible flooring.
Airflow Specifications
The following tables provide detailed airflow data (CFM) and temperature rise (RISE) versus external static pressure for various models and dip switch settings.
GMES96 Heating Airflow Data
| Model | DIP SWITCHES S2-1, S2-2 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | ||
| GMES96 0403A | OFF OFF | 715 | 50 | 666 | 53 | 609 | N/A | 558 | N/A | 500 | N/A | 438 | 386 | 333 | N/A | N/A | N/A | N/A | N/A | ||
| ON OFF* | 1110 | 32 | 1081 | 33 | 1042 | 34 | 1003 | 35 | 965 | 37 | 933 | 893 | 856 | 820 | 803 | N/A | N/A | N/A | |||
| ON ON | 913 | 39 | 871 | 41 | 833 | 43 | 807 | 44 | 765 | 46 | 722 | 675 | 629 | N/A | N/A | N/A | N/A | ||||
| OFF ON** | 1191 | N/A | 1168 | N/A | 1135 | N/A | 1112 | N/A | 1081 | N/A | 1055 | 1024 | 998 | N/A | N/A | N/A | N/A | ||||
| GMES96 0603B | OFF OFF | 785 | N/A | 717 | N/A | 648 | N/A | 587 | N/A | 520 | N/A | 457 | 400 | 327 | 269 | 206 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1240 | 43 | 1194 | 45 | 1153 | 46 | 1104 | 48 | 1069 | 50 | 1019 | 971 | 929 | 893 | N/A | N/A | N/A | N/A | |||
| ON ON | 972 | 55 | 922 | 58 | 864 | 62 | 811 | N/A | 767 | N/A | 718 | 651 | 597 | N/A | N/A | N/A | N/A | ||||
| OFF ON** | 1155 | N/A | 1105 | N/A | 1056 | N/A | 1006 | N/A | 958 | N/A | 908 | 857 | 808 | 772 | 723 | N/A | N/A | N/A | N/A | ||
| GMES96 0803B | OFF OFF | 747 | N/A | 676 | N/A | 602 | N/A | 529 | N/A | 453 | N/A | 386 | 329 | 281 | 186 | N/A | N/A | N/A | N/A | ||
| ON OFF* | 1206 | 57 | 1157 | 59 | 1111 | 61 | 1059 | 62 | 1009 | 65 | 966 | 913 | 863 | 834 | 784 | N/A | N/A | N/A | N/A | ||
| ON ON | 985 | N/A | 931 | N/A | 875 | N/A | 823 | N/A | 782 | N/A | 723 | 673 | 606 | 548 | 508 | N/A | N/A | N/A | N/A | ||
| OFF ON** | 1149 | N/A | 1095 | N/A | 1051 | N/A | 1003 | N/A | 951 | N/A | 900 | 845 | 812 | 762 | 707 | N/A | N/A | N/A | N/A | ||
| GMES96 0804C | OFF OFF | 1010 | N/A | 935 | N/A | 861 | N/A | 785 | N/A | 721 | N/A | 631 | 553 | 483 | 423 | 350 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1621 | 44 | 1570 | 45 | 1521 | 47 | 1467 | 48 | 1414 | 50 | 1378 | 1327 | 1274 | 1221 | 1167 | N/A | N/A | N/A | N/A | ||
| ON ON | 1439 | 49 | 1400 | 51 | 1347 | 53 | 1291 | 55 | 1234 | N/A | 1182 | 1125 | 1065 | 1000 | 930 | N/A | N/A | N/A | N/A | ||
| OFF ON** | 1826 | N/A | 1775 | N/A | 1726 | N/A | 1684 | N/A | 1634 | N/A | 1588 | 1538 | 1492 | 1448 | 1398 | N/A | N/A | N/A | N/A | ||
| GMES96 0805C | OFF OFF | 1012 | N/A | 937 | N/A | 861 | N/A | 801 | N/A | 722 | N/A | 630 | 552 | 485 | 420 | 353 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1836 | 39 | 1787 | 40 | 1746 | 41 | 1699 | 42 | 1653 | 43 | 1607 | 1561 | 1514 | 1471 | 1419 | N/A | N/A | N/A | N/A | ||
| ON ON | 1431 | 50 | 1389 | 51 | 1335 | 53 | 1283 | 55 | 1226 | N/A | 1176 | 1117 | 1055 | 993 | 924 | N/A | N/A | N/A | N/A | ||
| OFF ON** | 1836 | 39 | 1787 | 40 | 1746 | 41 | 1699 | 42 | 1653 | 43 | 1607 | 1561 | 1514 | 1471 | 1419 | N/A | N/A | N/A | N/A | ||
| GMES96 1005C | OFF OFF | 1012 | N/A | 940 | N/A | 863 | N/A | 800 | N/A | 715 | N/A | 627 | 561 | 496 | 437 | 374 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1826 | 49 | 1783 | 50 | 1730 | 51 | 1685 | 53 | 1642 | 54 | 1596 | 1548 | 1504 | 1455 | 1406 | N/A | N/A | N/A | N/A | ||
| ON ON | 1465 | N/A | 1402 | N/A | 1360 | N/A | 1306 | N/A | 1250 | N/A | 1197 | 1138 | 1073 | 1016 | 947 | N/A | N/A | N/A | N/A | ||
| OFF ON | 1602 | 55 | 1556 | 57 | 1510 | 59 | 1460 | N/A | 1411 | N/A | 1372 | 1315 | 1261 | 1207 | 1156 | N/A | N/A | N/A | N/A | ||
