Models: RAM-280FSPH(D) RAM-335FSPH(D)
This manual ensures proper transfer to the next construction step and final delivery to the customer. The process includes: Transportation and Handling ➡️ Refrigerant Piping Work ➡️ Electrical Wiring ➡️ Test Run ➡️ Customer.
This air conditioner is for general use. Do not use for food, animals, plants, precision machinery, or art preservation.
Do not install in the following places:
Electromagnetic Wave Considerations:
Other Installation Precautions:
This section provides a "Safety Summary". Please read it carefully for correct installation.
Pay close attention to "Danger" and "Caution" markings. Installation errors can lead to significant harm.
After installation is complete, perform a test run to confirm there are no abnormalities. Follow the manual's instructions for methods and maintenance, and ensure customers keep the installation and operation manuals.
⚠️ When performing electrical work, ensure it is done by qualified personnel. Do not attempt to complete complex electrical work yourself to avoid electric shock.
Perform electrical work according to the Installation Manual and all relevant regulations and standards. Failure to do so may result in electric shock or fire due to insufficient capacity or inadequate performance.
⚠️ When installing, follow the installation manual precisely. Failure to do so may result in water leakage, electric shock, or fire.
Install the unit where it can withstand its weight. Incomplete installation can cause the unit to fall and result in injury.
Do not install near flammable gases or in locations where flammable gases are suspected, as this may cause fires or other accidents.
Do not climb on the air conditioner or place objects on top of it to avoid falling damage.
In case of refrigerant leakage, immediately turn off any fire sources (e.g., stoves), remove refrigerant from the ground, ventilate the area by opening doors and windows, and contact your service contractor.
Do not connect the indoor unit drain pipe directly to drainage ditches. Biogas can be produced and enter the indoor space, leading to poisoning.
Refer to the table for selecting the outdoor unit and the number/capacity of indoor units.
Outdoor Unit Model | Combination Capacity of Ratio (For Outdoor Unit) | Combination Quantity (Indoor Unit) |
---|---|---|
RAM-280FSPH(D) | 50~130% | 14 |
RAM-335FPSH(D) | 14 | 14 |
For systems where all indoor units operate simultaneously, the total indoor unit capacity should be less than or equal to the outdoor unit capacity.
For systems where indoor units do not operate simultaneously, the total indoor unit capacity can be up to the maximum against the outdoor unit capacity.
Item | Condition | Air inlet temperature of outdoor unit | Air inlet temperature of indoor unit (non-room temperature) |
---|---|---|---|
Cooling | -5°C DB ~ 43°C DB | 21°C DB/15°C WB ~ 32°C DB/23°C WB |
DB: Dry Bulb, WB: Wet Bulb
The cooling operation shall be performed using the same refrigerant system for the indoor unit.
This system has a 4-hour protection feature; stop reason code "d1-22" will be displayed. To operate within 4 hours, follow these steps:
Observe the following items when transporting the outdoor unit. Keep the packaging intact as much as possible until it reaches the installation location.
Hanging Method Under Packing Condition:
Hang the unit using two ropes. Ensure the rope length is between 0.7m and 1.0m. Do not remove the top packing material and tape during hanging. Push wire rope through the hang hole and secure with a shackle.
Confirm the following accessory parts for the outdoor unit before installation.
Accessory | Q'ty | Use Place | Use Method |
---|---|---|---|
Pipe Combination | 1 | Use to connect gas piping. | Please refer to the piping work on page 9. |
Drain Connector | 1 | Base condensation water exhaust. | Please refer to the foundation work on page 9. |
Washer | 1 |
R410A refrigerant operates at approximately 1.4 times the pressure of R22 and is more susceptible to moisture, acid materials, oil, and other impurities. The refrigerant oil also differs. During installation, be careful to avoid water, impurities, and mixing with existing refrigerants or oils.
The product's design pressure is 4.15 MPaG.
To prevent accidental mixing of different refrigerants or oils, charging connection sizes have changed. Special R410A tools are necessary. Tools that contact refrigerant must be specifically for the new refrigerant.
