TOSHIBA

TOSVERT VF-PS1 series LONWORKS® Communication option LIU006Z

Instruction Manual

NOTICE

  1. Make sure that this instruction manual is delivered to the end user of LONWORKS communication option.
  2. Read this manual before installing or operating the LONWORKS communication option. Keep it in a safe place for reference.
  3. All information contained in this manual are subject to change without notice. Please confirm the latest information on TOSVERT series web site "www.inverter.co.jp".

Safety Precautions

On the inverter and in its instruction manual, important information is contained for preventing injuries to users, damages to assets, and for proper use of the device. Read the instruction manual attached to the inverter along with this instruction manual to completely understand the safety precautions, the symbols and indications shown below. Please adhere to the contents of these manuals at all times.

Explanation of markings

Marking Meaning of marking
Danger Indicates that errors in operation may lead to death or serious injury.
Warning Indicates that errors in operation may lead to injury (*1) to people or that these errors may cause damage to physical property. (*2)

(*1) Such things as injury, burns or shock that will not require hospitalization or long periods of outpatient treatment.

(*2) Physical property damage refers to wide-ranging damage to assets and materials.

Meanings of symbols

Marking Meaning of marking
? [Prohibited] Indicates prohibition (Do not do it). What is prohibited will be described in or near the symbol in either text or picture form.
ℹ️ [Mandatory] Indicates something mandatory (must be done). What is mandatory will be described in or near the symbol in either text or picture form.
⚠️ [Danger] Indicates danger. What is dangerous will be described in or near the symbol in either text or picture form.
[Warning] Indicates warning. What the warning should be applied to will be described in or near the symbol in either text or picture form.

Safety Precaution

Limitation of use

Never use this unit with any device other than TOSVERT VF-PS1 series inverters. Doing so may cause an accident.

Handling in general

Danger

Warning

Transportation and installation

Danger

Wiring

Warning

Danger

Warning

Disposal

Warning

Notes on operation

Notes

Preface

Thank you for purchasing the "LONWORKS communication option (LIU006Z)" for TOSVERT VF-PS1 inverter. By Installing this unit into the VF-PS1, data communication can be made with a host computer or other device via LONWORKS network.

Before using this unit, carefully read this instruction manual in order to completely and correctly utilize excellent performance of this unit. Besides this instruction manual, the "VF-PS1 LONWORKS Communication Function Manual" which includes the contents to install into LONWORKS network is prepared. If it is required, please contact with our branch offices, sales offices or web site "www.inverter.co.jp".

("VF-PS1 LONWORKS Communication Function Manual": E6581373)

After reading this instruction manual, please keep it handy for future reference.

* Echelon®, LONWORKS®, LONMARK®, LonTalk®, Neuron®, are the registered trademarks or the trademarks of Echelon Corporation in the USA and other countries.

* LONMARK and LONMARK Logo are managed, granted, and used by LONMARK International under a license granted by Echelon Corporation.

Part numbering

Part numbering diagram description: The part number is structured as LIU-006-Z-0. 'LIU' represents the Symbol of LONWORKS option. '006' is the Model number of LONWORKS option. 'Z' indicates cable length (meaning 'without cable'). '0' is the Revision number.

Accessory check list

LONWORKS communication option is shipped together with the following accessories. On opening the packing case, check to see if the following accessories are contained or not.

  1. Instruction manual: English (E6581369) - 1 copy (This book)
  2. Neuron ID label - 2 sheets (Attached on the unit, Barcode type is CODE39)
  3. LED label - 1 sheet

Overview

LONWORKS technology is a network control system concept developed by Echelon Corporation. LONWORKS network provides Local Operating Network that is superior in the distributed control. Each device works in a peer-to-peer fashion on LONWORKS network. This LONWORKS option is equipped with the LONWORKS Smart Transceiver (Neuron Chip).

Names and functions

The drawing below shows names and functions of main parts: Service LED, Status LED, Fault LED, and LONWORKS network detachable terminal (NETA, SHIELD, NETB).

Description of terminals

Control terminals specification

Name Function Electrical specification Internal circuits
NETA (A) LONWORKS transmission data / reception data No polarity [Diagram description: Shows NETA, NETB, SHIELD connections with a component labeled FT-X1 and a 10MΩ resistor connected to SHIELD.]
NETB (B)
SHIELD (S) LONWORKS communication shield terminal. This terminal is grounded through 10Mohm resistor.

Service pin

Service pin function causes the node to propagate the service message over the network so that the network controller finds the node. This option unit has the software service pin function that operates the procedure shown below:

  1. Set the inverter parameter F830 to 1.
  2. Set the inverter parameter F830 to 0.

Just after the parameter is set to "0", LONWORKS option unit propagates the service message over the network.