| GMES96 1205D | OFF OFF | 1121 | N/A | 1018 | N/A | 933 | N/A | 839 | N/A | 762 | N/A | 671 | 592 | 519 | 447 | 371 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1969 | 54 | 1913 | 56 | 1862 | 57 | 1807 | 59 | 1756 | 61 | 1705 | 1647 | 1599 | 1544 | 1481 | N/A | N/A | N/A | N/A | ||
| ON ON | 1688 | 63 | 1626 | N/A | 1564 | N/A | 1500 | N/A | 1448 | N/A | 1393 | 1334 | 1267 | 1199 | 1125 | N/A | N/A | N/A | N/A | ||
| OFF ON | 1865 | 57 | 1812 | 59 | 1755 | 61 | 1692 | 63 | 1638 | 65 | 1587 | 1527 | 1476 | 1411 | 1351 | N/A | N/A | N/A | N/A | ||
GMES96 Circulation Airflow Data
| Model | DIP SWITCHES S2-3, S2-4 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GMES96 0403A | OFF OFF* | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | ||||||||||
| ON OFF | 1110 | 1081 | 1042 | 1003 | 965 | 933 | 893 | 856 | 820 | 803 | |||||||||||
| OFF ON | 1191 | 1168 | 1135 | 1112 | 1081 | 1055 | 1024 | 998 | 978 | N/A | |||||||||||
| ON ON | 1344 | 1312 | 1278 | 1247 | 1215 | 1178 | 1143 | 1114 | 1081 | 1049 | |||||||||||
| GMES96 0603B | OFF OFF* | 785 | 717 | 648 | 587 | 520 | 457 | 400 | 327 | 269 | 206 | ||||||||||
| ON OFF | 1240 | 1194 | 1153 | 1104 | 1069 | 1019 | 971 | 929 | 893 | N/A | |||||||||||
| OFF ON | 1155 | 1105 | 1056 | 1006 | 958 | 908 | 857 | 808 | 772 | 723 | |||||||||||
| ON ON | 1384 | 1338 | 1300 | 1257 | 1215 | 1169 | 1125 | 1080 | 1040 | 994 | |||||||||||
| GMES96 0803B | OFF OFF* | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | ||||||||||
| ON OFF | 1206 | 1157 | 1111 | 1059 | 1009 | 966 | 913 | 863 | 834 | 784 | |||||||||||
| OFF ON | 1149 | 1095 | 1051 | 1003 | 951 | 900 | 845 | 812 | 762 | 707 | |||||||||||
| ON ON | 1414 | 1380 | 1333 | 1305 | 1260 | 1223 | 1180 | 1137 | 1091 | 1047 | |||||||||||
| GMES96 0804C | OFF OFF* | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | ||||||||||
| ON OFF | 1621 | 1570 | 1521 | 1467 | 1414 | 1378 | 1327 | 1274 | 1221 | 1167 | |||||||||||
| OFF ON | 1826 | 1775 | 1726 | 1684 | 1634 | 1588 | 1538 | 1492 | 1448 | 1398 | |||||||||||
| ON ON | 1843 | 1798 | 1753 | 1710 | 1666 | 1618 | 1574 | 1526 | 1481 | 1432 | |||||||||||
| GMES96 0805C | OFF OFF* | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | ||||||||||
| ON OFF | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| OFF ON | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| ON ON | 2215 | 2171 | 2137 | 2098 | 2060 | 2022 | 1986 | 1948 | 1908 | 1869 | |||||||||||
| GMES96 1005C | OFF OFF* | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | ||||||||||
| ON OFF | 1826 | 1783 | 1730 | 1685 | 1642 | 1596 | 1548 | 1504 | 1455 | 1406 | |||||||||||
| OFF ON | 1602 | 1556 | 1510 | 1460 | 1411 | 1372 | 1315 | 1261 | 1207 | 1156 | |||||||||||
| ON ON | 2225 | 2180 | 2141 | 2105 | 2070 | 2033 | 1996 | 1957 | 1923 | 1883 | |||||||||||
| GMES96 1205D | OFF OFF* | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | ||||||||||
| ON OFF* | 1969 | 1913 | 1862 | 1807 | 1756 | 1705 | 1647 | 1599 | 1544 | 1481 | |||||||||||
| ON ON | 1688 | 1626 | 1564 | 1500 | 1448 | 1393 | 1334 | 1267 | 1199 | 1125 | |||||||||||
| OFF ON | 1865 | 1812 | 1755 | 1692 | 1638 | 1587 | 1527 | 1476 | 1411 | 1351 | |||||||||||
GMES96 Cooling Airflow Data
| Model | DIP SWITCHES S1-1, S1-2, S1-3 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GMES96 0403A | OFF OFF OFF | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | ||||||||||
| OFF ON ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| ON OFF ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| ON ON ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| GMES96 0603B | ON OFF OFF | 1110 | 1081 | 1042 | 1003 | 965 | 933 | 893 | 856 | 820 | 803 | ||||||||||