Symbol Description:
Measuring Instrument and Tool | Interchangeability with R22 | Reason of Non-Interchangeability and Attention (Only for new refrigerant) (Strictly Required) | Use | |
---|---|---|---|---|
R407C | R410A | |||
Pipe Cutter | ◍ | ○ | Cutting Pipe; Removing Burrs | |
Flaring Tool | ◍ | ○ | To ensure the high pressure of R410A, if using flaring tube, make the dimension of tube larger for R410A. If you continue to use existent products, shall be used with the flaring tube adjustment gasket (1mm). Using the 1/2H pipe situation, can not be processed. (R410A special flaring tool can be used directly in the R407C) | Flaring for Tubes |
Extrusion Adjustment Gauge | (Not use) | ○ | Using the 1/2H pipe situation, can not be processed. | Dimensional Control for Extrusion Portion of Tube after Flaring |
Pipe Bender | ◍ | ○ | Using the 1/2H pipe situation, can not be processed. Please use the elbow welding connection. | Bending |
Expanding Tool | ◍ | ○ | Using the 1/2H pipe situation, can not be processed. Please use the elbow welding connection. | Expanding Tubes |
Torque Wrench | ◍ | ○ | R410A for Φ12.7, Φ15.88; spanner size is up 2mm; existent products can not be used. For Φ6.35, Φ9.53, Φ19.05; spanner size is the same. | Connection of Flare Nut |
Brazing Tool | ◍ | ○ | Perform correct brazing work. | Brazing for Tubes |
Nitrogen Gas | ◍ | ○ | Strict control against contamination. (Blow nitrogen during brazing) | Prevention from Oxidation during Brazing |
Lubrication Oil (for Flare Surface) | ● | ○ | Do not use R22 with mineral oil, and products must be used the same synthetic oil. Synthetic oil absorbs moisture quickly, Therefore, to avoid damp places. | Applying Oil to the Flared Surface |
Measuring Instrument and Tool | Interchangeability with R22 | Reason of Non-Interchangeability and Attention (Only for new refrigerant) (Strictly Required) | Use | |
---|---|---|---|---|
R407C | R410A | |||
Refrigerant Cylinder | (Brown) | (Pink) | Check refrigerant cylinder color. Filled with the gas refrigerant is strictly prohibited. Liquid refrigerant charging is required regarding Non-azeotropic refrigerant. | Refrigerant Charging |
Vacuum Pump | ☍ | ○ | The current ones are applicable. However, it is required to mount a vacuum pump adapter which can prevent from reverse flow when a vacuum pump stops, resulting in no reverse oil flow. | Vacuum Pumping |
Refrigerant Change Adapter for Vacuum Pump (Prevent from reverse) | ☍ | ○ |
For R410A piping and connection parts, flare nut and pipe flare sizes have changed. Refer to the specifications below.
Piping Diameter dø | Dimension A | Unit: mm | |
---|---|---|---|
R407C, R22 | R410A | ||
6.35 | 9.0 | 9.1 | |
9.53 | 13.0 | 13.2 | |
12.7 | 16.2 | 16.6 | |
15.88 | 19.4 | 19.7 | |
19.05 | 23.3 |
☍: Can not be processed (1/2H material)
☍ Please use the attached flare connecting pipe.
Due to design pressure changes, pipe thickness and material must also be changed.