Service LED

Service LED indicates the node condition.

LED status graph description: A graph shows time (0-5 seconds) against LED state (ON/OFF). Different lines represent conditions: 1 (Continues to be OFF), 2 (Continues to be ON), 3 (Momentarily OFF then continues to be ON), 4 (Repeats ON and OFF), 5 (Repeats ON and OFF), 6 (Continues to be OFF).

Problem & Solutions

No Phenomenon Problem & Solutions
1 Although the inverter is turned on, LED remains OFF. Check the connection between the inverter and the LONWORKS option unit. If abnormality is not found after checking, it needs to be repaired.
2 LED continues to be ON after the inverter is turned on. Internal application program is abnormal. If the same indication appears after resetting the power, it needs to be repaired.
3 LED is ON then OFF when the inverter is turned on, and it continues to be ON. This is a normal action of the "Unconfigured" device. If the device is not "Unconfigured", Internal application program is broken. It needs to be repaired.
4 LED flashes every 0.5 second. When the node is in "Configured" status, LED momentarily turns ON when the inverter is turned on. Then the LED continues to be OFF for some seconds. The node indicates "Configured" status that means the normal condition.
5 LED flashes every 1 second. CPU is abnormal. It needs to be repaired.
6 Flicker of LED (Approximately 10Hz to 30Hz) This is normal action while activating service pin.
LED turns ON while activating service pin.

Status LED

It displays node status with green color.

LED status graph description: A graph shows time (0-2 seconds) against LED state (ON/OFF). Different lines represent conditions: 1 (Continues to be OFF), 2 (Continues to be ON), 3 (Repeats ON and OFF), 4 (Repeats ON and OFF), 5 (Repeats ON and OFF), 6 (Repeats ON and OFF).

LED state description

No LED state Description
1 No power Although the inverter is turned on, LED remains OFF.
2 The LONWORKS option unit is running in normal mode.
3 LED flashes every 1 second. There is no connection to the LONWORKS network.
4 LED flashes every 0.25 second. The LONWORKS option unit has received a Wink command. It continues for 30 second.
5 Repeats 3 flashing and OFF for 1 second. These phenomenon occurs when the fault LED turning ON. CPU or Internal application program is abnormal. If the same indication appears after resetting the power, it needs to be repaired.
6 Repeats 2 flashing and OFF for 1 second.

Fault LED

It displays fault with red color.

LED state Description
OFF LONWORKS option unit has no fault.
ON Hardware or software fault of the LONWORKS option unit
Flashing The LONWORKS option unit does not communicate with the inverter. "E-23" or "E-24" error occurs. If the same indication appears after resetting the power, it needs to be repaired.

Installation and Setup

Installation method

Install the LONWORKS communication option to VF-PS1 as follows.

  1. Turn off input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit.
  2. Securing the option to the inverter
    • a) Insert a flat-blade screwdriver in each of the two holes at the upper part of the front panel, release the panel mounting tab by pushing the screwdriver down, and remove the front panel cover.
    • b) Fix the option into the inverter by fixing the tabs on the lower side of the option into the slots at the lower part of the inverter front panel. * Install this option into the front panel side when it is used together with the IO card option.
    • c) Make sure the option is securely attached to the inverter. Then, check whether the plastic bosses on the inverter case have fixed in the holes at the upper and lower parts of the option.
    • d) Insert the tabs at the lower part of the front cover into the slots at the lower part of the inverter to attach the front cover to the inverter.
    • e) Stick the enclosed "LED name label" on the option LED indicator part of a front cover.

Installation diagrams description: Illustrations a, b, c, d, and e show the step-by-step process of attaching the LONWORKS option to the VF-PS1 inverter, including removing the front panel, securing the option, and reattaching the cover.

VF-PS1 communication parameters

VF-PS1 parameters referring to below table are available.

Title Function Description
cmod Command mode selection While LONWORKS communication option is installed into VF-PS1 and configured to network, the network command and setpoint are prior to cmod/fmod. VF-PS1 LOCAL mode is prior to it.
fmod Setpoint mode selection
F830 Option parameter Service pin function (see section 2.2).
F851 Operation at network error Set the behavior when "Receive heart beat timer" overflow occurred (see function manual).
F899 Option reset Set 1 when resetting the option unit.

Network cable connection

Connect the LONWORKS network cable to LONWORKS communication option as follows.

Cable selection (a twisted pair cable with shield)

Use Level 4/22 AWG cable for the network cable.

Recommended cable: Manufacturer: SWCC SHOWA CABLE SYSTEMS CO.,LTD. Model name: LW221S, 22AWG, 1P, With shield, Standard 300m/reel

Use 0.75mm² wire for grounding to the earth terminal (G/E) of the board.

