FP4070 Series Quick Start Guide
Product Code: FP4070TN, FP4070TN-E
SPECIFICATIONS
Power(Base) | 24VDC (±20%), 220mA, 5.28W (TN-E module) |
Power (With 3 Expansions) | 24VDC (±20%), 370mA, 8.88W (TN-E module) |
Display | 7", 800 x 480, WVGA color TFT with resistive touch screen |
LEDs | 1 |
RAM Memory | 512MB |
User Application | Up to 1GB that includes user application, data log, alarms, retentive memory and logic memory |
eMMC | 4GB |
RTC | Built-in, Date and Time Function |
Expansions | It supports 3 Expansion slots* |
Weight | Approx. 400gm |
Product Dimensions | 186.0(W) x 138.0(H) x 35.3(D)mm |
Panel Cut-out | 175.00(W) x 127.00(H)mm |
Communication Interfaces | |
Serial Ports | 2 x RS232/RS485 |
USB Ports | 1 USB Type C port and 1 USB Host port |
Ethernet | 1 Ethernet Port |
SD Card | Micro SD [High Capacity (4GB to 32GB)] Speed Class: @@@@ [While inserting and removing SD card, please make sure to TURNOFF the power to the unit.] |
Environment & Approvals | |
Operating Temperature | -10° to 60°C** |
Storage Temperature | -30° to 85°C |
Humidity | 10 to 90% (Non-Condensing) |
Shock | IEC 60068-2-27 25g, 11ms, 6 shocks per axis, total 18 shocks (X, Y, Z) |
Vibration | IEC 60068-2-6 5 to 150Hz, 3g peak (X, Y, Z) |
EMC | EN 55011: 2009/A1: 2010 EN 61131-2: 2007 EN 61000-6-2: 2005/AC: 2005 EN 61000-6-4:2007/A1: 2011 |
Protection | Front panel-IP66, Rear panel-IP20 |
APPROVALS | CE, UL(Class1 Div2), ULCA, REACH & ROHS [* Note: Applicable for FP4070Tx-E modules.] [** Note: For UL, operating temperature range is 0° to 50°C.] |
PRODUCT DIMENSIONS
Product Dimensions: 186.0(W) x 138.0(H) x 35.3(D)mm
Panel Cut-out Dimensions: 175.00(W) x 127.00(H)mm
Panel Thickness: Maximum 6mm and Mounting Clamps: 4
GETTING STARTED
User should follow the given sequence to configure and use any FlexiPanels series unit:
- Install FlexiSoft Software.
- Create a PZM application using FlexiSoft software.
- Connect programming cable.
- Download Firmware i.e. driver for the HMI.
- Download application.
- Now FP unit is ready to use in the system.
For More Information, Visit https://www.renuelectronics.com
COMMUNICATION INTERFACES
This section provides information regarding communication interfaces supported by this product.
COM1: FP4 series has one terminal block port (COM1) which support RS232 / RS485 signal levels.
4 Wire RS485 connections
Driver end (PLC side or 2 wire network side) | Pin number | FP Unit side (COM2) |
---|---|---|
Signal | Signal | |
TX+ | 1 | RX+ |
RX+ | 4 | TX+ |
GND | 5 | GND and Shield |
TX- | 8 | RX- |
RX- | 9 | TX- |
COM2: FP4 series has one DB9 female port (COM2) which support RS232 / RS485 signal levels.
Pin Number | Signal | Pin number | Signal |
---|---|---|---|
1 | RX- | 1 | TX+ |
2 | TX- | 2 | TXD |
3 | RX+ | 3 | RXD |
4 | TX+ | 4 | RX+ |
5 | GND | 5 | SG |
6 | RXD | 6 | NC |
7 | TXD | 7 | NC |
8 | 8 | TX- | |
9 | 9 | RX- |
[Note: FP4070 device can support only two serial ports]
Cable Diagrams:
PC to unit programming cable (RS232):
Driver end (PLC side or 2 wire network side) | Pin number | FP Unit side (COM2) |
---|---|---|
Signal | Signal | |
TXD | 2 | RXD |
RXD | 3 | TXD |
GND | 5 | GND |
2 Wire RS485 connections
Driver end (PLC side or 2 wire network side) | Signal | FP Unit side (COM2) | |
---|---|---|---|
A (TX+/RX+) | Pin number | Signal | |
B (TX-/RX-) | 1 | TX+ | |
GND | 4 | RX+ | |
5 | GND and Shield | ||
8 | TX- | ||
9 | RX- |
USB Host Port
- USB Host, compliant with USB 2.0 specification.
- USB Host can be used to transfer logged data and historical alarm to USB memory stick.
- USB Host can handle only USB memory stick devices and can source current up to 150mA only.
- Connector used: Standard USB Type A Female connector.
USB Type C Port
- USB Type C, compliant with USB 2.0 specification, self-powered device.
- Connector used: USB Type C Female connector.
Ethernet Port
- Fully compliant with IEEE 802.3 / 802.3u standards.
- 10/100 Mbps support.
- Connector used: Standard shielded RJ-45 female jack with in-built speed and link activity indication LEDs.
Pin number | Signal |
---|---|
1 | TX+ |
2 | TX- |
3 | RX+ |
4 | NC |
5 | NC |
6 | RX- |
7 | NC |
8 | NC |
Earthing
The optimum method for Earthing electronic equipment is to earth it separately from other high-power systems, to earth more than one unit of electronic equipment with a single-point earth. The Earthing marked terminal (see below) is provided on the unit.
[Note: Do not use an earth that has an unstable impedance, such as painted screws or earth subject to vibration.]
UL APPROVAL
CONTROL DRAWING NO# CNTL/DWG/FP4070/0118 | VER.NO.:1.00 |
---|---|
Hazardous Location | Non-Hazardous Location |
Class I Division 2 Groups A B C and D | FP4070Tx Series |
USB Port | USB Port |
JP8 | |
Vmax 3.3 VDC | Associated Apparatus |
Imax= 150 mA | USB Port |
L= 0 | Voc, Isc, La and Ca to be determined per Table 1 |
C₁ = 9 pF | Nonincendive. Equipment |
Associated Apparatus | |
V max (or Ui) | |
Voc or Vt (or Uo) | |
I max (or li) | |
Isc or It (or lo) | |
Ci + Ccable | |
Ca (or Co) | |
Li + Lcable | |
La (or Lo) |
TABLE 1:
Capacitance and inductance of the field wiring from the nonincendive equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown in Table 1. Where the cable capacitance and inductance per foot are not known, the following values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 µH/ft. Wiring method must be in accordance with ANSI/NFPA70
WARNING:
- This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non- hazardous locations only.
- WARNING - EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
- WARNING - EXPLOSION HAZARD - Substitution of components may impair suitability for Class I, Division 2.
- WARNING - CAUTION, Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose of in Fire.
- The list of materials used in the construction of these devices with name of sealed device - generic name of the material and the supplier's name and type designation.
- It is recommended that the user periodically inspect the sealed devices used, for any degradation of properties and Replace the device if any degradation is found.
REVISION HISTORY
Rev. | Description | Date |
---|---|---|
1.5 | Specification updated | 09/10/2025 |
1.4 | COM Port details updated | 30/01/2024 |
1.3 | Some Information Updated | 05/10/2023 |
1.2 | Logo Updated | 20/09/2022 |
1.1 | Replaced USB type from Micro to Type C | 21/07/2021 |
1.0 | First Draft | 24/03/2020 |