Hitachi Split Unit Inverter Air Conditioner

Outdoor Unit Installation Manual

Introduction

This manual provides essential information for the correct installation of the Hitachi Split Unit Inverter Air Conditioner Outdoor Unit. Please read this manual carefully before installation and keep it for future reference. The unit contains refrigerant, and the quantity is adequate for pipes up to 30m. For longer pipes, additional refrigerant may be required. Refer to the piping instructions for specific details.

Important Note: Hand over this manual to workers involved in transportation, handling, piping work, electrical wiring, test run, and finally to the customer.

This product is a general air-conditioner and should not be used for special purposes such as food, animal, plant, or precision machinery storage.

Locations to Avoid for Installation:

Temperature Ranges of Use:

Function Condition Indoor Unit Air Temperature Outdoor Unit Air Temperature
Air-conditioning -5°C DB to 43°C DB 21°C DB/15°C WB to 32°C DB /23°C WB

DB: Dry-bulb temperature/WB: Wet-bulb temperature

Safety Precautions

Warning: Failure to follow these instructions may cause severe injury.

Precautions for Electrical Works:

Handling

Carry the outdoor unit in its original packing to the installation location whenever possible.

Before Installation:

Tools and Gauges:

Refer to the table for interchangeability with R22 and R407C, and specific tools required for R410A.

Pipe Specifications:

Outdoor Unit Accessories

Verify the following accessories before installation:

Verification of Combined Capacity

Select the quantity and capacity of indoor units for the outdoor unit as shown in the table:

Outdoor Unit Combined Capacity Maximum Number of Indoor Units
RAM-112FPSQB 100-110% 2
RAM-125FPSQB
RAM-140FPSQB
RAM-160FPSQB

Attention:

The unit will not operate for the first four hours after power connection (error code "d1-22"). To bypass this protection, connect power to both units, wait 30 seconds, and then press PSW1 and PSW3 switches on the outdoor unit's mainboard simultaneously for three seconds.

Outdoor Unit Installation

Cautions:

Installation Space:

Maintain adequate space around the outdoor unit for maintenance. Refer to the diagrams for specific clearances for standalone and multiple unit installations.

Installation Locations:

Installation in Places with Strong Winds:

Attention: Strong winds blowing towards the air outlet can cause the fan to rotate in reverse and become damaged.

Installation

Securing the Unit:

Example of Fixing Stand with Anchor Bolts:

Illustrates the process of fixing the stand with anchor bolts, noting the need to cut off section A for easier pipe cover removal.

Recommended Board Size:

SPHC material, 4.5mm thickness. Dimensions provided.

Maintaining Space for Piping:

Ensure adequate space for piping connections.

Frame Leg Width vs. Outdoor Unit Leg Width:

Diagrams show clearances and the need for support boards if the frame legs are narrower.

Piping

3-1 Refrigerant Pipe Installation:

Requirements for pipe diameter, length, and lapse height between indoor and outdoor units are detailed.

Cautions:

Refrigerant Pipe Size:

Details pipe sizes for indoor and outdoor units for gas and liquid sides.

Precautions for Installing Refrigerant Pipes:

Fixing Branch Pipes:

Diagrams illustrate correct and incorrect methods for fixing branch pipes.

Precautions for Releasing Pressure from Pipe Union:

Release pressure from the fluid interceptor valve and gas interceptor valve as instructed.

Pipe Removal Direction

Pipes can be installed in four locations. Remove the appropriate cover and install the pipe through the hole. Break covers with a screwdriver or hammer as needed.

Guidelines for Opening Panel Cover:

Instructions for removing the panel cover, including pressing and sliding.

Pipe Connection and Insulation

Interceptor Valve on Outdoor/Indoor Unit:

Illustrates the location and operation of interceptor valves. Torque specifications for locking are provided.

Air-tightness Test:

Evacuation and Refrigerant Filling

Evacuation:

Refrigeration Filling:

Note: Removing the interceptor valve spool cap may cause gas to pop from the O-ring, which is not a gas leak.

Caution: Do not purge air with refrigerant, as this can lead to refrigerant insufficiency and compressor damage.

Insulation Sheet Wrapping: Wrap pipes and pipe unions with insulation sheets and plastic tape to prevent performance deterioration and condensation.

Pipe Length DIP Switch (DSW) Settings

Adjust DSW2 settings as shown for refrigerant pipe lengths under 5m or over 30m.

Refrigerant Filling Level

Refrigerant Filling Level and Standard Pipe Length:

Table shows filling levels and standard pipe lengths for different models. Tolerance is ±0.1kg.

Calculation of Additional Refrigerant Filling:

Calculate the required quantity of refrigerant for pipe lengths over 30m using the formula: W = (L - l) x P, where L is the total pipe length, l is the standard pipe length, and P is the compensation value (60g/m).

Recovering Refrigerant:

Follow the steps to recover refrigerant from the outdoor unit before relocation:

  1. Connect the manifold gauge set to the gas and liquid interceptor valves.
  2. Turn on the A/C power.
  3. Set DSW1-1 to ON (unit operation starts) and close the liquid interceptor valve. Start refrigerant recovery.
  4. When the low pressure reaches -0.01MPaG (-75mmHg), close the gas interceptor valve, set DSW1-1 to OFF (unit operation stops), and shut down the power.

Caution: Ensure pressure does not drop below -0.01MPaG to prevent compressor damage.

Wiring

Electrical Work:

All electrical work must be performed by a qualified electrician according to national regulations.

Wiring Methods:

Wiring diagrams are provided for both methods.