Pipe Size | Existent Type R22 | New Refrigerant R407C | New Refrigerant R410A | |||
---|---|---|---|---|---|---|
Thickness | Material | Thickness | Material | Thickness | Material | |
Φ6.35 | 0.6 | O | 0.8 | O | 0.8 | O |
Φ9.53 | 0.8 | O | 0.8 | O | 0.8 | O |
Φ12.7 | 0.8 | O | 0.8 | O | 0.8 | O |
Φ15.88 | 1.0 | O | 1.0 | O | 1.0 | O |
Φ19.05 | 1.0 | O | 1.0 | O | 1.0 | 1/2H |
Φ22.2 | 1.2 | O | 1.15 | O | 1.0 | 1/2H |
Φ25.4 | 1.2 | O | 1.0 | 1/2H | 1.0 | 1/2H |
Φ28.6 | 1.4 | O | 1.0 | 1/2H | 1.0 | 1/2H |
Due to design pressure changes, connection pipe (elbow, etc.) thickness also changes. When using 1/2H material, bending and flaring cannot be processed. Follow the rules below for minimum thickness selection. Note that flare nut sizes also change.
Pipe Size | Connection Minimum Thickness (mm) | Pipe Size | Connection Minimum Thickness (mm) | |||
---|---|---|---|---|---|---|
R407C, R22 | R410A | R407C, R22 | R410A | |||
Φ6.35 | 0.5 | 0.5 | Φ22.2 | 0.9 | 0.9 | |
Φ9.53 | 0.6 | 0.6 | Φ25.4 | 0.95 | 0.95 | |
Φ12.7 | 0.7 | 0.7 | Φ28.6 | 1.0 | 1.0 | |
Φ15.88 | 0.8 | 0.8 | Φ31.75 | 1.05 | 1.1 | |
Φ19.05 | 0.8 | 0.8 | Φ38.1 | 1.25 | 1.35 |
Flare Nut Size B(mm) | Flare Nut Size B(mm) | |||
---|---|---|---|---|
Pipe Size | R407C, R22 / R410A | Pipe Size | R407C, R22 / R410A | |
Φ6.35 | 17 | Φ15.88 | 27 / 29 | |
Φ9.53 | 22 | Φ19.05 | 36 / 36 | |
Φ12.7 | 24 / 26 |
Select the installation location carefully, considering the following points:
For installations on roofs or open spaces prone to strong winds, follow these instructions:
Please note that strong winds blowing directly against the air outlet grille can prevent necessary airflow and lead to unit failure.
Wind Break Cover Plate Type:
Type | Q'ty |
---|---|
WSP-335A | 2 |
In open spaces, use steel wire cables or other means to secure the unit against strong winds.
Ensure adequate maintenance space around the outdoor unit as shown below.
(a) When the above is open
(b) When obstruction is at the top
(a) When the above is open
(a) When the above is open
(b) When obstruction is at the top
If the 170mm dimension is ensured and there is no interference with the foundation base, piping work can be directed downwards.
To prevent the unit from dumping, excessive noise, or tilting due to gusts and earthquakes, ensure the foundation work is robust. Use fixed brackets and consider installing anti-vibration rubber if necessary to isolate vibration transmission to buildings.
During defrost operation, condensation water is discharged. Select the best drainage area and ensure water flows to a drainage ditch. The drain hole position is shown with dimensions.
When using standard parts shelves that are narrower than the outdoor unit base bracket, follow the figure below. Use a wider flat base to support the full weight of the outdoor unit between the standard parts shelf and the outdoor unit base bracket feet.
The pipe can be connected in four directions.
Size | ΦA | ΦB |
---|---|---|
RAM-280FSPH(D) | 12.7 | 28.6 |
RAM-335FSPH(D) | 12.7 | 28.6 |
(Unit: mm)
Pipe Combination (Accessory Parts):
Connect the indoor and outdoor units with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points to prevent it from touching weak parts of the building (e.g., walls, ceilings). Touching can cause abnormal sound due to vibration. Pay special attention for short piping lengths.
Longer pipes can reduce air conditioner cooling and heating capacity. This factor must be considered when selecting piping specifications.