| ON ON OFF | 913 | 871 | 833 | 807 | 765 | 722 | 675 | 629 | 574 | 535 | |||||||||||
| OFF ON OFF | 1191 | 1168 | 1135 | 1112 | 1081 | 1055 | 1024 | 998 | 978 | N/A | |||||||||||
| OFF OFF ON* | 1344 | 1312 | 1278 | 1247 | 1215 | 1178 | 1143 | 1114 | 1081 | 1049 | |||||||||||
| GMES96 0803B | OFF OFF OFF | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | ||||||||||
| OFF ON ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON OFF ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON ON ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON OFF OFF | 1206 | 1157 | 1111 | 1059 | 1009 | 966 | 913 | 863 | 834 | 784 | |||||||||||
| ON ON OFF | 985 | 931 | 875 | 823 | 782 | 723 | 673 | 606 | 548 | 508 | |||||||||||
| OFF ON OFF | 1149 | 1095 | 1051 | 1003 | 951 | 900 | 845 | 812 | 762 | 707 | |||||||||||
| OFF OFF ON* | 1414 | 1380 | 1333 | 1305 | 1260 | 1223 | 1180 | 1137 | 1091 | 1047 | |||||||||||
| GMES96 0804C | OFF OFF OFF | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | ||||||||||
| OFF ON ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON OFF ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON ON ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON OFF OFF | 1621 | 1570 | 1521 | 1467 | 1414 | 1378 | 1327 | 1274 | 1221 | 1167 | |||||||||||
| ON ON OFF | 1439 | 1400 | 1347 | 1291 | 1234 | 1182 | 1125 | 1065 | 1000 | 930 | |||||||||||
| OFF ON OFF | 1826 | 1775 | 1726 | 1684 | 1634 | 1588 | 1538 | 1492 | 1448 | 1398 | |||||||||||
| OFF OFF ON* | 1843 | 1798 | 1753 | 1710 | 1666 | 1618 | 1574 | 1526 | 1481 | 1432 | |||||||||||
| GMES96 0805C | OFF OFF OFF | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | ||||||||||
| OFF ON ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON OFF ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON ON ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON OFF OFF | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| ON ON OFF | 1431 | 1389 | 1335 | 1283 | 1226 | 1176 | 1117 | 1055 | 993 | 924 | |||||||||||
| OFF ON OFF | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| ON ON | 2215 | 2171 | 2137 | 2098 | 2060 | 2022 | 1986 | 1948 | 1908 | 1869 | |||||||||||
| GMES96 1005C | OFF OFF* | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | ||||||||||
| ON OFF* | 1826 | 1783 | 1730 | 1685 | 1642 | 1596 | 1548 | 1504 | 1455 | 1406 | |||||||||||
| OFF ON | 1602 | 1556 | 1510 | 1460 | 1411 | 1372 | 1315 | 1261 | 1207 | 1156 | |||||||||||
| ON ON | 2225 | 2180 | 2141 | 2105 | 2070 | 2033 | 1996 | 1957 | 1923 | 1883 | |||||||||||
| GMES96 1205D | OFF OFF* | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | ||||||||||
| ON OFF* | 1969 | 1913 | 1862 | 1807 | 1756 | 1705 | 1647 | 1599 | 1544 | 1481 | |||||||||||
| ON ON | 1688 | 1626 | 1564 | 1500 | 1448 | 1393 | 1334 | 1267 | 1199 | 1125 | |||||||||||
| OFF ON | 1865 | 1812 | 1755 | 1692 | 1638 | 1587 | 1527 | 1476 | 1411 | 1351 | |||||||||||
GMES96 Cooling Airflow Data
| Model | DIP SWITCHES S1-1, S1-2, S1-3 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GMES96 0403A | OFF OFF OFF | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | ||||||||||
| OFF ON ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| ON OFF ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| ON ON ON | 715 | 666 | 609 | 558 | 500 | 438 | 386 | 333 | 276 | 220 | |||||||||||
| GMES96 0603B | ON OFF OFF | 1110 | 1081 | 1042 | 1003 | 965 | 933 | 893 | 856 | 820 | 803 | ||||||||||
| ON ON OFF | 913 | 871 | 833 | 807 | 765 | 722 | 675 | 629 | 574 | 535 | |||||||||||
| OFF ON OFF | 1191 | 1168 | 1135 | 1112 | 1081 | 1055 | 1024 | 998 | 978 | N/A | |||||||||||
