AutomationDirect Protos X Discrete Terminals

A comprehensive overview of AutomationDirect's Protos X series of discrete input, output, relay, and combination terminals, designed for industrial automation applications.

Discrete Input Terminals

PX-144: Four-point, 24VDC Discrete Input Terminal

$48.00

The PX-144 (Type 1) DC Input Terminal provides four electrically isolated 24VDC sinking inputs with LED status. Suitable for 3-wire and 2-wire sensors.

Diagram Description: A compact terminal block with four input channels labeled 1 through 4, each with an associated LED indicator. Connections for +24VDC and 0V are shown, along with input terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight55g (1.9 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs Per Terminal4
Input TypeSinking
Input Data Bytes Used1/2 byte (4 bits)
Input Power Source24VDC provided via terminal power bus
Current Consumption (from Terminal Power Bus)5mA typical
Operating Voltage Rating24VDC (-15%/+20%)
Peak Voltage Rating30VDC
ON Voltage Level15 to 30 VDC
OFF Voltage Level-3 to +5 VDC
Minimum ON Current50mA
Maximum OFF Current100mA
Current Consumption (from I/O Bus)5mA typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response3ms
ON to OFF Response3ms
Status Indicators4, indicates input is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-148: Eight-point, 24VDC Discrete Input Terminal

$78.00

The PX-148 (Type 1) DC Input Terminal provides eight electrically isolated 24VDC sinking inputs with LED status.

Diagram Description: A terminal block with eight input channels (1-8), each with an LED indicator. Shows connections for 24 VDC power supply and common, and input terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight55g (1.9 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs Per Terminal8
Input TypeSinking
Input Data Bytes Used1 byte
Input Power SourceRequires external 24VDC power source
Current Consumption (from Terminal Power Bus)2mA + load, typical
Operating Voltage Rating24VDC (-15%/+20%)
Peak Voltage Rating30VDC
ON Voltage Level15 to 30 VDC
OFF Voltage Level-3 to +5 VDC
Minimum ON Current2mA
Maximum OFF Current1.5 mA
Current Consumption (from I/O Bus)5mA typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response3ms
ON to OFF Response3ms
Status Indicators8, indicates input is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-149: Sixteen-point, 24VDC Discrete Input Terminal

$135.00

The PX-149 (Type 1) DC Input Terminal provides sixteen electrically isolated 24VDC sinking inputs with LED status.

Diagram Description: A terminal block with sixteen input channels (1-16), each with an LED indicator. Shows connections for 24 VDC power supply and common, and input terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs Per Terminal16
Input TypeSinking
Input Data Bytes Used2 bytes
Input Power SourceRequires external 24VDC power source
Current Consumption (from Terminal Power Bus)NA
Operating Voltage Rating24VDC (-15%/+20%)
Peak Voltage Rating30VDC
ON Voltage Level11 to 30 VDC
OFF Voltage Level-3 to +5 VDC
Minimum ON Current2mA
Maximum OFF Current40mA
Current Consumption (from I/O Bus)20mA typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response3ms
ON to OFF Response3ms
Status Indicators16, indicates input is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-172-1: Two-point, 120–230 VAC Discrete Input Terminal

$54.00

The PX-172-1 (Type 2) DC Input Terminal provides two electrically isolated 120–230 VAC inputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Diagram Description: A terminal block with two input channels (1-2), each with an LED indicator. Shows connections for 120-230 VAC/VDC, 0V, and PE.

