Delta Controls DSC-1616 Installation Guide
Document Edition 3.4
Updated November 17, 2015
Product Description
The DSC-1616 is a fully programmable, Native BACnet™ Building Controller that communicates on Twisted Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LAN using the BACnet MS/TP protocol.
The controller includes an easy to mount enclosure and is designed for a wide range of applications requiring no more than 16 inputs and 16 outputs, including but not limited to Roof Top Units, Air Handlers, Boilers or Chillers, etc. A second RS-485 port may be configured as an MS/TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers.
The 16 universal inputs are jumper configurable and the 16 analog outputs have an option of coming with monitored Hand-Off-Auto switches.
Diagram: A visual representation of the DSC-1616 controller unit is shown, depicting its physical form factor.
Important Information
ℹ️ ORCAview OWS and controller firmware must all be of the same version number to be compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you must upgrade all the remaining products. Exception: UL 864 model, DSC-1616E-UL864 can be used with V3.33 and V3.40 firmware.
Package Contents
- Product: DSC-1616
- DSC-1616 Installation Guide
Related Documents
- Delta Controls Wiring Guidelines
- ORCAview Operator Guide
- ORCAview Technical Reference Manual
- Release Notes for related Firmware
UL864 Specific Considerations
ℹ️ Wiring to and from the device shall be through power-limited circuits.
Use only Core Components transformer, Model No. 120-024-100-2TF-CB, by Lectro Components Inc. to power the device. (Delta Part # 440008)
Use only UL Listed Class 2 Power Supplies for auxiliary field devices.
Use only UL Recognized Ethernet Switch, 571-580, by Siemens for Smoke Control Systems that utilize Ethernet communications.
Impedance value for which ground faults are detected is zero ohms.
Cautions or Warnings
⚠️ This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap) should be used when installing this product so that damage to the product does not occur.
Danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer's instructions. Replace the battery with type CR2032.
Equipment damage or loss of data may occur if these procedures are not followed as specified.
Installations requiring CE conformance: All wiring for CE rated products must use an extra low voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% duty cycle.
Mounting
The DSC-1616 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This controller should be mounted in an appropriate location within packaged equipment or another enclosure that meets code requirements.
Diagram: Dimensional drawings of the DSC-1616 enclosure with measurements for width, length, and various other dimensions labeled A through G. A table lists these dimensions in mm.
Table:
Dimension | Value (mm +/- 0.5mm) |
---|---|
PCB width | 200 |
PCB length | 300 |
A | 201 |
B | 46.55 |
C | 307 |
D | 320 |
E | 333 |
F | 24 |
G | 12 |
Board Layout
Diagram: A detailed layout of the DSC-1616E board showing all input and output ports, LEDs, and connectors. Labels include: 24VAC POWER IN, NET 1 PORT (SUPERVISED), POWER LED, SCAN LED, ETHERNET PORT (SUPERVISED), INPUT TYPE SELECTORS, INPUT 1 through INPUT 16, 24VAC POWER OUT (SPECIAL APPLICATION), NET 2 PORT (SUPERVISED), RS-232 PORT, SERVICE TOOL PORT, OUTPUT 1 through OUTPUT 16, and GROUND LUG.
Controller Configuration
Controller Type
Various products have the capability of being configured as one of several possible controller types, which represents the network level that it will reside on in the network architecture (Area, System, Subnet). Other than the one controller acting as a router, all other controllers on the same network segment must be configured the same.
- Area - Configures the controller as an Area level controller on a network. This is an option only on the Ethernet model and is the setting when the controller is connected to an Ethernet network (typically between buildings) and is acting as a router from one LAN to either a network of System controllers or Subnet controllers.
- System - Configures the controller as a System level controller on a network of System controllers. This is the setting when the controller is connected to an Ethernet or BACnet MS/TP network with other System controllers or is a single head-end controller for a network of Subnet controllers.
- Subnet - Configures the controller as a Subnet level controller on a Subnet of similar controllers. This is the setting when the controller is connected to a BACnet MS/TP network with other Subnet controllers.