Maximum Piping Length | Actual Length | L1+L2+l3 : 150m Below | |||
Equivalent Length | L1+L2+l3 : 190m Below | ||||
The Total Length | L1+L2+l0+l1+l2+l3 : 300m Below | ||||
Maximum Lift between Outdoor Unit and Indoor Unit | The outdoor unit is higher than that of indoor unit. | H 1 : 50m Below | |||
The outdoor unit is lower than that of indoor unit. | H 1 : 40m Below | ||||
Between each indoor unit | H2 : 15m Below | ||||
Maximum Piping Length | Between Each Multi-Kit and Each Indoor Unit | l0, l1, l2, l3 : 15m Below | |||
Between Multi-kit "a" And the Farthest Indoor Unit | l4 : 40m Below |
Multi-kit And Connection Pipe | Outdoor Unit Model | Gas/Liquid Pipe Size (Φ mm) | Multi-Kit Pipe Type |
---|---|---|---|
The First Multi-Kit Pipe (a) And L1 Connection Pipe | RAM-280FSPH(D) | 28.6 / 12.7 | E-NP452S |
RAM-335FPS(D) | 28.6 / 12.7 | E-NP452S |
Others Multi-kit Pipe And Connection Pipe | Indoor Unit Total Capacity (kW) | Gas/Liquid Pipe Size (Φ mm) | Multi-Kit Pipe Type |
---|---|---|---|
27≤ | 28.6 / 12.7 | E-NP452S | |
23~26.99 | 25.4 / 9.53 | E-NP282S | |
15~22.99 | 22.2 / 9.53 | E-N55HT ※1 | |
'15 | 19.05 / 9.53 | E-N55HT ※1 |
※1: E-N55HT (Header Branch), it can be used that each indoor unit distribution and connection.
Multi-kit pipes must follow requirements; remove unused pipes. Welding other pipes into the multi-kit pipe is necessary to avoid reducing cooling capacity.
For multi-kit pipes connected to indoor units, use optional multi-kit pipe set parts to prevent uneven refrigerant distribution and capacity reduction. Do not connect using standard connectors.
1) Line Branch (Use the line branch pipe), As shown below:
It is divided into two kinds: upward and downward.
Note: The header branch pipe cannot be continuously installed.
The header branch pipe must be installed horizontally.
Note: 1. The line branch pipe cannot be connected after the header branch pipe. 2. The first branch pipe cannot use the header branch pipe.
Piping Size (mm) and Flare Nut | Tightening Torque (N·m) | Spindle Valve Torque (N·m) | |||
---|---|---|---|---|---|
Gas | Liquid | Gas | Liquid | ||
Φ6.35 (1/4") | 20 | 20~25 | Hexagonal Wrench | ||
Φ9.53 (3/8") | 40 | Gas | Liquid | ||
Φ12.7 (1/2") | 60 | 10mm | 5mm | ||
Φ15.88 (5/8") | 80 | ||||
Φ19.05 (3/4") | 100 |
(1) After connection piping and before the airtight test, remove the liquid and gas stop valve caps. Ensure the spindle valve is closed with the specified torque. Do not overtighten the flare nut, as it can cause spindle valve leakage.
Do Not Apply the Double Spanner Work Here. Refrigerant Leakage Shall Occur.
Note: 1. A slight refrigerant leakage sound when removing the spindle valve cap of the stop valve is normal. 2. Use tools and measuring instruments specifically designed for new refrigerant (R410A). 3. If a vacuum degree of -0.1MPa (-750mmHg) is not achieved, leakage is considered to exist. Check for gas leakage again. If no leakage is found, operate the vacuum pump for one to two hours.
Implement vacuum drying determination to confirm the absence of water in the system. If moisture is present, extend vacuum time or install a drying filter. Failure to do so can lead to unit failure and difficulties in handling.
The outdoor unit is pre-filled with refrigerant, but additional refrigerant may be needed based on pipe length. Calculate the filling amount using the following formula and table:
Calculation Formula:
W: Additional refrigerant of liquid pipe (kg) = W11 + W12 + W13
W Total =
Model | The factory refrigerant charging weight (kg) | Additional refrigerant (kg) | Additional refrigerant upper limit (kg) |
---|---|---|---|
RAM-280FSPH(D) | 6.5 | 13.5 | |
RAM-335FSPH(D) | 7.8 |
☍ Additional refrigerant W exceeds the amount of additional refrigerant filling upper limit, adjust the length of piping, such that W does not exceed the value of upper limit.