| OFF OFF ON* | 1344 | 1312 | 1278 | 1247 | 1215 | 1178 | 1143 | 1114 | 1081 | 1049 | |||||||||||
| GMES96 0803B | OFF OFF OFF | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | ||||||||||
| OFF ON ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON OFF ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON ON ON | 747 | 676 | 602 | 529 | 453 | 386 | 329 | 281 | 186 | N/A | |||||||||||
| ON OFF OFF | 1206 | 1157 | 1111 | 1059 | 1009 | 966 | 913 | 863 | 834 | 784 | |||||||||||
| ON ON OFF | 985 | 931 | 875 | 823 | 782 | 723 | 673 | 606 | 548 | 508 | |||||||||||
| OFF ON OFF | 1149 | 1095 | 1051 | 1003 | 951 | 900 | 845 | 812 | 762 | 707 | |||||||||||
| OFF OFF ON* | 1414 | 1380 | 1333 | 1305 | 1260 | 1223 | 1180 | 1137 | 1091 | 1047 | |||||||||||
| GMES96 0804C | OFF OFF OFF | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | ||||||||||
| OFF ON ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON OFF ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON ON ON | 1010 | 935 | 861 | 785 | 721 | 631 | 553 | 483 | 423 | 350 | |||||||||||
| ON OFF OFF | 1621 | 1570 | 1521 | 1467 | 1414 | 1378 | 1327 | 1274 | 1221 | 1167 | |||||||||||
| ON ON OFF | 1439 | 1400 | 1347 | 1291 | 1234 | 1182 | 1125 | 1065 | 1000 | 930 | |||||||||||
| OFF ON OFF | 1826 | 1775 | 1726 | 1684 | 1634 | 1588 | 1538 | 1492 | 1448 | 1398 | |||||||||||
| OFF OFF ON* | 1843 | 1798 | 1753 | 1710 | 1666 | 1618 | 1574 | 1526 | 1481 | 1432 | |||||||||||
| GMES96 0805C | OFF OFF OFF | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | ||||||||||
| OFF ON ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON OFF ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON ON ON | 1012 | 937 | 861 | 801 | 722 | 630 | 552 | 485 | 420 | 353 | |||||||||||
| ON OFF OFF | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| ON ON OFF | 1431 | 1389 | 1335 | 1283 | 1226 | 1176 | 1117 | 1055 | 993 | 924 | |||||||||||
| OFF ON OFF | 1836 | 1787 | 1746 | 1699 | 1653 | 1607 | 1561 | 1514 | 1471 | 1419 | |||||||||||
| ON ON | 2215 | 2171 | 2137 | 2098 | 2060 | 2022 | 1986 | 1948 | 1908 | 1869 | |||||||||||
| GMES96 1005C | OFF OFF* | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | ||||||||||
| ON OFF* | 1826 | 1783 | 1730 | 1685 | 1642 | 1596 | 1548 | 1504 | 1455 | 1406 | |||||||||||
| OFF ON | 1602 | 1556 | 1510 | 1460 | 1411 | 1372 | 1315 | 1261 | 1207 | 1156 | |||||||||||
| ON ON | 2225 | 2180 | 2141 | 2105 | 2070 | 2033 | 1996 | 1957 | 1923 | 1883 | |||||||||||
| GMES96 1205D | OFF OFF* | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | ||||||||||
| ON OFF* | 1969 | 1913 | 1862 | 1807 | 1756 | 1705 | 1647 | 1599 | 1544 | 1481 | |||||||||||
| ON ON | 1688 | 1626 | 1564 | 1500 | 1448 | 1393 | 1334 | 1267 | 1199 | 1125 | |||||||||||
| OFF ON | 1865 | 1812 | 1755 | 1692 | 1638 | 1587 | 1527 | 1476 | 1411 | 1351 | |||||||||||
GMES96 Cooling Airflow Data (Contd.)
| Model | DIP SWITCHES S1-1, S1-2, S1-3 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GMES96 1005C | OFF OFF OFF | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | ||||||||||
| OFF ON ON | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | |||||||||||
| ON OFF ON | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | |||||||||||
| ON ON ON | 1012 | 940 | 863 | 800 | 715 | 627 | 561 | 496 | 437 | 374 | |||||||||||
| GMES96 1205D | ON OFF OFF | 1826 | 1783 | 1730 | 1685 | 1642 | 1596 | 1548 | 1504 | 1455 | 1406 | ||||||||||
| ON ON OFF | 1465 | 1402 | 1360 | 1306 | 1250 | 1197 | 1138 | 1073 | 1016 | 947 | |||||||||||
| OFF ON OFF | 1602 | 1556 | 1510 | 1460 | 1411 | 1372 | 1315 | 1261 | 1207 | 1156 | |||||||||||
