HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM AIR CONDITIONERS

Outdoor Units

Installation & Maintenance Manual

Models: RAM-280FSPH(D) RAM-335FSPH(D)

This manual ensures proper transfer to the next construction step and final delivery to the customer. The process includes: Transportation and Handling ➡️ Refrigerant Piping Work ➡️ Electrical Wiring ➡️ Test Run ➡️ Customer.

Important Notice

This air conditioner is for general use. Do not use for food, animals, plants, precision machinery, or art preservation.

Do not install in the following places:

Electromagnetic Wave Considerations:

Other Installation Precautions:

Safety Summary

This section provides a "Safety Summary". Please read it carefully for correct installation.

Pay close attention to "Danger" and "Caution" markings. Installation errors can lead to significant harm.

After installation is complete, perform a test run to confirm there are no abnormalities. Follow the manual's instructions for methods and maintenance, and ensure customers keep the installation and operation manuals.

Definition for signal words

About Electrical Works

⚠️ When performing electrical work, ensure it is done by qualified personnel. Do not attempt to complete complex electrical work yourself to avoid electric shock.

Perform electrical work according to the Installation Manual and all relevant regulations and standards. Failure to do so may result in electric shock or fire due to insufficient capacity or inadequate performance.

About Installation

⚠️ When installing, follow the installation manual precisely. Failure to do so may result in water leakage, electric shock, or fire.

Install the unit where it can withstand its weight. Incomplete installation can cause the unit to fall and result in injury.

Do not install near flammable gases or in locations where flammable gases are suspected, as this may cause fires or other accidents.

Do not climb on the air conditioner or place objects on top of it to avoid falling damage.

In case of refrigerant leakage, immediately turn off any fire sources (e.g., stoves), remove refrigerant from the ground, ventilate the area by opening doors and windows, and contact your service contractor.

Do not connect the indoor unit drain pipe directly to drainage ditches. Biogas can be produced and enter the indoor space, leading to poisoning.

Caution

1. Common Items

1.1 Combination of Indoor Unit and Outdoor Unit

Refer to the table for selecting the outdoor unit and the number/capacity of indoor units.

Outdoor Unit Model Combination Capacity of Ratio (For Outdoor Unit) Combination Quantity (Indoor Unit)
RAM-280FSPH(D) 50~130% 14
RAM-335FPSH(D) 14 14

For systems where all indoor units operate simultaneously, the total indoor unit capacity should be less than or equal to the outdoor unit capacity.

For systems where indoor units do not operate simultaneously, the total indoor unit capacity can be up to the maximum against the outdoor unit capacity.

1.2 Operation Temperature Range

Item Condition Air inlet temperature of outdoor unit Air inlet temperature of indoor unit (non-room temperature)
Cooling -5°C DB ~ 43°C DB 21°C DB/15°C WB ~ 32°C DB/23°C WB

DB: Dry Bulb, WB: Wet Bulb

1.3 Cooling Operating Instructions

The cooling operation shall be performed using the same refrigerant system for the indoor unit.

1.4 Note

This system has a 4-hour protection feature; stop reason code "d1-22" will be displayed. To operate within 4 hours, follow these steps:

  1. Power ON the indoor and outdoor units.
  2. Wait 30 seconds.
  3. Press the outdoor unit's PSW1 button for more than 3 seconds.

2. Transportation and Handling

2.1 Transporting the Outdoor Unit

Observe the following items when transporting the outdoor unit. Keep the packaging intact as much as possible until it reaches the installation location.

Hanging Method Under Packing Condition:

Hang the unit using two ropes. Ensure the rope length is between 0.7m and 1.0m. Do not remove the top packing material and tape during hanging. Push wire rope through the hang hole and secure with a shackle.

Diagram showing the outdoor unit being lifted by two ropes. It indicates the center of gravity, handle, and wooden base. The angle for hanging is shown as 60° Above.

2.2 Accessory Parts

Confirm the following accessory parts for the outdoor unit before installation.

Accessory Q'ty Use Place Use Method
Pipe Combination 1 Use to connect gas piping. Please refer to the piping work on page 9.
Drain Connector 1 Base condensation water exhaust. Please refer to the foundation work on page 9.
Washer 1

3. Before Installation

3.1 R410A Refrigerant Considerations

R410A refrigerant operates at approximately 1.4 times the pressure of R22 and is more susceptible to moisture, acid materials, oil, and other impurities. The refrigerant oil also differs. During installation, be careful to avoid water, impurities, and mixing with existing refrigerants or oils.

The product's design pressure is 4.15 MPaG.

3.2 Special R410A Tools Required

To prevent accidental mixing of different refrigerants or oils, charging connection sizes have changed. Special R410A tools are necessary. Tools that contact refrigerant must be specifically for the new refrigerant.

Symbol Description:

Measuring Instrument and Tool Interchangeability with R22 Reason of Non-Interchangeability and Attention (Only for new refrigerant) (Strictly Required) Use
R407C R410A
Pipe Cutter Cutting Pipe; Removing Burrs
Flaring Tool To ensure the high pressure of R410A, if using flaring tube, make the dimension of tube larger for R410A. If you continue to use existent products, shall be used with the flaring tube adjustment gasket (1mm). Using the 1/2H pipe situation, can not be processed. (R410A special flaring tool can be used directly in the R407C) Flaring for Tubes
Extrusion Adjustment Gauge (Not use) Using the 1/2H pipe situation, can not be processed. Dimensional Control for Extrusion Portion of Tube after Flaring
Pipe Bender Using the 1/2H pipe situation, can not be processed. Please use the elbow welding connection. Bending
Expanding Tool Using the 1/2H pipe situation, can not be processed. Please use the elbow welding connection. Expanding Tubes
Torque Wrench R410A for Φ12.7, Φ15.88; spanner size is up 2mm; existent products can not be used. For Φ6.35, Φ9.53, Φ19.05; spanner size is the same. Connection of Flare Nut
Brazing Tool Perform correct brazing work. Brazing for Tubes
Nitrogen Gas Strict control against contamination. (Blow nitrogen during brazing) Prevention from Oxidation during Brazing
Lubrication Oil (for Flare Surface) Do not use R22 with mineral oil, and products must be used the same synthetic oil. Synthetic oil absorbs moisture quickly, Therefore, to avoid damp places. Applying Oil to the Flared Surface
Measuring Instrument and Tool Interchangeability with R22 Reason of Non-Interchangeability and Attention (Only for new refrigerant) (Strictly Required) Use
R407C R410A
Refrigerant Cylinder (Brown) (Pink) Check refrigerant cylinder color. Filled with the gas refrigerant is strictly prohibited. Liquid refrigerant charging is required regarding Non-azeotropic refrigerant. Refrigerant Charging
Vacuum Pump The current ones are applicable. However, it is required to mount a vacuum pump adapter which can prevent from reverse flow when a vacuum pump stops, resulting in no reverse oil flow. Vacuum Pumping
Refrigerant Change Adapter for Vacuum Pump (Prevent from reverse)

3.3 Piping and Connection Parts

For R410A piping and connection parts, flare nut and pipe flare sizes have changed. Refer to the specifications below.

Diagram showing pipe flare dimensions with angles (90°±2°, 45°±2°) and diameters (dø, Aφ).
Piping Diameter dø Dimension A Unit: mm
R407C, R22 R410A
6.35 9.0 9.1
9.53 13.0 13.2
12.7 16.2 16.6
15.88 19.4 19.7
19.05 23.3

☍: Can not be processed (1/2H material)

☍ Please use the attached flare connecting pipe.

Pipe Thickness Selection

Due to design pressure changes, pipe thickness and material must also be changed.

Pipe Size Existent Type R22 New Refrigerant R407C New Refrigerant R410A
Thickness Material Thickness Material Thickness Material
Φ6.35 0.6 O 0.8 O 0.8 O
Φ9.53 0.8 O 0.8 O 0.8 O
Φ12.7 0.8 O 0.8 O 0.8 O
Φ15.88 1.0 O 1.0 O 1.0 O
Φ19.05 1.0 O 1.0 O 1.0 1/2H
Φ22.2 1.2 O 1.15 O 1.0 1/2H
Φ25.4 1.2 O 1.0 1/2H 1.0 1/2H
Φ28.6 1.4 O 1.0 1/2H 1.0 1/2H

Connection Selection

Due to design pressure changes, connection pipe (elbow, etc.) thickness also changes. When using 1/2H material, bending and flaring cannot be processed. Follow the rules below for minimum thickness selection. Note that flare nut sizes also change.

Pipe Size Connection Minimum Thickness (mm) Pipe Size Connection Minimum Thickness (mm)
R407C, R22 R410A R407C, R22 R410A
Φ6.35 0.5 0.5 Φ22.2 0.9 0.9
Φ9.53 0.6 0.6 Φ25.4 0.95 0.95
Φ12.7 0.7 0.7 Φ28.6 1.0 1.0
Φ15.88 0.8 0.8 Φ31.75 1.05 1.1
Φ19.05 0.8 0.8 Φ38.1 1.25 1.35
Flare Nut Size B(mm) Flare Nut Size B(mm)
Pipe Size R407C, R22 / R410A Pipe Size R407C, R22 / R410A
Φ6.35 17 Φ15.88 27 / 29
Φ9.53 22 Φ19.05 36 / 36
Φ12.7 24 / 26

4. Installation Work

4.1 Outdoor Unit Installation Place Selection (Common Items)

Select the installation location carefully, considering the following points:

  1. Ensure adequate space for normal operation and maintenance.
  2. Install where ventilation is good and the area is dry.
  3. Install in a shaded location, away from direct sunlight or high-temperature heat radiation.
  4. Choose a spot where the unit's sound will not disturb neighbors.
  5. The unit's air outlet should not blow directly towards plants or neighbors' windows.
  6. Provide a foundation to support all feet of the outdoor unit.
  7. Locate where the heat exchanger will not inhale dust or paper scraps.
  8. Install as far as possible from areas with reverse wind (wind blowing directly against the fan). If installed on a roof or open space with strong winds blowing directly against the unit, ensure strong winds do not blow directly against the air outlet grille.
  9. Do not install inside the house.
  10. Do not place flammable objects near the unit to prevent fires.
  11. Avoid installing where there is a high level of oil mist, salty air, or harmful gases like sulphur.
  12. Do not install where electromagnetic waves are directly radiated to the electrical box.
  13. Install the outdoor unit at least 3 meters away from electromagnetic wave radiators.

Strong Wind Blowing Directly Against the Product Installation Method

For installations on roofs or open spaces prone to strong winds, follow these instructions:

Please note that strong winds blowing directly against the air outlet grille can prevent necessary airflow and lead to unit failure.

Diagram showing strong wind direction impacting the air outlet. It illustrates two options: (1) Option the wind break cover plate, and (2) Use a wall shelter to direct the air outlet away from the wind. The diagram also indicates that service space of more than 600mm is required.

Wind Break Cover Plate Type:

Type Q'ty
WSP-335A 2

In open spaces, use steel wire cables or other means to secure the unit against strong winds.

4.2 Installation Space

Ensure adequate maintenance space around the outdoor unit as shown below.