The Cap Tightening Torque:
Be sure to perform the air-tight test. Additional refrigerant that is too much or too little can result in compressor failure or other abnormal conditions. Charge refrigerant according to calculated values.
Liquid piping must be thermally insulated to prevent poor performance and condensation on low-pressure pipe surfaces.
When installing air conditioners in rooms, refrigerant concentration must not exceed specified limits in case of leakage. R410A is non-flammable and non-toxic, but significant leakage filling a room can cause choking hazards. This is especially true for long-distance piping connections with large refrigerant amounts. Ensure indoor unit installation is in a room where refrigerant concentration can be kept below limits even in case of leakage.
Calculate limits refrigerant concentration by the following formula:
The total amount of refrigerant within the system (kg) / Installation the product of the room indoor volume (m³) ≤ limits refrigerant concentration
R410A (0.3kg / m³)
If the calculation result exceeds the limits, implement the following treatment methods:
Example: Total amount of refrigerant within the system: 20kg
Note: 1) The amount of leakage refrigerant is 20kg for all room sizes. 2) The room must not exceed the limits refrigerant concentration of 0.42kg/m³.
Outdoor Unit Model | Cooling Capacity R410A |
---|---|
RAM-280FSPH(D) | 4.11 Ton |
RAM-335FSPH(D) | 4.11 Ton |
New refrigerant R410A product notes: Since R410A is a non-azeotropic refrigerant, its composition changes upon leakage. It cannot be directly added; reprocessing is required.
Measure pressure data from the check joints of the gas line stop valve (A) and the piping line (B). Adjust high and low pressure positions based on the operation state. Refer to the table for details.
Cooling | |
---|---|
The check joints of gas line stop valve Ⓐ | Low pressure |
The check joints of piping line Ⓑ | High pressure |
The check joints of liquid line stop valve Ⓒ | When vacuum, maintenance services use to charge the refrigerant specially. |
When moving the unit, recover outdoor refrigerant following these steps:
Please do not let the low-pressure gauge measure pressure lower than -0.01MPa. Low pressure below -0.01MPa during refrigerant recovery can result in compressor failure.
CAUTION: All field wiring and electrical components must comply with local codes.
Item | Model | Power Supply (60Hz) | Maximum Current (A) | Number of Poles | ELB (Earth Leakage Breaker) | Power Switch | Fuse Capacity (A) | Power Supply Size (mm²) | Earth Wire Size (mm²) | Transmission Cable Size | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Rating Sensitivity Current (mA) | Rating Current (A) | Switch Capacity (A) 1 | Switch Capacity (A) 2 | |||||||||
RAM-280FSPH | 230V | 37 | 3 | 100 | 60 | 60 | 50 | 14 | 5.5 | 2-Core Shielded Twist Pair Cable 0.75mm² | ||
RAM-335FSPH | Total Length 1000m Below | |||||||||||
RAM-280FSPHD | 380V | 23 | 4 | 30 | 40 | 40 | 25 | 8 | 3.5 | |||
RAM-335FSPHD |
Note: When selecting the earth leakage breaker specification, refer to the table above. For 380V power supply, use 3Φ4 wire.
※ Piping thermal insulation material: Please use heat-resistant specification products that can withstand high-temperature gas piping.
Follow these essentials for power source cords and transmission cables:
Caution of Indoor and Outdoor Unit Connection Wiring Construction:
Keep the transmission cable and 220V power source cord more than 5-6cm apart. Do not use coaxial cable. Incorrect connection of transmission cable and power source cord can burn the outdoor unit's PCB.
After wiring, seal to prevent water invasion into the metal conduit pipe. Ensure terminal plugs are attached with insulation tape or sleeve.
TURN OFF all power sources before setting. Switches will not function, and settings will be invalid if power is on.
For multiple outdoor units sharing the same transmission line, set the refrigerant cycle number and end terminal resistance.