| OFF OFF ON* | 2225 | 2180 | 2141 | 2105 | 2070 | 2033 | 1996 | 1957 | 1923 | 1883 | |||||||||||
| OFF OFF OFF | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | |||||||||||
| OFF ON ON | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | |||||||||||
| ON OFF ON | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | |||||||||||
| ON ON ON | 1121 | 1018 | 933 | 839 | 762 | 671 | 592 | 519 | 447 | 371 | |||||||||||
| ON OFF OFF | 1969 | 1913 | 1862 | 1807 | 1756 | 1705 | 1647 | 1599 | 1544 | 1481 | |||||||||||
| ON ON OFF | 1688 | 1626 | 1564 | 1500 | 1448 | 1393 | 1334 | 1267 | 1199 | 1125 | |||||||||||
| OFF ON OFF | 1865 | 1812 | 1755 | 1692 | 1638 | 1587 | 1527 | 1476 | 1411 | 1351 | |||||||||||
| OFF OFF ON* | 2268 | 2214 | 2173 | 2117 | 2068 | 2022 | 1978 | 1924 | 1874 | 1832 | |||||||||||
GCES96 Heating Airflow Data
| Model | DIP SWITCHES S2-1, S2-2 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | CFM | RISE | ||
| GCES96 0403B | OFF OFF | 629 | N/A | 566 | N/A | 509 | N/A | 450 | N/A | 388 | N/A | 327 | 269 | 228 | N/A | N/A | N/A | N/A | |||
| ON OFF* | 949 | 37 | 899 | 40 | 853 | 42 | 809 | 44 | 786 | 45 | 742 | 697 | 652 | N/A | N/A | N/A | N/A | ||||
| ON ON | 733 | 49 | 672 | 53 | 613 | N/A | 563 | N/A | 512 | N/A | 454 | 404 | 349 | N/A | N/A | N/A | N/A | ||||
| OFF ON** | 1126 | N/A | 1086 | N/A | 1044 | N/A | 1006 | N/A | 968 | N/A | 925 | 885 | 849 | N/A | N/A | N/A | N/A | ||||
| GCES96 0603B | OFF OFF | 754 | N/A | 684 | N/A | 615 | N/A | 542 | N/A | 471 | N/A | 411 | 343 | 276 | 214 | N/A | N/A | N/A | N/A | ||
| ON OFF* | 1332 | 40 | 1291 | 41 | 1252 | 43 | 1218 | 44 | 1173 | 45 | 1134 | 1088 | 1049 | 1013 | N/A | N/A | N/A | N/A | |||
| ON ON | 972 | 55 | 922 | 58 | 864 | 62 | 811 | N/A | 767 | N/A | 718 | 651 | 597 | N/A | N/A | N/A | N/A | ||||
| OFF ON | 1155 | 46 | 1105 | 48 | 1056 | 51 | 1006 | 53 | 958 | 56 | 908 | 857 | 808 | 772 | 723 | N/A | N/A | N/A | N/A | ||
| GCES96 0804C | OFF OFF* | 760 | N/A | 686 | N/A | 613 | N/A | 542 | N/A | 459 | N/A | 376 | 310 | 266 | 224 | 190 | N/A | N/A | N/A | N/A | |
| ON OFF* | 1390 | 51 | 1342 | 53 | 1292 | 55 | 1254 | 57 | 1201 | 59 | 1157 | 1112 | 1072 | 1022 | 985 | N/A | N/A | N/A | N/A | ||
| OFF ON | 1581 | N/A | 1537 | N/A | 1492 | N/A | 1452 | N/A | 1413 | N/A | 1387 | 1347 | 1305 | 1267 | 1225 | N/A | N/A | N/A | N/A | ||
| ON ON | 1800 | 1758 | 1716 | 1678 | 1636 | 1601 | 1565 | 1529 | 1491 | 1457 | N/A | N/A | N/A | N/A | |||||||
| GCES96 1005C | OFF OFF* | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | N/A | N/A | N/A | N/A | ||||||
| ON OFF* | 1650 | 1592 | 1530 | 1478 | 1428 | 1389 | 1327 | 1270 | 1213 | 1159 | N/A | N/A | N/A | N/A | |||||||
| OFF ON | 1860 | 1810 | 1755 | 1702 | 1656 | 1611 | 1553 | 1511 | 1454 | 1405 | N/A | N/A | N/A | N/A | |||||||
| ON ON | 2230 | 2176 | 2125 | 2086 | 2038 | 1999 | 1958 | 1917 | 1880 | 1829 | N/A | N/A | N/A | N/A | |||||||
| GCES96 1205D | OFF OFF* | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | N/A | N/A | N/A | N/A | ||||||
| ON OFF* | 1917 | 1843 | 1759 | 1686 | 1600 | 1513 | 1420 | 1348 | 1258 | 1173 | N/A | N/A | N/A | N/A | |||||||
| OFF ON | 2011 | 1936 | 1858 | 1779 | 1692 | 1610 | 1531 | 1442 | 1365 | 1266 | N/A | N/A | N/A | N/A | |||||||
| ON ON | 2317 | 2257 | 2196 | 2122 | 2061 | 1990 | 1914 | 1762 | 1523 | 1232 | N/A | N/A | N/A | N/A | |||||||
GCES96 Circulation Airflow Data
| Model | DIP SWITCHES S2-3, S2-4 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GCES96 0403B | OFF OFF* | 629 | 566 | 509 | 450 | 388 | 327 | 269 | 228 | 195 | 153 | ||||||||||
| ON OFF | 949 | 899 | 853 | 809 | 786 | 742 | 697 | 652 | 609 | 575 | |||||||||||