1) Obstruction in the Air Inlet Side

(a) When the above is open

Diagrams showing installation space requirements for a separate installation and a row installation (two or more units) when there is an obstruction above. Dimensions are provided in millimeters (mm) for front side clearance, side clearance, and space above the unit. Notes indicate the need for wind break cover plates and ensuring sides are open.

(b) When obstruction is at the top

Diagrams showing installation space requirements for a separate installation and a row installation (two or more units) when there is an obstruction at the top. Dimensions are provided in millimeters (mm) for clearance below the unit, front side, and space above. Notes indicate the need for wind break cover plates and ensuring sides are open.

2) Obstruction in the Air Outlet Side

(a) When the above is open

Diagrams showing installation space requirements for a separate installation and a row installation (two or more units) when there is an obstruction above and the air outlet is considered. Dimensions are provided in millimeters (mm). Notes emphasize the need for wind break cover plates and opening at least one side.

3) Obstruction at Both Sides

(a) When the above is open

Diagrams illustrating installation space for a separate installation and a row installation (two or more units) with obstructions on both sides. Dimensions are provided in millimeters (mm). Notes highlight the requirement for wind break cover plates and ensuring both sides are open.

(b) When obstruction is at the top

Diagrams showing installation space for a separate installation with obstructions at the top. Dimensions are provided in millimeters (mm). A note explains how to set a metal framework if L > H to prevent air bypass.

4) Multiple Rows Side by Side Installation (Roof, etc.)

Diagram illustrating the spacing requirements for multiple outdoor units installed side-by-side. Dimensions (L, A, B) are provided in millimeters (mm). A note explains the use of a metal framework if L > H to prevent air bypass.

4.3 Foundation Work

1) Anchor Bolts Installation

Diagrams showing anchor bolt installation methods, including examples of lock methods and fixed installations. It illustrates the use of anchor bolts (M12) with nuts and washers on concrete foundations. A note mentions cutting off part 'A' if necessary for pipe cover difficulty.

If the 170mm dimension is ensured and there is no interference with the foundation base, piping work can be directed downwards.

2) Vibration and Inclination Prevention

To prevent the unit from dumping, excessive noise, or tilting due to gusts and earthquakes, ensure the foundation work is robust. Use fixed brackets and consider installing anti-vibration rubber if necessary to isolate vibration transmission to buildings.

3) Confirm Drainage Smooth Flow

During defrost operation, condensation water is discharged. Select the best drainage area and ensure water flows to a drainage ditch. The drain hole position is shown with dimensions.

Diagram showing the outdoor unit with an air inlet and a drain hole (Φ20) with dimensions (629mm). It indicates the direction of water discharge.

4) Shelf Installation

When using standard parts shelves that are narrower than the outdoor unit base bracket, follow the figure below. Use a wider flat base to support the full weight of the outdoor unit between the standard parts shelf and the outdoor unit base bracket feet.

Diagrams illustrating shelf settings. One shows the outdoor unit base bracket cannot fully load the unit weight, while another shows it can fully load the unit weight. It specifies the outdoor unit base bracket width (100mm) and recommends a flat size (SPHC) with a thickness of 4.5mm. Shelf width options (60mm standard parts, 100mm flat width) are shown with dimensions.

5. Refrigerant Piping Work

5.1 Refrigerant Pipe

1) Refrigerant Pipe Selection

Cautions for Refrigerant Piping Work (Example)

Diagrams illustrating cautions for piping work. One shows a hole in a wall with a pipe, cautioning to secure a cap or attach tape to the pipe end. Another shows a pipe not to be placed directly on the ground. A third shows rainwater potentially entering a pipe and suggests using a rubber band. Another diagram shows attaching a cap or vinyl tape to a pipe end.

2) Piping Direction

The pipe can be connected in four directions.

Diagram showing the outdoor unit with knock-out holes for piping connections from the front, rear, right, and bottom. It indicates liquid and gas piping connections and provides dimensions.
Size ΦA ΦB
RAM-280FSPH(D) 12.7 28.6
RAM-335FSPH(D) 12.7 28.6

(Unit: mm)

Pipe Combination (Accessory Parts):

Diagrams showing accessory parts for pipe combination, including a connecting pipe set (flare nut) for gas side piping, and a connecting pipe set (welding) for gas pipe size. It also shows the front and rear piping covers.

3) Refrigerant Piping Fixation Methods

Connect the indoor and outdoor units with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points to prevent it from touching weak parts of the building (e.g., walls, ceilings). Touching can cause abnormal sound due to vibration. Pay special attention for short piping lengths.

Diagram illustrating an example of refrigerant piping fixation. It shows the outdoor unit and indoor unit connected by piping, with suspension points indicated at intervals (1m, 1m, 1~1.5m). A table provides piping fixation intervals based on pipe size (20Less, 25~40).

4) Refrigerant Piping Limitation and Multi-Kit Pipe

Longer pipes can reduce air conditioner cooling and heating capacity. This factor must be considered when selecting piping specifications.