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, AC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusYes ✔️
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs Per Terminal2
Input TypeNA
Input Data Bytes Used1/4 byte (2 bits)
Input Power SourceRequires external 120–230 VAC power source. PX-908 terminal recommended to provide power to the terminal power bus.
Current Consumption (from Terminal Power Bus)6mA typical
Operating Voltage Rating120 to 230 VAC
Peak Voltage Rating260VAC
ON Voltage Level79 to 260 VAC
OFF Voltage Level0 to 40 VAC
Minimum ON Current250mA
Maximum OFF Current500mA
Current Consumption (from I/O Bus)3mA typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response10ms
ON to OFF Response10ms
Status Indicators2, indicates input is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-172-2: Two-point, 120 VAC/VDC Discrete Input Terminal

$54.00

The PX-172-2 (Type 2) DC Input Terminal provides two electrically isolated 120 VAC/VDC inputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Diagram Description: A terminal block with two input channels (1-2), each with an LED indicator. Shows connections for 120 VAC/VDC, 0V, and PE.

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, 120 VAC/VDC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusYes ✔️
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs Per Terminal2
Input TypeNA
Input Data Bytes Used1/4 byte (2 bits)
Input Power SourceRequires external 120 VAC/VDC power source. PX-908 terminal recommended to provide power to the terminal power bus.
Current Consumption (from Terminal Power Bus)6mA typical
Operating Voltage Rating120 VAC/VDC
Peak Voltage Rating140 VAC/VDC
ON Voltage Level80 to 140 VAC/VDC
OFF Voltage Level0 to 40 VAC/VDC
Minimum ON Current250mA
Maximum OFF Current500mA
Current Consumption (from I/O Bus)3mA typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response10ms
ON to OFF Response10ms
Status Indicators2, indicates input is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Discrete Output Terminals

PX-244-1: Four-point, 0.5 A, 24VDC Discrete Output Terminal

$72.00

The PX-244-1 (Type 1) DC Output Terminal provides four 24VDC 0.5 A short-circuit protected sourcing outputs with LED status. For use with 3-wire and 2-wire devices.

Diagram Description: A terminal block with four output channels (1-4), each with an LED indicator. Shows connections for +24VDC, 0V, and output terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal4
Commons Per Terminal2
Output TypeSourcing
Output Data Bytes Used1/2 byte (4 bits)
Output Power Source24VDC provided via terminal power bus
Current Consumption (from Load Voltage)30mA typical
Operating Voltage24VDC (-15%/+20%)
Maximum Load Current0.5 A per channel (Short-Circuit Protected)
On Voltage Drop0.4 VDC @ 0.5 A
Maximum Leakage Current300mA
Maximum Inrush Current1.5 A
Maximum Short-Circuit Voltage35V
Load TypeResistive, inductive, lamp
Current Consumption (from I/O Bus)9mA typical
Reverse Voltage ProtectionNo ❌
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response100ms max
ON to OFF Response20ms max
Status Indicators4, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-244-2: Four-point, 2A, 24VDC Discrete Output Terminal

$88.00

The PX-244-2 (Type 1) DC Output Terminal provides four 24VDC 2A short-circuit protected sourcing outputs with LED status.

Diagram Description: A terminal block with four output channels (1-4), each with an LED indicator. Shows connections for +24VDC, 0V, and output terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal4
Commons Per Terminal4
Output TypeSourcing
Output Data Bytes Used1/2 byte (4 bits)
Output Power Source24VDC provided via terminal power bus
Current Consumption (from Load Voltage)30mA typical
Operating Voltage24VDC (-15%/+20%)
Maximum Load Current2A per channel (Short-Circuit Protected)
On Voltage Drop0.14 VDC @ 2A
Maximum Leakage Current60mA
Maximum Inrush Current35A
Maximum Short-Circuit Voltage52V
Load TypeResistive, inductive, lamp
Current Consumption (from I/O Bus)9mA typical
Reverse Voltage ProtectionYes ✔️
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response160ms typ, 300ms max
ON to OFF Response10ms min, 80ms max
Status Indicators4, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-248: Eight-point, 0.5 A, 24VDC Discrete Output Terminal

$91.00

The PX-248 (Type 1) DC Output Terminal provides eight 24VDC 0.5 A short-circuit protected sourcing outputs with LED status.