| OFF ON | 1126 | 1086 | 1044 | 1006 | 968 | 925 | 885 | 849 | 827 | 792 | |||||||||||
| ON ON | 1359 | 1321 | 1284 | 1251 | 1218 | 1181 | 1147 | 1114 | 1080 | 1045 | |||||||||||
| GCES96 0603B | OFF OFF* | 754 | 684 | 615 | 542 | 471 | 411 | 343 | 276 | 214 | N/A | ||||||||||
| ON OFF | 1332 | 1291 | 1252 | 1218 | 1173 | 1134 | 1088 | 1049 | 1013 | N/A | |||||||||||
| OFF ON | 1155 | 1105 | 1056 | 1006 | 958 | 908 | 857 | 8080 | 772 | 723 | |||||||||||
| ON ON | 1384 | 1338 | 1300 | 1257 | 1215 | 1189 | 1169 | 1125 | 1080 | 1040 | |||||||||||
| GCES96 0804C | OFF OFF* | 760 | 686 | 613 | 542 | 459 | 376 | 310 | 266 | 224 | 190 | ||||||||||
| ON OFF | 1390 | 1342 | 1292 | 1254 | 1201 | 1157 | 1112 | 1072 | 1022 | 985 | |||||||||||
| OFF ON | 1581 | 1537 | 1492 | 1452 | 1413 | 1387 | 1347 | 1305 | 1267 | 1225 | |||||||||||
| ON ON | 1800 | 1758 | 1716 | 1678 | 1636 | 1601 | 1565 | 1529 | 1491 | 1457 | |||||||||||
| GCES96 1005C | OFF OFF* | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | ||||||||||
| ON OFF | 1650 | 1592 | 1530 | 1478 | 1428 | 1389 | 1327 | 1270 | 1213 | 1159 | |||||||||||
| OFF ON | 1860 | 1810 | 1755 | 1702 | 1656 | 1611 | 1553 | 1511 | 1454 | 1405 | |||||||||||
| ON ON | 2230 | 2176 | 2125 | 2086 | 2038 | 1999 | 1958 | 1917 | 1880 | 1829 | |||||||||||
| GCES96 1205D | OFF OFF* | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | ||||||||||
| ON OFF | 1917 | 1843 | 1759 | 1686 | 1600 | 1513 | 1420 | 1348 | 1258 | 1173 | |||||||||||
| OFF ON | 2011 | 1936 | 1858 | 1779 | 1692 | 1610 | 1531 | 1442 | 1365 | 1266 | |||||||||||
| ON ON | 2317 | 2257 | 2196 | 2122 | 2061 | 1990 | 1914 | 1762 | 1523 | 1232 | |||||||||||
GCES96 Cooling Airflow Data
| Model | DIP SWITCHES S1-1, S1-2, S1-3 | 0.1" | 0.2" | 0.3" | 0.4" | 0.5" | 0.6" | 0.7" | 0.8" | 0.9" | 1" | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | CFM | ||||||||||||
| GCES96 0403B | OFF OFF OFF | 629 | 566 | 509 | 450 | 388 | 327 | 269 | 228 | 195 | 153 | ||||||||||
| OFF ON ON | 629 | 566 | 509 | 450 | 388 | 327 | 269 | 228 | 195 | 153 | |||||||||||
| ON OFF ON | 629 | 566 | 509 | 450 | 388 | 327 | 269 | 228 | 195 | 153 | |||||||||||
| ON ON ON | 629 | 566 | 509 | 450 | 388 | 327 | 269 | 228 | 195 | 153 | |||||||||||
| GCES96 0603B | ON OFF OFF | 949 | 899 | 853 | 809 | 786 | 742 | 697 | 652 | 609 | 575 | ||||||||||
| ON ON OFF | 733 | 672 | 613 | 563 | 512 | 454 | 404 | 349 | 306 | 261 | |||||||||||
| OFF ON OFF | 1126 | 1086 | 1044 | 1006 | 968 | 925 | 885 | 849 | 827 | 792 | |||||||||||
| OFF OFF ON* | 1359 | 1321 | 1284 | 1251 | 1218 | 1181 | 1147 | 1114 | 1080 | 1045 | |||||||||||
| GCES96 0804C | OFF OFF OFF | 754 | 684 | 615 | 542 | 471 | 411 | 343 | 276 | 214 | N/A | ||||||||||
| OFF ON ON | 754 | 684 | 615 | 542 | 471 | 411 | 343 | 276 | 214 | N/A | |||||||||||
| ON OFF ON | 754 | 684 | 615 | 542 | 471 | 411 | 343 | 276 | 214 | N/A | |||||||||||
| ON ON ON | 754 | 684 | 615 | 542 | 471 | 411 | 343 | 276 | 214 | N/A | |||||||||||
| ON OFF OFF | 1332 | 1291 | 1252 | 1218 | 1173 | 1134 | 1088 | 1049 | 1013 | N/A | |||||||||||
| ON ON OFF | 972 | 922 | 864 | 811 | 767 | 718 | 651 | 597 | 556 | 511 | |||||||||||
| OFF ON OFF | 1155 | 1105 | 1056 | 1006 | 958 | 908 | 857 | 808 | 772 | 723 | |||||||||||
| OFF OFF ON* | 1384 | 1338 | 1300 | 1257 | 1215 | 1189 | 1169 | 1125 | 1080 | 1040 | |||||||||||
| GCES96 1005C | OFF OFF OFF | 760 | 686 | 613 | 542 | 459 | 376 | 310 | 266 | 224 | 190 | ||||||||||
| OFF ON ON | 760 | 686 | 613 | 542 | 459 | 376 | 310 | 266 | 224 | 190 | |||||||||||
| ON OFF ON | 760 | 686 | 613 | 542 | 459 | 376 | 310 | 266 | 224 | 190 | |||||||||||