Diagram showing a piping connection example for a system with one outdoor unit and four indoor units (NO.0 to NO.3). It illustrates liquid and gas line piping requirements.
Maximum Piping Length Actual Length L1+L2+l3 : 150m Below
Equivalent Length L1+L2+l3 : 190m Below
The Total Length L1+L2+l0+l1+l2+l3 : 300m Below
Maximum Lift between Outdoor Unit and Indoor Unit The outdoor unit is higher than that of indoor unit. H 1 : 50m Below
The outdoor unit is lower than that of indoor unit. H 1 : 40m Below
Between each indoor unit H2 : 15m Below
Maximum Piping Length Between Each Multi-Kit and Each Indoor Unit l0, l1, l2, l3 : 15m Below
Between Multi-kit "a" And the Farthest Indoor Unit l4 : 40m Below
Multi-kit And Connection Pipe Outdoor Unit Model Gas/Liquid Pipe Size (Φ mm) Multi-Kit Pipe Type
The First Multi-Kit Pipe (a) And L1 Connection Pipe RAM-280FSPH(D) 28.6 / 12.7 E-NP452S
RAM-335FPS(D) 28.6 / 12.7 E-NP452S
Others Multi-kit Pipe And Connection Pipe Indoor Unit Total Capacity (kW) Gas/Liquid Pipe Size (Φ mm) Multi-Kit Pipe Type
27≤ 28.6 / 12.7 E-NP452S
23~26.99 25.4 / 9.53 E-NP282S
15~22.99 22.2 / 9.53 E-N55HT ※1
'15 19.05 / 9.53 E-N55HT ※1

※1: E-N55HT (Header Branch), it can be used that each indoor unit distribution and connection.

Multi-kit pipes must follow requirements; remove unused pipes. Welding other pipes into the multi-kit pipe is necessary to avoid reducing cooling capacity.

Line Branch Pipe

Diagrams showing dimensions for Line Branch Pipes (E-NP282S, E-NP452S) for Gas Piping and Liquid Piping.

Header Branch Pipe

Diagrams showing dimensions for Header Branch Pipes (E-N55HT) for Gas Piping and Liquid Piping.

5) Setting of the Multi-Kit Pipe

For multi-kit pipes connected to indoor units, use optional multi-kit pipe set parts to prevent uneven refrigerant distribution and capacity reduction. Do not connect using standard connectors.

1) Line Branch (Use the line branch pipe), As shown below:

Setting Ways of Branch Pipe

Diagrams illustrating correct and incorrect ways to set up branch pipes for line branch systems. It shows 'Best installation situation' and 'Allowing installation situation' as correct, and 'X Wrong' for incorrect configurations.
Diagrams illustrating correct and incorrect ways to set up branch pipes for line branch systems, showing different configurations of outdoor and indoor units with first, second, and third branches.

The Line Branch Pipe Fixed Limits

Horizontal

Diagram showing horizontal pipe installation with a straight pipe above 0.5m.

Vertical

It is divided into two kinds: upward and downward.

Diagrams showing vertical branch pipe installations: Upward Branch and Downward Branch. Both indicate a straight pipe above 0.5m.
Diagram illustrating tilt angle limits (within 30°) for piping.

2) Header Branch (Use the header branch pipe), As shown below:

Diagrams comparing 'Correct Setting' and 'Wrong Setting' for header branch installations, showing main pipes and header branch pipes connecting to indoor units.

Note: The header branch pipe cannot be continuously installed.

The Header Branch Pipe Fixed Limits

The header branch pipe must be installed horizontally.

3) Mixing Setting of Line Branch and Header Branch, As shown below:

Diagrams showing correct and incorrect methods for mixing line branch and header branch piping configurations. It indicates maximum lengths and notes on connection order.

Note: 1. The line branch pipe cannot be connected after the header branch pipe. 2. The first branch pipe cannot use the header branch pipe.

5.2 Refrigerant Piping Work

  1. Confirm that the stop valves of the outdoor unit are closed.
  2. Connect the piping between the indoor and outdoor unit. When tightening piping joints, coat the inside and outside of the flare piping with refrigerant oil (field-supplied). Tighten using a double spanner according to the specified torque. After tightening, confirm gas leakage again. Blow nitrogen into the piping during brazing. Use the attached flange combination and washer.
  3. Connect the indoor and outdoor units with field-supplied refrigerant piping. Suspend the piping at certain points to prevent it from touching weak building parts (wall, ceiling, etc.). Touching may cause abnormal sound due to vibration.
  4. Perform the air-tight test. Connect a gauge manifold using charging hoses with a vacuum pump or nitrogen cylinder to the check joints of the liquid and gas line stop valves. Apply nitrogen gas pressure of 4.15MPaG. Do not open the stop valves.

Required Torque

Piping Size (mm) and Flare Nut Tightening Torque (N·m) Spindle Valve Torque (N·m)
Gas Liquid Gas Liquid
Φ6.35 (1/4") 20 20~25 Hexagonal Wrench
Φ9.53 (3/8") 40 Gas Liquid
Φ12.7 (1/2") 60 10mm 5mm
Φ15.88 (5/8") 80
Φ19.05 (3/4") 100
Diagrams showing the spindle valve of the gas check valve and the spindle valve of the liquid check valve.

(1) After connection piping and before the airtight test, remove the liquid and gas stop valve caps. Ensure the spindle valve is closed with the specified torque. Do not overtighten the flare nut, as it can cause spindle valve leakage.

Do Not Apply the Double Spanner Work Here. Refrigerant Leakage Shall Occur.

Diagram illustrating the stop valve, flare nut, and a warning against using a double spanner.

5.3 Vacuum

  1. Refer to the nameplate inside the service cover for stop valve operation details.
  2. Connect a manifold gauge to the check joints on both sides. Continue vacuum pumping until the pressure reaches -0.1MPa (-750mmHg) or lower for one to two hours.
  3. After vacuum pumping, close the manifold valve, stop the vacuum pump, and leave it for one hour. Check that the pressure in the manifold gauge does not increase.
  4. Use charging hoses (as check joints and flare nuts may not connect directly). After the work, tighten the flare nut with 16Nm of torque.
  5. Check for gas leakage at flare nut connections or brazed parts using a gas leakage tester or foaming agent. Use the recommended foam testing fluid. Do not use general household cleaners.

Vacuum Drying Determination Example

Three graphs showing Vacuum Degree (Torr) versus Vacuum Time (min). They illustrate vacuum drying determination examples under different conditions: outside air temperature, system with/without water, and after vacuum pump stop. One graph shows a rebound phenomenon.