Terminal blocks

Terminal blocks diagram description: Shows a connector with three terminals labeled NETA, NETB, and SHIELD, with 'Catches' indicated. Manufacturer: PHOENIX CONTACT, Model name: MSTB 2,5/3-ST-5.08.

Communication terminal "NETA (A)", "NETB (B)": Connect LONWORKS transmission/reception data cable. Polarity of the communication terminals NETA and NETB does not have to be considered.

Shield terminal "SHIELD (S)": Connect the shield of network cable. Refer to next section for grounding.

Connection

Cable sheath should be peeled off by about 7mm.

For wiring work, use a flat blade screwdriver with a 0.6mm thick and 3.5mm width blade.

Tightening torque for the terminal block is 0.5Nm.

Network configuration

Make up the network as follows.

Transmission/reception signals (NETA, NETB)

Make up the communication path by connecting all transmission/reception data cables (No polarity).

Grounding the shield of cable (SHIELD)

Connect all shield lines of network cable. Ground through as a total resistance of network cable shield is about 470k ohm, so that static electricity does not increase (at the point where it separated from the power ground of inverters or motors).

Termination resistor (Please refer to "3.5. Termination resistor")

Only one terminal resistor is needed for the segment of the free topology. It can also be placed wherever it is on the free topology segments. (2 termination resistors in case of Bus topology)

Network cable length (for recommended cable usage)

Connection image

Connection image diagram: Illustrates how to connect a host computer/router to multiple LIU006Z units using twisted pair cable with shield. Shows NETA, NETB, and SHIELD connections, and a terminal resistor (52.3ohm, 1/8W).

Network configuration is shown in the figures below. This LONWORKS communication option has TP/FT-10 channel type transceiver. The free topology wiring supported by the TP/FT-10 channel type accommodates bus, star, loop, or several combinations of these topologies shown in below.

Network configuration example

Network configuration diagram: Shows a host computer connected to routers, which then connect to VF-PS1 units with LIU006Z options. Indicates a maximum of 63 nodes connected to a router.

Free topology: 63 units connected at maximum

Number of connected units to the router: 63 nodes at maximum

The free topology wiring example

Free topology wiring example diagram: Depicts nodes connected in a star or complex topology, with a termination resistor at one end. A legend indicates 'means a node'.

Complex topology can be configured.

N.B.: Do not connect the SHIELD terminal to the power ground of inverters or other units. Keep the network cables 20cm or more separate from the power cables to prevent from malfunctioning due to electromagnetic noise.

Termination resistor

Terminate the network bus with about 52.3ohm impedance to minimize the reflections. There are two choices for the termination.

1. Free Topology Network Segment

Only one termination and may be placed anywhere on the free topology segment. RC network (Following figure), with R1 = 52.3ohm +/-1%, 1/8W

2. Doubly Terminated Bus Topology Segment

It is necessary to terminate at both ends of a twisted pair bus. RC network (Following figure), with R1 = 105ohm +/-1%, 1/8W

Terminal circuit

Terminal circuit diagram: Shows an RC network with resistor R1 and capacitors C1, C2. R1 is specified as 52.3ohm or 105ohm depending on topology. C1 and C2 are required for connection to link power network. C1, C2: Aluminum-electrolytic type 100uF, 50V min.

Before making a service call

If a problem arises, please see the following trouble-shooting table. If the problem can not be solved, please contact your Toshiba distributor.

Phenomenon Problem and Solutions
Illegal LED indication Refer to "Service LED", "Status LED" and "Fault LED" written in section 2.3 to 2.5.
No replying from LONWORKS communication option Check proper termination resister is installed on the network. (See section 3.5.) Checking the LED indicator status.
Communication error in network variable Check the connection between the option and the inverter.

Specifications

Environmental specification

Item Specification Notes
Service environment Conforms to VF-PS1
Operation temperature Conforms to VF-PS1
Storage temperature -25 to +65°C
Relative humidity 20 to 93% (free from condensation and vapor)
Vibration 5.9m/s² (0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)