Diagram Description: A terminal block with eight output channels (1-8), each with an LED indicator. Shows connections for common, and output terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight70g (2.4 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal8
Commons Per TerminalField wired
Output TypeSourcing
Output Data Bytes Used1 byte
Output Power Source24VDC provided via terminal power bus
Current Consumption (from Load Voltage)60mA + load typical
Operating Voltage24VDC (-15%/+20%)
Maximum Load Current0.5 A per channel (Short-Circuit Protected)
On Voltage Drop0.4 VDC @ 0.5 A
Maximum Leakage Current300mA
Maximum Inrush Current1.5 A
Max. Short-Circuit Voltage35V
Load TypeResistive, inductive, lamp
Current Consumption (from I/O Bus)18mA typical
Reverse Voltage ProtectionYes ✔️
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response100ms max
ON to OFF Response20ms max
Status Indicators8, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-249: Sixteen-point, 0.5 A, 24VDC Discrete Output Terminal

$126.00

The PX-249 (Type 1) DC Output Terminal provides sixteen 24VDC 0.5 A short-circuit protected sinking outputs with LED status.

Diagram Description: A terminal block with sixteen output channels (1-16), each with an LED indicator. Shows connections for common, and output terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight70g (2.4 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal16
Commons Per TerminalField wired
Output TypeSinking
Output Data Bytes Used2 bytes
Output Power SourceRequires external 24VDC power source
Current Consumption (from Load Voltage)35mA + load typical
Operating Voltage24VDC (-15%/+20%)
Maximum Load Current0.5 A per channel (Short-Circuit Protected)
On Voltage Drop0.12 VDC @ 0.5 A
Maximum Leakage Current75mA
Maximum Inrush Current3.5 A
Max. Short-Circuit Voltage36V
Load TypeResistive, inductive, lamp
Current Consumption (from I/O Bus)45mA typical
Reverse Voltage ProtectionYes ✔️
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
OFF to ON Response0.45 ms
ON to OFF Response3.3 ms
Status Indicators16, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Discrete Relay Output Terminals

PX-272-1: Two-point, 0-230 VAC/VDC Discrete Solid State Relay Output Terminal

$97.00

The PX-272-1 (Type 2) Solid State Relay Output Terminal provides two 230 VAC/VDC 0.3 A outputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Diagram Description: A terminal block with two output channels (1-2), each with an LED indicator. Shows connections for 230 VAC/VDC, 0V, and PE.

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight55g (1.9 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, 230 VAC/VDC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusYes ✔️
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal2
Commons Per Terminal2
Output TypeSolid State Relay (DC sourcing only)
Output Data Bytes Used1/4 byte (2 bits)
Output Power Source230 VAC/VDC provided via terminal power bus
Current Consumption (from Terminal Power Bus)(ON resistance max 100mV) + load
Operating Voltage0 to 230 VAC/VDC (DC 100Hz)
Maximum Load Current0.3 A per point
Maximum Leakage Current< 1mA (off state)
Maximum Inrush Current0.5 A for 20s, 1.5 A for 100ms
Contact Resistance2.1 V, typical 3.2 V, max.
Surge Voltage ProtectionFrom 400VAC
Load TypeResistive, inductive
Current Consumption (from I/O Bus)10mA
Electrical Isolation500Vms (I/O bus/field potential) 2500VDC (1 min.)
Heat Dissipation1W max
Switch-ON Time4 to 6 ms
Switch-OFF Time0.05 to 0.1 ms
Switch-ON Delay320ms
Switch-OFF Delay6.2 ms
Status Indicators2, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

PX-272-2: Two-point, 230VAC / 30VDC Discrete Relay Output Terminal

$76.00

The PX-272-2 (Type 2) Relay Output Terminal provides two 230VAC / 30VDC 5A outputs with LED status. For use with 4-wire, 3-wire and 2-wire devices.