Note: 1. A slight refrigerant leakage sound when removing the spindle valve cap of the stop valve is normal. 2. Use tools and measuring instruments specifically designed for new refrigerant (R410A). 3. If a vacuum degree of -0.1MPa (-750mmHg) is not achieved, leakage is considered to exist. Check for gas leakage again. If no leakage is found, operate the vacuum pump for one to two hours.

Implement vacuum drying determination to confirm the absence of water in the system. If moisture is present, extend vacuum time or install a drying filter. Failure to do so can lead to unit failure and difficulties in handling.

5.4 The Additional Refrigerant

The outdoor unit is pre-filled with refrigerant, but additional refrigerant may be needed based on pipe length. Calculate the filling amount using the following formula and table:

Calculation Formula:

W: Additional refrigerant of liquid pipe (kg) = W11 + W12 + W13

W Total =

Model The factory refrigerant charging weight (kg) Additional refrigerant (kg) Additional refrigerant upper limit (kg)
RAM-280FSPH(D) 6.5 13.5
RAM-335FSPH(D) 7.8

☍ Additional refrigerant W exceeds the amount of additional refrigerant filling upper limit, adjust the length of piping, such that W does not exceed the value of upper limit.

  1. Fully open the gas line stop valve and slightly open the liquid line stop valve.
  2. During cooling operation, connect the gauge manifold using charging hoses with a refrigerant charging cylinder to the check joint of the liquid line stop valve. (Refrigerant charging quantity tolerance is around ± 0.1kg.)
  3. Fully open the liquid line stop valve after completing refrigerant charge.
  4. Finally, lock the spindle valve cap of the liquid stop valve according to the following tightening torque.

The Cap Tightening Torque:

6) Air-Tight Test

Be sure to perform the air-tight test. Additional refrigerant that is too much or too little can result in compressor failure or other abnormal conditions. Charge refrigerant according to calculated values.

Liquid piping must be thermally insulated to prevent poor performance and condensation on low-pressure pipe surfaces.

Diagram illustrating the setup for refrigerant recovery and air-tight testing, including outdoor unit, indoor unit, manifold gauge, vacuum pump, refrigerant cylinder, nitrogen bottle, gas/liquid stop valves, and piping.

5.5 Caution of The Refrigerant Leakage

When installing air conditioners in rooms, refrigerant concentration must not exceed specified limits in case of leakage. R410A is non-flammable and non-toxic, but significant leakage filling a room can cause choking hazards. This is especially true for long-distance piping connections with large refrigerant amounts. Ensure indoor unit installation is in a room where refrigerant concentration can be kept below limits even in case of leakage.

Calculate limits refrigerant concentration by the following formula:

The total amount of refrigerant within the system (kg) / Installation the product of the room indoor volume (m³) ≤ limits refrigerant concentration

R410A (0.3kg / m³)

If the calculation result exceeds the limits, implement the following treatment methods:

  1. Set up refrigerant leakage detector alarms linked to mechanical ventilation devices. (Ventilation capacity should be more than 0.4 m³/min per ton of cooling capacity).
  2. Create effective ventilation mouths between adjacent rooms (e.g., openings without doors, or openings with more than 0.15% floor area on the upper and lower parts of the door) to keep leakage refrigerant concentration below the limit.

Example: Total amount of refrigerant within the system: 20kg

Diagrams illustrating different room sizes (Tiny, Small, Medium, The Room, Large) and indicating the placement of ventilation mouths and mechanical ventilation devices with refrigerant leakage detectors.

Note: 1) The amount of leakage refrigerant is 20kg for all room sizes. 2) The room must not exceed the limits refrigerant concentration of 0.42kg/m³.

Outdoor Unit Model Cooling Capacity R410A
RAM-280FSPH(D) 4.11 Ton
RAM-335FSPH(D) 4.11 Ton

New refrigerant R410A product notes: Since R410A is a non-azeotropic refrigerant, its composition changes upon leakage. It cannot be directly added; reprocessing is required.

5.6 Caution of Measure Pressure Data from The Check Joints

Measure pressure data from the check joints of the gas line stop valve (A) and the piping line (B). Adjust high and low pressure positions based on the operation state. Refer to the table for details.

Cooling
The check joints of gas line stop valve Ⓐ Low pressure
The check joints of piping line Ⓑ High pressure
The check joints of liquid line stop valve Ⓒ When vacuum, maintenance services use to charge the refrigerant specially.
Diagram showing the location of check joints A, B, and C on the outdoor unit.

5.7 Refrigerant Recovery Methods

When moving the unit, recover outdoor refrigerant following these steps:

  1. Close the gas line stop valve, liquid line stop valve, and manifold gauge.
  2. Turn on the power source.
  3. Set outdoor unit electrical board DSW1-1 to ON. Implement cooling operation, then close the liquid line stop valve to start refrigerant recovery.
  4. When the low-pressure (gas line stop valve) side reaches -0.01MPa (-100mmHg), take the following actions rapidly:
    1. Close the gas line stop valve.
    2. Set outdoor unit electrical board DSW1-1 to OFF (Unit stop).
  5. Turn off the power source.

Please do not let the low-pressure gauge measure pressure lower than -0.01MPa. Low pressure below -0.01MPa during refrigerant recovery can result in compressor failure.

6. Electrical Wiring

CAUTION: All field wiring and electrical components must comply with local codes.