Precautions:

Precautions for H-LINK System Connection:

Wiring Connection Port

Follow indoor unit installation manual instructions for the indoor unit wiring connection port.

Precautions for Wiring:

Wiring Indoor and Outdoor Units:

Test Run and Handover

5-1 Test Run:

Perform test runs after completing indoor unit installation.

Precautions for Test Running:

About Insulation Impedance:

Low insulation impedance can cause the ELCB to trip. Check compressor insulation impedance and other electrical parts. If impedance is low, remove compressor cables, aliment the oil heater for three hours, and re-measure.

Test Run Procedure:

  1. Press the Run/Stop and CHECK buttons on the remote control simultaneously for 3 seconds to initiate test run.
  2. The LCD display will show "Test Run" and the number of connected indoor units. Check for proper wiring if the unit count is incorrect. Press Run/Stop to start operation.
  3. The unit will operate for 2 hours automatically. The protective device remains active.
  4. Press the LOUVER button to check deflector response on indoor units with auto-swing.
  5. Test Run ends automatically after 2 hours or when Run/Stop is pressed again. An abnormality will be indicated by a blinking operation light and an error code on the remote control display.

Note: If the operation light blinks every 2 seconds, there is a signal transfer error between the indoor unit and remote control.

Note: Giggling sounds from the outdoor unit after power connection or compressor start/stop are normal.

Test Run Checklist

A checklist is provided to verify all aspects of the test run, including fan direction, temperatures, pressures, refrigerant filling level, remote control functions, protective devices, leakage, cleanliness, and valve status.

5-2 Menu Setup

Perform menu setup after the outdoor unit stops. Do not run setup during operation or in check mode.

Menu Setup:

Press the CHECK button to show function selection codes. Run setup according to instructions, using PSW2 and PSW3 as indicated.

External I/O Setup:

Perform external I/O setup after the outdoor unit stops. Follow similar procedures as menu setup.

Note 1: Record the code for each function set during External I/O setup.

Note 2: Settings for each input terminal should be different. Values exceeding the default are invalid.

Connection examples for input and output are provided, along with factory settings and optional components.

6. Error Code Table

This section lists error codes, their causes, and troubleshooting steps. Critical errors (e.g., "EE") indicate potential compressor failure.

Note: Blinking operation light every 2 seconds indicates a signal transfer error.

Note: Check outlet temperature difference between units if it exceeds 10°C for cooling, indicating a potential refrigerant piping problem.

Warning: Do not operate the unit before test run is completed. Check electrical wiring carefully.

Models: RAM-112FPSQB, RAM-125FPSQB, RAM-140FPSQB, RAM-160FPSQB, RAM-112FPSQB Split Unit Inverter Air Conditioner Outdoor Unit, Split Unit Inverter Air Conditioner Outdoor Unit, Inverter Air Conditioner Outdoor Unit, Air Conditioner Outdoor Unit, Outdoor Unit

File Info : application/pdf, 20 Pages, 3.84MB

PDF preview unavailable. Download the PDF instead.

66MP1388 00 3-Heights™ PDF Toolbox API 6.12.0.6 (http://www -tools.com)

Related Documents

Preview Hitachi M400 Multi-Zone Mini-Split Systems: Efficient Cooling and Heating
Explore the Hitachi M400 Multi-Zone Mini-Split Systems, offering flexible, energy-efficient ductless cooling and heating solutions. Features include a human sensor system, airCloud Home app control, and multiple indoor unit options for up to five zones.
Preview Hitachi airHome MultiPro RAM-G55N2HBE Split Unit Air Conditioner Installation Manual
Detailed installation manual for the Hitachi airHome MultiPro RAM-G55N2HBE split unit air conditioner, covering safety precautions, tools required, pipe installation, electrical wiring, and operational testing for service personnel.
Preview Hitachi Split Unit Air Conditioner RAM-40NE2F Installation Manual
Detailed installation manual for the Hitachi Split Unit Air Conditioner, model RAM-40NE2F, covering safety precautions, site selection, piping, electrical connections, and testing procedures for service personnel.
Preview Hitachi airHome Multi Split Unit Air Conditioner Service Manual RAM-G18N2HAA
This service manual provides technical information for the Hitachi airHome Multi Split Unit Air Conditioner, model RAM-G18N2HAA. It covers specifications, installation, diagrams, troubleshooting, and parts lists for service personnel.
Preview Hitachi Air Home RAM-G18N2HAA Split Type Air Conditioner Installation Manual
This installation manual provides detailed instructions for the Hitachi Air Home RAM-G18N2HAA split-type air conditioner. It covers essential tools, critical safety precautions, site selection, piping, electrical wiring, and operational testing for professional installers. Ensure safe and efficient setup of your Hitachi HVAC system.
Preview Hitachi MultiZone Reverse Cycle Air Conditioning Systems
Explore Hitachi's MultiZone Reverse Cycle Air Conditioning Systems, offering flexible, efficient, and personalized climate control for homes and offices. Discover features like individual room control, wide ambient operating range, and various indoor unit options.
Preview Hitachi airCloud Home Application Adapter Service Manual
This service manual provides comprehensive instructions for the Hitachi airCloud Home Application Adapter, a system for managing air conditioners. It covers product overview, installation, application download and registration, account login, and troubleshooting.
Preview Hitachi Split Unit Air Conditioner Installation Manual (RAK-VJ50/60/70PHAT)
Comprehensive installation guide for Hitachi RAK-VJ50PHAT, RAK-VJ60PHAT, and RAK-VJ70PHAT split unit air conditioners, covering safety precautions, tools, and step-by-step installation procedures for indoor units.