Note: This also determines where the DIP or MAC address is mapped into the controllers BACnet address and which other portions of its BACnet address are inherited when DNA is enabled.
Diagram: Visual representation of Area, System, and Subnet settings.
Derived Network Addressing
The DNA jumper comes ON by default. This allows the controller to automatically configure a BACnet controller address. This should NOT be removed unless you are assigning a BACnet controller number through software. The BACnet controller number should not be confused with the DIP switch setting, and each controller must still have a unique dip switch address even when using software to define the controller number.
Diagram: Visual representation of the DNA jumper setting.
Controller Addressing
The Dip Switch is a binary switch. Each individual DIP switch represents a unique value, which forms the controller address when added together.
To set the address, simply move the switches that add up to the controllers desired address to the ON position.
Example: If the controller is to be address 5 on the network, set the switch numbered 4 and the switch numbered 1 (equals 5) to the On position.
Note: Each controller on the same MS/TP segment must have a unique DIP switch address.
Diagram: A visual representation of DIP switches labeled 1 through 8, with an ON/OFF indicator.
Wiring General
All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product and output loads.
⚠️ More than one disconnect switch may be required to de-energize the equipment before servicing.
ℹ️ Input Class 2 Power Supplies are interconnected. Use only Class 2 sources suitable for interconnections.
- All terminals are acceptable for Class 2 Circuit connections only
- Use copper conductors only
- Apply minimum 6.0 lb-in torque for tightening field wires into the terminal blocks
Power
This product is designed to use a 24 VAC, Class 2 power supply. The proper specified cabling must be used. (18 – 16 AWG, 2-conductor wire)
A single transformer may be used to power multiple controllers and/or auxiliary field devices (actuators, etc.) provided the following conditions are met:
- All devices MUST be 1½ wave rectified. Mixing power between 1½ wave and full wave rectified devices will damage both the transformer and connected equipment.
- The transformer is properly sized, including line losses for the total VA requirements.
- Polarity is observed between controllers (with respect to 24~ and Gnd).
- Each controller is grounded as shown in the diagram below. This is important to protect equipment and ensure a common ground reference for RS-485 communications.
- The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits).
Diagram: A wiring diagram showing a 24VAC (Class 2) transformer powering two devices. It illustrates the grounding connections for Device 1 and Device 2, including the use of a ground lug and a terminal labeled GND.
ℹ️ Make sure to ground the controller using the ground lug that is available on the controller.
Network Communication
The controller communicates on Twisted Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LAN using the BACnet MS/TP protocol. Refer to Delta Controls Wiring Guidelines for further details.
MS/TP (RS-485) Wiring
For detailed information on MS/TP and LINKnet wiring refer to Delta Controls Wiring Guidelines.
- The proper specified cabling must be used to ensure reliable communications. (22 AWG twisted pair, 100-120 ohms impedance, 17 pF/ft or lower capacitance, with a braided or aluminum foil shield.)
- Controllers should always be wired together in a daisy-chain fashion. Attempting to connect them using a starred or bus configuration will cause problems on the network.
- Networks with a total length greater than 4000 ft or with more than 50 controllers require a repeater (RPT-768).
- LINKnet networks that have only 1-2 controllers, and have less then 100 ft of cable length do not require network terminators.
Diagram: A schematic illustrating RS-485 daisy-chain wiring with shield connections and network terminators.
Input and Output Wiring
Inputs and outputs on the DSC-1616 controller follow the same general wiring requirements as other Delta Controls products. Recommended cable types should be used as listed below. Refer to the Delta Controls Wiring Guidelines for more details.
Recommended Cable Type | Where to Use |
---|---|
2 Conductor, 18 AWG, Unshielded | All outputs and 4-20mA, 10KΩ, and 10V input types |
2 Conductor, 22 AWG, Shielded | Inputs configured for 5V |
Input Configuration
The input must be configured to accept the signal used by the input device. Place the jumper for each input in the correct location on the Input Type Selector Block. The diagram to the right shows the factory default selection of 10 KΩ.
- 4-20mA - For sensors that use a 4 to 20 mA signal.
- 10K - For 10 KΩ Thermistor temperature sensors, as well as Dry Contact binary inputs.