6.1 Wiring Capacity

  1. The indoor and outdoor unit transmission cable is non-polar.
  2. For the earth leakage breaker, select a "high-speed type" (active time less than 0.1 sec.).
  3. Install over current breaker, manual switch, and earth leakage breaker (ELB) together.
  4. Outdoor unit power supply specification: 3230V / 380V 60Hz.
  5. Wiring capacity is detailed in the following table:
Item Model Power Supply (60Hz) Maximum Current (A) Number of Poles ELB (Earth Leakage Breaker) Power Switch Fuse Capacity (A) Power Supply Size (mm²) Earth Wire Size (mm²) Transmission Cable Size
Rating Sensitivity Current (mA) Rating Current (A) Switch Capacity (A) 1 Switch Capacity (A) 2
RAM-280FSPH 230V 37 3 100 60 60 50 14 5.5 2-Core Shielded Twist Pair Cable 0.75mm²
RAM-335FSPH Total Length 1000m Below
RAM-280FSPHD 380V 23 4 30 40 40 25 8 3.5
RAM-335FSPHD

Note: When selecting the earth leakage breaker specification, refer to the table above. For 380V power supply, use 3Φ4 wire.

Wiring example diagram showing connections between ELB, power switch, outdoor unit, indoor units, and power supply.

※ Piping thermal insulation material: Please use heat-resistant specification products that can withstand high-temperature gas piping.

6.2 Wiring Essential

Follow these essentials for power source cords and transmission cables:

  1. To prevent electric shock, turn off power supply completely before opening service covers for electrical wiring, maintenance, or other operations.
  2. Ensure indoor unit power supplies connect to the same outdoor unit. Install an inverter-corresponding type earth leakage breaker (ELB) and manual switch for each indoor unit.
  3. The transmission cable connection must be with the same refrigerant cycle system. If connected to a different system, abnormal operation may occur.
  4. Use 2-core shielded twist pair cable (0.75mm² or above) for transmission cables between indoor and outdoor units, and between indoor units (DC5V). Total length must be within 1000m.
  5. Use 2-core wire for transmission cable connections. Do not use more than 3-core wire.
  6. Check if the power supply voltage matches the rating voltage within ±10%. Higher or lower voltage can damage the unit.
  7. Check electrical wire capacity. Insufficient power source capacity can prevent system startup due to voltage drop.
  8. Ensure indoor and outdoor units are grounded to prevent electric shock and accidents. Use grounding resistance of 100Ω or less, performed by qualified personnel.
  9. Turn off power supply completely before opening service covers for electrical wiring, maintenance, or other operations.

Caution of Indoor and Outdoor Unit Connection Wiring Construction:

Keep the transmission cable and 220V power source cord more than 5-6cm apart. Do not use coaxial cable. Incorrect connection of transmission cable and power source cord can burn the outdoor unit's PCB.

10) Indoor and Outdoor Unit's Power Source Cord and Connection Wiring Methods:

Diagrams illustrating incorrect wiring scenarios and their countermeasures. Scenarios include insufficient power supply terminal capacity, transmission abnormality, and insufficient indoor unit wiring capacity.

11) Wiring Connection Port:

After wiring, seal to prevent water invasion into the metal conduit pipe. Ensure terminal plugs are attached with insulation tape or sleeve.

Diagram showing the wiring connection port, rear cover, and cord band operation. It includes cautions regarding metal conduit pipes and shielded wiring.

7. Dip Switch (DSW) Setting of Outdoor Unit

TURN OFF all power sources before setting. Switches will not function, and settings will be invalid if power is on.

1) Transmission Method Setting

For multiple outdoor units sharing the same transmission line, set the refrigerant cycle number and end terminal resistance.

Setting of Refrigerant Cycle Number:

Diagram showing dip switches DSW4 (Tens Digit) and DSW5 (Last Digit) for setting the refrigerant cycle number. An example Ref. Cycle NO.25 is shown.

Setting of End Terminal Resistance (DSW5):

The unit is factory set with pin 1 of DSW5 at the "ON" side. If there are 2 or more outdoor units in the same H-link, set pin 1 of DSW5 to "OFF" for the 2nd unit onwards. If only one outdoor unit is used, no setting is required.

2) Lift Difference Setting

Set the lift difference between the outdoor and indoor units using DIP switch (DSW6) on the outdoor unit PCB.

Diagram showing DIP switch DSW6 and its settings for 'Outdoor unit lower than indoor unit 20~30m' and 'Outdoor unit higher than indoor unit'. It also shows H1 and H2 dimensions.

3) Others Setting Switch

DSW1 Test Operation Setting:

Settings for Factory Setting, Cooling Operation, and Compressor Forced Stop.

Diagrams showing the positions of DIP switches for DSW1 (1-4) for different test operation modes.

DSW2 Auxiliary Function Setting:

Settings for High Efficiency Fan Motor, Function Setting, and External I/O Setting.

Diagrams showing DIP switches DSW2 (1-6) and their corresponding setting items and switch numbers.

DSW3 Capacity Setting:

Each model is set based on the table.

Diagrams showing DIP switches DSW3 (1-4) for capacity setting for models RAM-280FSPH(D) and RAM-335FSPH(D).

8. Test Run

Before Test Run

Before starting the test run, re-confirm the installation for any problems and check the following:

Test Run

After installation is complete, perform the test run according to the following procedure. Confirm there is no abnormal operation before handing over the system to the customer.