The unit is factory set with pin 1 of DSW5 at the "ON" side. If there are 2 or more outdoor units in the same H-link, set pin 1 of DSW5 to "OFF" for the 2nd unit onwards. If only one outdoor unit is used, no setting is required.
Set the lift difference between the outdoor and indoor units using DIP switch (DSW6) on the outdoor unit PCB.
Settings for Factory Setting, Cooling Operation, and Compressor Forced Stop.
Settings for High Efficiency Fan Motor, Function Setting, and External I/O Setting.
Each model is set based on the table.
Before starting the test run, re-confirm the installation for any problems and check the following:
After installation is complete, perform the test run according to the following procedure. Confirm there is no abnormal operation before handing over the system to the customer.
Number of The Unit | 0 | 1 | 2 | 3 | 4 | ... | 10 | 11 | ... | 63 | |
---|---|---|---|---|---|---|---|---|---|---|---|
Timer Setting Display Left Two Digit | 01 02 03 04 05 ... 11 12 ... 64 | ||||||||||
Ref. Cycle NO. | 0 | 1 | 2 | 3 | 4 | ... | 10 | 11 | ... | 63 | |
Timer Setting Display Right Two Digit | 01 02 03 04 05 ... 11 12 ... 64 |
Note: After the product stops operation, the compressor continues to run for a period (about 10 minutes) to recover piping refrigerant to the outdoor unit. This is not a product failure or abnormality. During test running, if a protection device activates due to an abnormality, the controller's operation indicator will blink, displaying "Alarm" (abnormality), and the setting temperature display will show the alarm code.
Refer to page 22 for alarm codes and treatment. If unable to resolve, contact your contractor.
Code | Distinction | Content of Abnormality | Leading Cause |
---|---|---|---|
01 | Indoor Unit | Indoor Unit Activation of Protection Device (Float Switch) | Activation of Float Switch (High water Level Drain Pan, Abnormality of Drainpipe, Float Switch or Drain Pan) |
02 | Outdoor Unit | Outdoor Unit Activation of Protection Device | Activation of High Pressure Switch (4.15MPa); Air Conditioner Outdoor Unit Fan Motor Lock. |
03 | Wiring | Transmission Abnormality between Indoor and Outdoor | Incorrect Wiring, Loose Terminals, Disconnect Wire, Blowout of Fuse, Outdoor Unit Power OFF. |
04 | Inverter | Transmission Abnormality between Inverter PCB and Outdoor PCB | Inverter PCB - Outdoor PCB Transmission Failure (Loose Connector, Wire Breaking, Blowout of Fuse), Abnormal fan motor controller transmitted, "04" the lower right will be "Signal flashing". |
05 | Wiring | Abnormality Power Source Phases | Incorrect Power Source Phases, Connection to Reversed Phases, Open-Phases. |
06 | Voltage | Abnormality Inverter Voltage | Outdoor Voltage Drop, Insufficient Power Capacity. |
07 | Refrigerant Cycle System | Decrease in Discharge Gas Superheat | Excessive Refrigerant Charge, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Opened Position (Disconnect Connector). |
08 | Increase in Discharge Gas Temperature | Insufficient Refrigerant Charge, Pipe Clogging, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Closed Position (Disconnect Connector). | |
11 | Indoor Unit Thermistor | Abnormality Inlet Air Thermistor (Indoor) | Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. |
12 | Abnormality Outlet Air Thermistor (Indoor) | Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. | |