- 5V - For sensors that use a 0 - 5 VDC signal.
- 10V - For sensors that use a 0 -10 VDC signal.
Diagram: A visual representation of input type selector options: 4-20mA, 10k, 0-5V, 0-10V.
Output Configuration
Each HOA switch is HAND, OFF, AUTO from right to left. The HAND position allows a user to manually force the output on, the OFF position allows a user to manually force an output off, and the AUTO position allows the output to be controlled automatically by the controller.
Diagram: A visual representation of the HOA switch positions.
Indicators
LED | Function | Description |
---|---|---|
Power Indicator | Controller Power | This yellow LED turns on to indicate that the controller has power applied. |
Scan | CPU Scan Indicator | This red LED flashes at a rate relative to the CPU scan rate. |
Network (Ethernet) | Ethernet Communication Status Indicators | The green LNK LED is turned on when a link is established between two Ethernet devices. (for example, controller, computer, switch, etc.) The green ACT LED flashes when communications are active. |
Network (NET1) | MS/TP (RS485) Communication Status Indicators | The green LED flashes to indicate when the controller is transmitting out the port, and the red LED flashes to indicate when the controller is receiving data through the port. If communication is good, both LEDs will flash at a high rate. |
Network (NET2) | MS/TP (RS485) Communication Status Indicators | The green LED flashes to indicate when the controller is transmitting out the port, and the red LED flashes to indicate when the controller is receiving data through the port. If communication is good, both LEDs will flash at a high rate. |
Inputs (IP1 - IP16) | Input Status Indicators | A corresponding red LED varies in intensity and is brightly lit when the associated input is receiving a low voltage input signal (i.e. a closed contact, 0 VDC, 0mA or a high temperature reading or low resistance). |
Outputs (OP1 – OP16) | Output Status Indicators | A tri-color LED is used. Under automatic control, the corresponding output LED is green and is on or off to match the status of an associated binary output. The LED will also vary in intensity relative to the output signal for an analog output. With HOA switches, the output LED is red in the OFF position and yellow in the HAND position. |
Product Specifications
- Power Requirements: 24 VAC, 60Hz, Class 2
- Power Consumption: 30 VA
- Ambient Ratings: 32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)
- Communication Ports:
- Ethernet: 10 BaseT @ 10Mbps, BACnet IP, BACnet over Ethernet
- NET1: BACnet MS/TP (RS-485) Communication: 9600, 19200, 38400, 76800 bps (Default). Maximum of 99 controllers.
- NET2: OR LINKnet Communication: 76800 bps. Maximum of 12 LINKnet controllers including up to two DFM controllers.
- NET2: OR BACnet MS/TP (RS-485) Communication: 9600, 19200, 38400, 76800 bps (Default). Maximum of 99 controllers.
- Serial: OR LINKnet Communication: 76800 bps. Maximum of 12 LINKnet controllers including up to two DFM controllers.
- Serial: RS-232, BACnet PTP Communication: 9600, 19200, 38400 (default)
- Service Port: RJ-11 Jack. Used with Delta Controls service tool devices (for example, CON-768).
- Inputs: 16 Universal Inputs (10 bit), jumper configurable for the following input types: 0-5 VDC, 0-10 VDC, 10 KΩ Thermistor, Dry Contact (using 10 KΩ Thermistor jumper setting), 4-20 mA.
- Outputs: 16 Universal Outputs c/w LED status indication (including HOA status). 0-10 VDC @ 20 mA maximum per output. Software configurable as binary or analog. Hand/Off/Auto Switches (c/w position feedback).
- Technology: 32 bit processor, 2 MB (16 megabit) Flash Memory, 512 KB SRAM memory.
- Listings: UL 916 Listed, BTL Listed, UL 864 Listed (DSC-1616E-UL864 model only).
- Compliance: CE, FCC.