  1. Ensure the outdoor unit's gas stop valve and liquid stop valve are fully open.
  2. Test each indoor unit in turn to confirm the refrigerant cycle system and electrical wiring system are the same. (If multiple indoor units operate simultaneously, consistency may be difficult to confirm.)
  3. Follow the procedure below to test run and check for abnormalities:
  4. 3.1 Depress the "MODE" and "CHECK" switches together for more than 3 seconds. The "TEST RUN" indicator and the connected unit count will appear on the remote control switch.
  5. Cooling Operation Conditions: Room temperature DB 21°C, WB 15°C; Outside air temperature DB -5°C or more. (Air conditioner cannot operate below -5°C outside air temperature.)
  6. If operating multiple indoor units with the remote controller, confirm the displayed unit count. If no indication appears or the count is smaller than actual, abnormalities exist. Press "MODE" again to set the desired operation mode.
  7. 3.2 Depress the "RUN/STOP" switch. The "TEST RUN" operation will begin (with a 2-hour OFF-TIMER set). The test run will finish after 2 hours or when "RUN/STOP" is pressed again.
  8. 3.3 To end the test run, wait 2 hours or press the "RUN/STOP" switch again.
Number of The Unit 0 1 2 3 4 ... 10 11 ... 63
Timer Setting Display Left Two Digit 01 02 03 04 05 ... 11 12 ... 64
Ref. Cycle NO. 0 1 2 3 4 ... 10 11 ... 63
Timer Setting Display Right Two Digit 01 02 03 04 05 ... 11 12 ... 64

Note: After the product stops operation, the compressor continues to run for a period (about 10 minutes) to recover piping refrigerant to the outdoor unit. This is not a product failure or abnormality. During test running, if a protection device activates due to an abnormality, the controller's operation indicator will blink, displaying "Alarm" (abnormality), and the setting temperature display will show the alarm code.

Diagrams showing changes in setting temperature and setting timer display, including indicators for Abnormality, Occurred Setting Temperature, Abnormality Indoor Unit No., Unit Type, Abnormality Indoor Unit Refrigerant Cycle, Content of Abnormality (Alarm Code), and Total Number of Indoor Units.

Refer to page 22 for alarm codes and treatment. If unable to resolve, contact your contractor.

Alarm Code

Code Distinction Content of Abnormality Leading Cause
01 Indoor Unit Indoor Unit Activation of Protection Device (Float Switch) Activation of Float Switch (High water Level Drain Pan, Abnormality of Drainpipe, Float Switch or Drain Pan)
02 Outdoor Unit Outdoor Unit Activation of Protection Device Activation of High Pressure Switch (4.15MPa); Air Conditioner Outdoor Unit Fan Motor Lock.
03 Wiring Transmission Abnormality between Indoor and Outdoor Incorrect Wiring, Loose Terminals, Disconnect Wire, Blowout of Fuse, Outdoor Unit Power OFF.
04 Inverter Transmission Abnormality between Inverter PCB and Outdoor PCB Inverter PCB - Outdoor PCB Transmission Failure (Loose Connector, Wire Breaking, Blowout of Fuse), Abnormal fan motor controller transmitted, "04" the lower right will be "Signal flashing".
05 Wiring Abnormality Power Source Phases Incorrect Power Source Phases, Connection to Reversed Phases, Open-Phases.
06 Voltage Abnormality Inverter Voltage Outdoor Voltage Drop, Insufficient Power Capacity.
07 Refrigerant Cycle System Decrease in Discharge Gas Superheat Excessive Refrigerant Charge, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Opened Position (Disconnect Connector).
08 Increase in Discharge Gas Temperature Insufficient Refrigerant Charge, Pipe Clogging, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Closed Position (Disconnect Connector).
11 Indoor Unit Thermistor Abnormality Inlet Air Thermistor (Indoor) Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
12 Abnormality Outlet Air Thermistor (Indoor) Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
13 Abnormality Freeze Protection Thermistor (Indoor) Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
14 Abnormality Gas Piping Thermistor (Indoor) Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
19 Activation of Protection for Indoor Fan Motor Fan Motor Overheat, Locking.
21 Outdoor Unit Thermistor Abnormality High Pressure Thermistor (Outdoor) Thermistor Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
22 Abnormality Outdoor Air Thermistor
23 Abnormality Discharge Pipe Thermistor (Outdoor)
24 Abnormality Heat Exchanger Liquid Pipe Thermistor (Outdoor)
29 Abnormality Low Pressure Thermistor (Outdoor)
31 System Incorrect Capacity Setting of Outdoor and Indoor Unit Incorrect Capacity Code Setting of Combination; Excessive or Insufficient Indoor Unit Total Capacity Code (outside of 80~120%)
35 Incorrect Setting of Indoor Unit No. Duplication of Indoor Unit No. In Same Ref. Gr., or The Connection Unit Number Exceeds the Maximum Number of Combination.
38 Outdoor Unit Abnormality of Picking Up Circuit for Protection (Outdoor) Failure of Protection Detecting Device (Incorrect Wiring of Outdoor PCB)
43 Activation of Low Pressure Decrease Protection Device Defective Compressor (Failure of Compressor of Inverter, Loose Power Supply Connection)
44 Pressure Activation of Low Pressure Increase Protection Device Overload at Cooling, High Temperature at Expansion Valve Locking (Loose Connector)
45 Activation of High Pressure Increase Protection Device Overload Operation (Clogging, Short-Pass), Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing.
47 Activation of Low Pressure Decrease Protection Device (Vacuum Operation Protection) Insufficient Refrigerant, Pipe Clogging, Expansion Valve Locking at Open Position (Loose Connector).
48 Outdoor Unit Activation of Inverter Overcurrent Protection Device Overload Operation, Compressor Failure.
51 Inverter Abnormality Inverter Current Sensor Current Sensor Failure.
53 IPM Protection Activation Driver IC Error Signal Detection (Protection for Overcurrent, Low Voltage)
54 Activation of Inverter Fin Thermistor Protection Abnormality Fin Thermistor, Heat Exchanger Clogging, Fan Motor Failure.
55 Inverter Failure Inverter PCB Failure
57 Outdoor Unit Activation of Outdoor Fan Controller Protection Abnormality Fan Controller Protection (Overcurrent), Fin Overheat
EE Compressor Compressor Protection Alarm Compressor Occurred Three Times of Abnormality within 6 Hour.
b1 Wiring Incorrect Outdoor Unit Address Number or Unit Number Setting Over 64 Number Is Set for Address or Refrigerant Cycle.
b5 Number of Indoor Units Connected Error. Connection of Non-H-LINK-II Indoor Unit More Than 17 Units.