13 | Abnormality Freeze Protection Thermistor (Indoor) | Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. | |
14 | Abnormality Gas Piping Thermistor (Indoor) | Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. | |
19 | Activation of Protection for Indoor Fan Motor | Fan Motor Overheat, Locking. | |
21 | Outdoor Unit Thermistor | Abnormality High Pressure Thermistor (Outdoor) | Thermistor Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit. |
22 | Abnormality Outdoor Air Thermistor | ||
23 | Abnormality Discharge Pipe Thermistor (Outdoor) | ||
24 | Abnormality Heat Exchanger Liquid Pipe Thermistor (Outdoor) | ||
29 | Abnormality Low Pressure Thermistor (Outdoor) | ||
31 | System | Incorrect Capacity Setting of Outdoor and Indoor Unit | Incorrect Capacity Code Setting of Combination; Excessive or Insufficient Indoor Unit Total Capacity Code (outside of 80~120%) |
35 | Incorrect Setting of Indoor Unit No. | Duplication of Indoor Unit No. In Same Ref. Gr., or The Connection Unit Number Exceeds the Maximum Number of Combination. | |
38 | Outdoor Unit | Abnormality of Picking Up Circuit for Protection (Outdoor) | Failure of Protection Detecting Device (Incorrect Wiring of Outdoor PCB) |
43 | Activation of Low Pressure Decrease Protection Device | Defective Compressor (Failure of Compressor of Inverter, Loose Power Supply Connection) | |
44 | Pressure | Activation of Low Pressure Increase Protection Device | Overload at Cooling, High Temperature at Expansion Valve Locking (Loose Connector) |
45 | Activation of High Pressure Increase Protection Device | Overload Operation (Clogging, Short-Pass), Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing. | |
47 | Activation of Low Pressure Decrease Protection Device (Vacuum Operation Protection) | Insufficient Refrigerant, Pipe Clogging, Expansion Valve Locking at Open Position (Loose Connector). | |
48 | Outdoor Unit | Activation of Inverter Overcurrent Protection Device | Overload Operation, Compressor Failure. |
51 | Inverter | Abnormality Inverter Current Sensor | Current Sensor Failure. |
53 | IPM Protection Activation | Driver IC Error Signal Detection (Protection for Overcurrent, Low Voltage) | |
54 | Activation of Inverter Fin Thermistor Protection | Abnormality Fin Thermistor, Heat Exchanger Clogging, Fan Motor Failure. | |
55 | Inverter Failure | Inverter PCB Failure | |
57 | Outdoor Unit | Activation of Outdoor Fan Controller Protection | Abnormality Fan Controller Protection (Overcurrent), Fin Overheat |
EE | Compressor | Compressor Protection Alarm | Compressor Occurred Three Times of Abnormality within 6 Hour. |
b1 | Wiring | Incorrect Outdoor Unit Address Number or Unit Number Setting | Over 64 Number Is Set for Address or Refrigerant Cycle. |
b5 | Number of Indoor Units Connected Error. | Connection of Non-H-LINK-II Indoor Unit More Than 17 Units. |
PS: Remote control operation indicator flashes once every 2 seconds. Symbol between indoor unit and remote control indicates transmission abnormality (connector loss, loose, incorrect wiring, disconnection).
4) Finally, deliver the guarantee, operation manual, and installation manual, etc. to the customer.
Danger: Before test running preparation, do not start running. Be sure to confirm electrical wiring, etc.