| ON ON ON | 760 | 686 | 613 | 542 | 459 | 376 | 310 | 266 | 224 | 190 | |||||||||||
| ON OFF OFF | 1390 | 1342 | 1292 | 1254 | 1201 | 1157 | 1112 | 1072 | 1022 | 985 | |||||||||||
| ON ON OFF | 1397 | 1361 | 1318 | 1266 | 1224 | 1181 | 1139 | 1095 | 1050 | 1003 | |||||||||||
| OFF ON OFF | 1581 | 1537 | 1492 | 1452 | 1413 | 1387 | 1347 | 1305 | 1267 | 1225 | |||||||||||
| OFF OFF ON* | 1800 | 1758 | 1716 | 1678 | 1636 | 1601 | 1565 | 1529 | 1491 | 1457 | |||||||||||
| GCES96 1205D | OFF OFF OFF | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | ||||||||||
| OFF ON ON | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | |||||||||||
| ON OFF ON | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | |||||||||||
| ON ON ON | 1211 | 1129 | 1045 | 964 | 890 | 812 | 764 | 702 | 639 | 583 | |||||||||||
| ON OFF OFF | 1650 | 1592 | 1530 | 1478 | 1428 | 1389 | 1327 | 1270 | 1213 | 1159 | |||||||||||
| ON ON OFF | 1457 | 1394 | 1338 | 1294 | 1236 | 1171 | 1110 | 1048 | 986 | 919 | |||||||||||
| OFF ON OFF | 1860 | 1810 | 1755 | 1702 | 1656 | 1611 | 1553 | 1511 | 1454 | 1405 | |||||||||||
| OFF OFF ON* | 2230 | 2176 | 2125 | 2086 | 2038 | 1999 | 1958 | 1917 | 1880 | 1829 | |||||||||||
| OFF OFF OFF | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | |||||||||||
| OFF ON ON | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | |||||||||||
| ON OFF ON | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | |||||||||||
| ON ON ON | 1296 | 1190 | 1076 | 960 | 839 | 760 | 653 | 559 | 452 | 351 | |||||||||||
| ON OFF OFF | 1917 | 1843 | 1759 | 1686 | 1600 | 1513 | 1420 | 1348 | 1258 | 1173 | |||||||||||
| ON ON OFF | 1611 | 1521 | 1433 | 1347 | 1246 | 1145 | 1044 | 953 | 876 | 790 | |||||||||||
| OFF ON OFF | 2011 | 1936 | 1858 | 1779 | 1692 | 1610 | 1531 | 1442 | 1365 | 1266 | |||||||||||
| ON ON | 2317 | 2257 | 2196 | 2122 | 2061 | 1990 | 1914 | 1762 | 1523 | 1232 | |||||||||||
Minimum Filter Sizes
| Filter Size (in²) (Qty) | GMES96 0403ANA | GMES96 0603BNA | GMES96 0803BNA | GMES96 0804CNA | GMES96 0805CNA | GMES96 1005CNA | GMES96 1205DNA |
|---|---|---|---|---|---|---|---|
| (1) 16 x 25 (side) or (1) 14 x 25 (bottom) | V | ||||||
| (1) 16 x 25 (side or bottom) | V | ||||||
| (2) 10 x 20 or (1) 16 x 25 (top return) | V | V | |||||
| (1) 14 x 20 (bottom) or (1) 20 x 25 (top return) | V | V | V |
Note: Other size filters of equal or greater dimensions may be used. Filters may also be centrally located.
Notes for Airflow Data:
CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed.
All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling and heating speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
This chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on the rating plate.
The dashed (----) areas indicate a temperature rise not recommended for this model.
At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while ESP at the CFM will be lower.
Performance Charts and Diagrams
Temperature Rise Range Chart
This chart graphically represents the relationship between BTU Output (in thousands), Temperature Rise (in °F), and Airflow (CFM). It includes formulas for calculating BTU/h Output and Temperature Rise based on CFM and Rise. The chart displays lines for various CFM values from 600 to 2400.
Wiring Diagram
The wiring diagram illustrates the electrical connections for the furnace components. It details the 115 VAC power supply, 24 VAC transformer, integrated control module, blower motor, igniter, gas valve, pressure switches, limit controls, and thermostat connections. The diagram includes color codes for wiring and important safety warnings regarding high voltage and proper grounding.