PS: Remote control operation indicator flashes once every 2 seconds. Symbol between indoor unit and remote control indicates transmission abnormality (connector loss, loose, incorrect wiring, disconnection).

4) Finally, deliver the guarantee, operation manual, and installation manual, etc. to the customer.

Danger: Before test running preparation, do not start running. Be sure to confirm electrical wiring, etc.

Test Run and Maintenance Record

MODEL: SERIAL. No. COMPRESSOR MFG. No. DATE:
CUSTOMER'S NAME AND ADDRESS:
1. Is the rotation direction of the indoor coil fan correct?
2. Is the rotation direction of the outdoor coil fan correct?
3. Are there any abnormal compressor sounds?
4. Has the unit been operated at least twenty (20) minutes?
5. Check Room Temperature
Inlet: No. 1 DB /WB °C, No. 2 DB /WB °C, No. 3 DB /WB °C, No. 4 DB /WB °C,
Outlet: DB /WB °C, DB /WB °C, DB /WB °C, DB /WB °C,
Inlet: No. 5 DB /WB °C, No. 6 DB /WB °C, No. 7 DB /WB °C, No. 8 DB /WB °C,
Outlet: DB /WB °C, DB /WB °C, DB /WB °C, DB /WB °C,
6. Check Outdoor Ambient Temperature
Inlet: DB °C, WB °C, Outlet: DB °C, WB °C
7. Check Refrigerant Temperature: Operating Mode (Cool)
Discharge Gas Temperature: Td= °C
Liquid Pipe Temperature: Te= °C
8. Check Pressure
Discharge Pressure: Pd= MPa
Suction Pressure: Ps= MPa
9. Check Voltage
Rated Voltage: V
Operating Voltage: L1-L2 V, L1-L3 V, L2-L3 V
Starting Voltage: V
10. Check Compressor Input Running Current
Input: kW
Running Current: A
11. Is the refrigerant charge adequate?
12. Do the operation control devices operate correctly?
13. Do the safety devices operate correctly?
14. Has the unit been checked for refrigerant leakage?
15. Is the unit clean inside and outside?
16. Are all cabinet panels fixed?
17. Are all cabinet panels free from rattles?
18. Is the filter clean?
19. Is the heat exchanger clean?
20. Are the stop valves open?
21. Does the drain water flow smoothly from the drain pipe?
Models: RAM-280FSPH D, RAM-335FSPH D, RAM-280FSPH Inverter Driven Multi-Split System Air Conditioner, Inverter Driven Multi-Split System Air Conditioner, Multi-Split System Air Conditioner, Air Conditioner

File Info : application/pdf, 24 Pages, 3.48MB

PDF preview unavailable. Download the PDF instead.

66MP1570-A1 Microsoft Word for Microsoft 365

Related Documents

Preview Hitachi Inverter-Driven Multi-Split System Operation Manual
Comprehensive operation manual for Hitachi Inverter-Driven Multi-Split Air Conditioning Systems, covering installation, operation, maintenance, and troubleshooting for models like 65MP2180-A1 and RAM-FPS(B/D).
Preview Hitachi Split Unit Inverter Air Conditioner Outdoor Unit Installation Manual
This manual provides detailed instructions for the installation of Hitachi Split Unit Inverter Air Conditioners, covering safety precautions, handling, installation procedures, piping, wiring, test runs, and error codes.
Preview Hitachi Inverter-Driven Multi-Split Air Conditioner Operation Manual
Official operation manual for Hitachi Inverter-Driven Multi-Split Air Conditioning Systems. Includes safety guidelines, operating instructions, maintenance procedures, troubleshooting tips, and error code explanations.
Preview Hitachi Air Conditioner Operation Manual
This operation manual provides detailed instructions for the safe and efficient use of Hitachi Inverter-Driven Multi-Split System Air Conditioners. It covers installation precautions, operating procedures, maintenance, troubleshooting, and safety guidelines.
Preview Hitachi Inverter-Driven Multi-Split System Air Conditioners Operation Manual
This operation manual provides detailed instructions for Hitachi Inverter-Driven Multi-Split System Air Conditioners, covering installation, operation, maintenance, troubleshooting, and safety precautions. It includes information on remote controls, unit types, operation ranges, and error indications.
Preview Hitachi air365 Max Series Outdoor Units: Installation & Maintenance Manual
Comprehensive installation and maintenance guide for Hitachi air365 Max Series inverter-driven outdoor air conditioning units, covering models RAS-080CNCCLI to RAS-300CNCCLI.
Preview Hitachi M400 Multi-Zone Mini-Split Systems: Efficient Cooling and Heating
Explore the Hitachi M400 Multi-Zone Mini-Split Systems, offering flexible, energy-efficient ductless cooling and heating solutions. Features include a human sensor system, airCloud Home app control, and multiple indoor unit options for up to five zones.
Preview Hitachi Inverter-Driven Split System Heat Pump Air Conditioners Technical Catalog
Comprehensive technical catalog for Hitachi Inverter-Driven Split System Heat Pump Air Conditioners, DC Inverter UTOPIA series, detailing specifications, safety, and model information for RAS-4HVNC1, RAS-5HVNC1, and RAS-6HVNC1.