MODEL: | SERIAL. No. | COMPRESSOR MFG. No. | DATE: | ||||
---|---|---|---|---|---|---|---|
CUSTOMER'S NAME AND ADDRESS: | |||||||
1. Is the rotation direction of the indoor coil fan correct? | |||||||
2. Is the rotation direction of the outdoor coil fan correct? | |||||||
3. Are there any abnormal compressor sounds? | |||||||
4. Has the unit been operated at least twenty (20) minutes? | |||||||
5. Check Room Temperature | |||||||
Inlet: No. 1 DB /WB °C, No. 2 DB /WB °C, No. 3 DB /WB °C, No. 4 DB /WB °C, | |||||||
Outlet: DB /WB °C, DB /WB °C, DB /WB °C, DB /WB °C, | |||||||
Inlet: No. 5 DB /WB °C, No. 6 DB /WB °C, No. 7 DB /WB °C, No. 8 DB /WB °C, | |||||||
Outlet: DB /WB °C, DB /WB °C, DB /WB °C, DB /WB °C, | |||||||
6. Check Outdoor Ambient Temperature | |||||||
Inlet: DB °C, WB °C, Outlet: DB °C, WB °C | |||||||
7. Check Refrigerant Temperature: Operating Mode (Cool) | |||||||
Discharge Gas Temperature: Td= °C | |||||||
Liquid Pipe Temperature: Te= °C | |||||||
8. Check Pressure | |||||||
Discharge Pressure: Pd= MPa | |||||||
Suction Pressure: Ps= MPa | |||||||
9. Check Voltage | |||||||
Rated Voltage: V | |||||||
Operating Voltage: L1-L2 V, L1-L3 V, L2-L3 V | |||||||
Starting Voltage: V | |||||||
10. Check Compressor Input Running Current | |||||||
Input: kW | |||||||
Running Current: A | |||||||
11. Is the refrigerant charge adequate? | |||||||
12. Do the operation control devices operate correctly? | |||||||
13. Do the safety devices operate correctly? | |||||||
14. Has the unit been checked for refrigerant leakage? | |||||||
15. Is the unit clean inside and outside? | |||||||
16. Are all cabinet panels fixed? | |||||||
17. Are all cabinet panels free from rattles? | |||||||
18. Is the filter clean? | |||||||
19. Is the heat exchanger clean? | |||||||
20. Are the stop valves open? | |||||||
21. Does the drain water flow smoothly from the drain pipe? |
File Info : application/pdf, 24 Pages, 3.48MB
DocumentDocument![]() |
Hitachi Inverter-Driven Multi-Split System Operation Manual Comprehensive operation manual for Hitachi Inverter-Driven Multi-Split Air Conditioning Systems, covering installation, operation, maintenance, and troubleshooting for models like 65MP2180-A1 and RAM-FPS(B/D). |
![]() |
Hitachi Split Unit Inverter Air Conditioner Outdoor Unit Installation Manual This manual provides detailed instructions for the installation of Hitachi Split Unit Inverter Air Conditioners, covering safety precautions, handling, installation procedures, piping, wiring, test runs, and error codes. |
![]() |
Hitachi Inverter-Driven Multi-Split Air Conditioner Operation Manual Official operation manual for Hitachi Inverter-Driven Multi-Split Air Conditioning Systems. Includes safety guidelines, operating instructions, maintenance procedures, troubleshooting tips, and error code explanations. |
![]() |
Hitachi Air Conditioner Operation Manual This operation manual provides detailed instructions for the safe and efficient use of Hitachi Inverter-Driven Multi-Split System Air Conditioners. It covers installation precautions, operating procedures, maintenance, troubleshooting, and safety guidelines. |
![]() |
Hitachi Inverter-Driven Multi-Split System Air Conditioners Operation Manual This operation manual provides detailed instructions for Hitachi Inverter-Driven Multi-Split System Air Conditioners, covering installation, operation, maintenance, troubleshooting, and safety precautions. It includes information on remote controls, unit types, operation ranges, and error indications. |
![]() |
Hitachi air365 Max Series Outdoor Units: Installation & Maintenance Manual Comprehensive installation and maintenance guide for Hitachi air365 Max Series inverter-driven outdoor air conditioning units, covering models RAS-080CNCCLI to RAS-300CNCCLI. |
![]() |
Hitachi M400 Multi-Zone Mini-Split Systems: Efficient Cooling and Heating Explore the Hitachi M400 Multi-Zone Mini-Split Systems, offering flexible, energy-efficient ductless cooling and heating solutions. Features include a human sensor system, airCloud Home app control, and multiple indoor unit options for up to five zones. |
![]() |
Hitachi Inverter-Driven Split System Heat Pump Air Conditioners Technical Catalog Comprehensive technical catalog for Hitachi Inverter-Driven Split System Heat Pump Air Conditioners, DC Inverter UTOPIA series, detailing specifications, safety, and model information for RAS-4HVNC1, RAS-5HVNC1, and RAS-6HVNC1. |