Diagnostic LED Codes (Integrated Control Module)
- STEADY ON: Normal Operation
- OFF: Control Failure
- 1 FLASH: System Lockout (Retries Exceeded)
- 2 FLASHES: Pressure Switch Stuck Closed
- 3 FLASHES: Pressure Switch Stuck Open
- 4 FLASHES: Open High Limit
- 5 FLASHES: Flame Sense Without Gas Valve
- 6 FLASHES: Open Rollout
- 7 FLASHES: Low Flame Signal
- 8 FLASHES: Igniter Relay Fault
- 9 FLASHES: Twinning Fault
- 10 FLASHES: Open Fuse
- 11 FLASHES: Igniter Open
- 12 FLASHES: Inducer Relay Error
- CONTINUOUS/RAPID FLASHES: Reversed 115 VAC Polarity
High Voltage Warning: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
Wiring Note: Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Notes for Wiring Diagram:
1. Set heat anticipator on room thermostat at 0.7 Amps.
2. Manufacturer's specified replacement parts must be used when servicing.
3. If original wire must be replaced, use wiring material with a temperature rating of at least 105°C. Use copper conductors only.
4. Blower speeds should be adjusted by installer to match installation requirements for correct heating temperature rise and cooling CFM.
5. Unit must be permanently grounded and conform to N.E.C. and local codes.
Accessories
The following table lists available accessories for the GMES96 and GCES96 furnace models.
GMES96 Accessories
| Model | Description | GMES96 0403ANA | GMES96 0603BNA | GMES96 0803BNA | GMES96 0804CNA | GMES96 0805CNA | GMES96 1005CNA | GMES96 1205DNA |
|---|---|---|---|---|---|---|---|---|
| CVENT-2 | Concentric Vent Kit (2") | V | V | V | V | V | V | V |
| CVENT-3 | Concentric Vent Kit (3") | V | V | V | V | V | V | V |
| CFSB17 | Downflow Sub-Base 17.5" | --- | --- | --- | --- | --- | --- | --- |
| CFSB21 | Downflow Sub-Base 21" | --- | --- | --- | --- | --- | --- | --- |
| CFSB24 | Downflow Sub-Base 24" | --- | --- | --- | --- | --- | --- | --- |
| RF000142 | Drain Kit-Horizontal Left Vertical Flue | V | V | V | V | V | V | V |
| EFR02 | External Filter Rack with 16"x25" Permanent Filter | V | V | V | V | V | V | V |
| 0170K00000S | Flush Mount Vent Kit- 3" or 2" | V | V | V | V | V | V | V |
| 0170K00001S | Flush Mount Vent Kit- 2" | V | V | V | V | V | V | V |
| AFE18-60A | Fossil Fuel (Dual Fuel) Kit | V | V | V | V | V | V | V |
| HASFK | High-Altitude Natural Gas Kit | TBD | HASFK-4 | HASFK-4 | HASFK-4 | HASFK-4 | HASFK-4 | HASFK-4 |
| HASFK | High-Altitude LP Gas Kit | TBD | HASFK-5,6 | HASFK-5,6 | N/A | N/A | N/A | N/A |
| LPLP03 | Low LP Gas Pressure Switch | V | V | V | V | V | V | V |
| LPM-07 | LP Conversion Kits | V | V | V | V | V | V | V |
| TK-400 | Twinning Kit | V | V | V | V | V | V | V |
GCES96 Accessories
| Model | Description | GCES96 0403BNA | GCES96 0603BNA | GCES96 0804CNA | GCES96 1005CNA | GCES96 1205DNA |
|---|---|---|---|---|---|---|
| CVENT-2 | Concentric Vent Kit (2") | V | V | V | V | V |
| CVENT-3 | Concentric Vent Kit (3") | V | V | V | V | V |
| CFSB17 | Downflow Sub-Base 17.5" | V | V | |||
| CFSB21 | Downflow Sub-Base 21" | V | V | |||
| CFSB24 | Downflow Sub-Base 24" | V | ||||
| RF000142 | Drain Kit-Horizontal Left Vertical Flue | V | V | V | V | V |
| EFR02 | External Filter Rack with 16"x25" Permanent Filter | V | V | V | V | V |
| 0170K00000S | Flush Mount Vent Kit- 3" or 2" | V | V | V | V | V |
| 0170K00001S | Flush Mount Vent Kit- 2" | V | V | V | V | V |
| AFE18-60A | Fossil Fuel (Dual Fuel) Kit | V | V | V | V | V |
| HASFK | High-Altitude Natural Gas Kit | HASFK-4 | HASFK-4 | HASFK-4 | HASFK-4 | HASFK-4 |
| HASFK | High-Altitude LP Gas Kit | HASFK-5 | HASFK-5 | HASFK-5 | HASFK-4 | HASFK-4 |
| LPLP03 | Low LP Gas Pressure Switch | V | V | V | V | V |
| LPM-07 | LP Conversion Kits | V | V | V | V | V |
| TK-400 | Twinning Kit | V | V | V | V | V |
Warranty Information
Complete warranty details are available from your local dealer or at www.amana-hac.com. To receive the Lifetime Heat Exchanger Limited Warranty (good for as long as you own your home), 10-Year Unit Replacement Limited Warranty, and 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.