LONWORKS node specification

Item Specification Notes
Applicable model VF-PS1 series
Control supply 24VDC Supplied from VF-PS1
Transceiver TP/FT-10 type (Free Topology Transceiver) 78kbps
Channel type ANSI/EIA/CEA 709.3
Communication signal 2 wires and shield NETA, SHIELD, NETB
Transmission distance (Free topology) Between devices: 400m at maximum
Total cable length: 500m at maximum
When recommended cable is used: Level 4/22AWG
Transmission distance (Bus topology) Total cable length: 1400m at maximum
Stub length: 3m at maximum
When recommended cable is used: Level 4/22AWG
Number of connected nodes 64 nodes at maximum in a segment Because a host and routers are counted as one node, the option can be connected up to 63 nodes.
Protocol LonTalk ANSI/EIA 709.1
Address and related items Number of domains: 2
Number of address entries: 53
Number of alias tables: 8
Number of transmission data: 28
Number of receiving data: 13
Number of configuration property: 12
LONMARK Variable Speed Motor Drive (6010_11) functional profile.
Network variables
Service pin VF-PS1 parameter F 830 Used for notification of Neuron ID to the host.
Terminal block Detachable terminal block 3-pole Applicable terminal block
Manufacturer: PHOENIX CONTACT
Type-Form : MSTB 2,5/3-ST-5.08

Warranty

Any part of LONWORKS communication option that proves defective will be repaired free of charge under the following conditions:

  1. This warranty applies only to the LONWORKS communication option unit.
  2. Any part of the unit which fails or is damaged under normal use within 12 months from the date of delivery shall be repaired free of charge.
  3. For the following kinds of failure or damage, the repair cost shall be borne by the customer even within the warranty period.
    • i) Failure or damage caused by improper or incorrect use or handling, or unauthorized repair or modification of the unit.
    • ii) Failure or damage caused by the unit falling or an accident during transportation after the purchase.
    • iii) Failure or damage caused by fire, salty water or wind, corrosive gas, earthquake, storm or flood, lightning, abnormal voltage supply, or other natural disasters.
    • iv) Failure or damage due to the use of LONWORKS communication option for non-intended purposes.
  4. All expenses incurred by Toshiba for on-site services shall be charged to the customer, unless a service contract is signed beforehand between the customer and Toshiba, in which case the service contract has priority over this.
Models: VF-PS1 Series AC Inverter Drive, VF-PS1 Series, AC Inverter Drive, Inverter Drive, Drive

File Info : application/pdf, 15 Pages, 315.16KB

PDF preview unavailable. Download the PDF instead.

LonWorks Option Manual Acrobat Distiller 7.0.5 (Windows)

Related Documents

Preview TOSVERT VF-AS1/PS1 PROFIBUS-DP Option Instruction Manual (PDP002Z)
Instruction manual for the Toshiba TOSVERT VF-AS1/PS1 PROFIBUS-DP Option (PDP002Z). Covers installation, connection, parameters, operation, specifications, and warranty for integrating VF-AS1/PS1 inverters with PROFIBUS networks.
Preview TOSVERT VF-A7 High-Performance Inverter Instruction Manual
This instruction manual provides detailed information on the TOSVERT VF-A7 high-performance industrial inverter, covering safety precautions, installation, operation, wiring, and technical specifications for optimal use.
Preview Toshiba TOSVERT VF-PS1 Variable Torque Inverter Instruction Manual
Comprehensive instruction manual for the Toshiba TOSVERT VF-PS1 variable torque inverter, covering safety precautions, installation, connection, operation, parameter settings, maintenance, and troubleshooting for industrial applications.
Preview TOSHIBA TOSVERT VF-S15 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the TOSHIBA TOSVERT VF-S15 industrial inverter. Covers safety, installation, operation, parameter settings, and specifications for 3-phase induction motors.
Preview TOSVERT VF-AS3 Trace Tool PCT003Z-E Instruction Manual for Inverter Communication
This instruction manual provides comprehensive guidance for using the TOSVERT VF-AS3 Trace Tool PCT003Z-E software. Learn how to export/import parameters, read inverter information, display trace data graphically, and store trace data for TOSHIBA VF-AS3 inverters via RS-485 communication.
Preview TOSHIBA VF-S11 RS485 Built-in Board Option RS4003Z Instruction Manual
This instruction manual provides detailed information on the TOSHIBA VF-S11 RS485 built-in board option (RS4003Z). It covers installation, operation, communication specifications, wiring, and troubleshooting for enabling data communication with VF-S11 inverters via RS485.
Preview Toshiba TOSVERT VF-S11 Supplementary Instruction Manual
This supplementary manual provides additional explanations for items in the main instruction manual for the Toshiba TOSVERT VF-S11 Totally-Enclosed Box Type Inverter. It covers exterior features, wiring diagrams, installation environment, and specifications.
Preview Toshiba TOSVERT VF-S11 Industrial Inverter Instruction Manual
Comprehensive instruction manual for the Toshiba TOSVERT VF-S11 industrial inverter, covering safety precautions, installation, operation, basic and extended parameters, troubleshooting, and disposal. This guide is essential for users to safely and effectively operate the inverter with 3-phase induction motors.