Diagram Description: A terminal block with two output channels (1-2), each with an LED indicator. Shows connections for 230VAC or 30VDC, 0V, and PE.

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight85g (3.0 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, 230VAC or 30VDC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusYes ✔️
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Outputs Per Terminal2
Commons Per Terminal2
Output TypeSPST Relay, normally open contact (DC sourcing only)
Output Data Bytes Used1/4 byte (2 bits)
Output Power Source230VAC/30VDC provided via terminal power bus
Current Consumption (from Terminal Power Bus)(ON resistance typ 2.4 V, max 3.2 V) + load
Operating Voltage230VAC/30VDC
Maximum Load Current5A per point
Maximum Load Current with Resistive LoadAC: 5A @230VAC, 1250VA DC: 5A @ 30VDC, 150W
Maximum Load Current with Inductive Load, cosφ = 0.4, L/R = 7msAC: 2A @230VAC DC: 2A @ 30VDC
Minimum Load (approximate)10mA @ 5VDC (as supplied) 100mA @ 20VDC (after approx. ≥ 100mA has been switched at least once)
Load TypeResistive, inductive, lamp
Switching TimesReaction Time: 10ms max. Release Time; 4ms max. Bounce Time: 5ms max.
Contact MaterialSilver Cadmium Oxide
Current Consumption (from I/O Bus)80mA
Electrical Isolation500Vms (I/O bus/field potential) 2500VDC (1 min.)
Heat Dissipation1W max
Switching Frequency at Maximum Contact Load10/minute
Maximum Contact Resistance< 30mV
Minimum Insulation Resistance100MΩ @ 500VDC
Mechanical Operating Life20,000,000 switching operations
Electrical Operating LifeMinimum 100,000 switching operations with resistive loads
Test Voltage Between Open Contacts750V for 1 minute
Status Indicators2, indicates output is ON

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Discrete Combination Terminal

PX-549: Eight inputs/Eight outputs, 24VDC Discrete Input/Output Terminal

$138.00

The PX-549 (Type 1) DC Input/Output Terminal provides eight 24VDC inputs and eight 24VDC 0.5 A outputs with reverse polarity protection and LED status.

Diagram Description: A terminal block with eight input channels and eight output channels, each with corresponding LED indicators. Shows connections for 24VDC power supply and common, and input/output terminals.

General Specifications
Operating Temp32 to 131 °F (0 to 55 °C)
Storage Temp-13 to 185 °F (-25 to 85 °C)
Relative Humidity5% to 95%, non-condensing
Environment AirNo corrosive gases permitted
Mounting/Orientation Restrictions35mm DIN rail/None
VibrationConforms to EN 60068-2-6
ShockConforms to EN 60068-2-27/ EN 60068-2-29
Noise ImmunityConforms to EN 61000-6-2/ EN61000-6-4
Protection ClassIP20
Weight60g (2.1 oz)
Dimensions (WxHxD)12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Adjacent Mounting on Bus Terminals with Power ContactYes, DC only ✔️
Adjacent Mounting on Bus Terminals without Power ContactNo ❌
Passes Terminal Bus PowerYes ✔️
Passes PE BusNo ❌
Agency Approvals*UL/cUL File No. E157382, CE
Terminal Specifications
Inputs/Outputs Per Terminal8 sinking inputs / 8 sourcing outputs
Data Bytes Used1 byte (inputs) / 1 byte (outputs)
Input/Output Power SourceRequires external 24VDC power source
Operating Voltage Rating24VDC (-15%/+20%)
Current Consumption (from I/O Bus)25mA typical
Current Consumption (from Terminal Power Bus)15mA + load typical
Electrical Isolation500Vms (I/O bus/field potential)
Heat Dissipation1W max
Status Indicators8 input and 8 output, indicates ON
Input Specifications
Peak Voltage Rating30VDC
ON Voltage Level15 to 30 VDC
OFF Voltage Level-3 to +5 VDC
Minimum ON Current2mA
Minimum OFF Current40mA
Current Consumption (from I/O Bus)3mA typical
OFF to ON Response3ms
ON to OFF Response3ms
Output Specifications
Max. Load Current per Output0.5 A (Short-Circuit Protected)
On Voltage Drop0.14 VDC @ 2A
Maximum Leakage Current5mA
Maximum Inrush Current2A
Maximum Short-Circuit Voltage45V
Load TypeResistive, inductive, lamp
Reverse Voltage ProtectionYes ✔️
OFF to ON Response50ms
ON to OFF Response75ms