CE - DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and EN 45014
Manufacturer's Name: Delta Controls
Manufacturer's Address: 17850 56th Avenue, Surrey, British Columbia, Canada V3S 1C7
Declares that the product(s):
Product Name: 16 x 16 Controllers
Model Numbers: DSC-1616, DFM-1616
Product Options: All
Conforms to the following Product Specifications:
Standard | Description | Class | Notes |
---|---|---|---|
EN 50081-1:1992 | Generic Emission Standard Part 1: Residential | Class A | |
EN 55022:1998 | Radiated and Conducted Emissions | Class A | |
EN 61000-3-2:1999 | Power Line Harmonics | Class A | |
EN 61000-3-3:1998 | Power Line Fluctuations | Pst < 1, Plt < 0.65 | |
EN 50082-1:1997 | Generic Immunity Standard Part 1: Residential | ||
EN 61000-4-2:1995 | ESD Immunity | Level B | |
EN 61000-4-3:1996 | RF Electromagnetic Field Immunity | Level A | |
ENV 50204:1995 | RF Electromagnetic Field Immunity (Keyed Carrier) | Level A | |
EN 61000-4-4:1995 | EFT/Burst Immunity | Level B | |
EN 61000-4-5:1995 | Surge Immunity | Level B | |
EN 61000-4-6:1996 | Conducted Immunity | Level A | |
EN 61000-4-11:1994 | Voltage Dips / Interruptions | Level A/B/B/B |
Supplementary Information: The product(s) herewith comply with the requirements of the EMC Directive 89/336/EEC. The product(s) were tested in a typical configuration.
Lee Dickson
Quality Assurance Manager
Signature: [Signature graphic]
FCC Compliance Information
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Industry Canada Compliance Statement
ICES-003 This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations
Cet appareil numérique de la Classe A Respecte toutes les exigences du Règlement sur le matérial brouiller du Canada.
UL This product conforms to the following UL requirements:
- UL916: Energy Management Equipment
- UL864*: Control Units and Accessories for Fire Alarm Systems, 9th Edition
* - Applicable to DSC-1616E-UL864 model only
Related Documents
![]() |
eZNT-Wi Programmable Wi-Fi Thermostat Application Guide Comprehensive application guide for the Delta Controls eZNT-Wi Programmable Wi-Fi Thermostat, detailing its features, Wi-Fi configuration, setup, troubleshooting, and integration within the enteliZONE product line. |
![]() |
Delta Controls DNS-24L Installation and Application Guide A comprehensive guide for installing, configuring, and programming the Delta Controls DNS-24L network sensor. Covers wiring, setup, software objects, and GCL+ programming for LINKnet systems. |
![]() |
Delta Controls eZVP-440E enteliZONE VAV Controller Details on the Delta Controls eZVP-440E enteliZONE VAV controller, a programmable native BACnet Ethernet controller with integrated airflow sensor and damper actuator for VAV and VVT applications. Includes features, specifications, and ordering information. |
![]() |
Delta Controls O3 Sense Multisensor Quick Start Guide Install and set up your Delta Controls O3 Sense multisensor device with this quick start guide. Learn about wiring, placement, configuration, and firmware upgrades using the O3 Setup app. |
![]() |
Delta Controls O3 App: Enhancing Occupant Experience and Building Efficiency Explore the Delta Controls O3 App, a smart building solution that engages occupants, enhances user experience, and provides valuable data for building management. Learn about its features like room detection, activity-based control, and direct control options. |
![]() |
Delta Controls enteliTOUCH Touchscreen Building Controller Delta Controls enteliTOUCH is a 7-inch touchscreen building controller providing intuitive graphic navigation and access to your building's BAS. Features include a high-resolution display, temperature sensor, optional motion sensing, and flexibility for web server capabilities or wireless hub functionality. |
![]() |
Delta Controls Red5 EDGE VAV Controller for Building Automation Discover the Delta Controls Red5 EDGE VAV controller, a fully integrated, programmable, and IoT-based Native BACnet VAV controller. Learn about its features including enhanced cybersecurity, improved accuracy, and easy installation for building automation. |
![]() |
Delta Controls eZV-440 VAV Controller: Features and Specifications Explore the Delta Controls eZV-440, a versatile VAV controller with integrated airflow sensor and damper actuator. Learn about its BACnet compatibility, configurable algorithms, and connectivity options for smart building systems. |