*To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

System Installation and Removal

Bus Coupler and Bus Terminal Installation

Bus Coupler Installation:

  1. Attach a Bus Coupler by snapping it onto 35mm DIN rail and securing it into position using the DIN rail locking wheel (where applicable) located on the left side of the coupler.
  2. Insert unit using tongue and groove molded guide and press gently until it becomes firmly seated on DIN rail.

Where applicable, rotate Locking Wheel to lock Bus Coupler ⚙️

Bus Terminal Installation:

  1. To add a bus terminal, insert unit onto the right side of the Bus Coupler using the tongue and groove at the top and bottom of the unit, pressing gently until it snaps onto the DIN rail.

? Important: A proper connection cannot be made by sliding the units together on the DIN rail. When correctly installed, no significant gap can be seen between the attached units. Bus connection is made through the six slide contacts located on the upper right side of the units. Up to 64 bus terminals can be added per Bus Coupler, including a bus end terminal.

Align tab with molded guide

Wiring Connections

Wire connection is made through a spring clamp style terminal. This terminal is designed for a single-conductor solid or stranded wire. Wire connection is made by firmly pushing the screwdriver into the screwdriver slot, inserting the wire into the wire slot, and removing the screwdriver, locking the wire into position.

Wiring Specifications:

Connection TypeSpring Clamp Terminals
Wire Gauge28-14 AWG (0.08–2.5 mm²)
Screwdriver Width2.5 mm (0.10 in) such as P/N TW-SD-MSL-2
Wire Stripping Length8mm

*For Thermocouple terminals, thermocouple extension wire is recommended.

Diagram Description: Shows a screwdriver slot and a wire slot on a spring clamp terminal. A screwdriver is depicted being used to insert a wire.

Removing Bus Coupler and Bus Terminals

A locking mechanism prevents individual units from being pulled off. For bus terminal removal, pull the orange DIN rail release tab firmly to unlatch the unit from the rail. If attached to other terminal units, slide unit forward until released. For Bus Couplers with locking wheels, release the DIN rail locking wheel, then pull firmly on DIN rail release tab.

Where applicable, rotate Locking Wheel to unlock Bus Coupler ⚙️

Firmly pull DIN Rail Release Tab to unlatch unit from rail.

Installation Considerations

Terminal Dimensions and Spacing Requirements

Use the following diagrams to ensure the Protos X system can be installed correctly in your application. Protos X terminals require 35mm DIN rail for mounting; there are no orientation restrictions.

To ensure proper airflow for cooling purposes, units should be spaced, at a minimum, as shown. It is also important to check the Protos X dimensions against the conditions required for your application.

Diagram Description: Shows a DIN rail with multiple terminals mounted. Spacing recommendations are indicated with dimensions (e.g., 20mm min, 35mm min). Also shows dimensions for various Protos X terminals (PX-TCP2, PX-TCP1/PX-MOD/PX-EIP1, PX-903, PX-902, Standard Terminal) and their overall height and width.

Spacing Requirements:

  • Minimum 20mm (0.8") spacing between terminals.
  • Minimum 35mm (1.4") spacing between terminals.

Terminal Types

Protos XTM terminals are available in five basic types, each with specific characteristics regarding power bus and PE bus continuity.

Type 1

Description: Passes terminal power bus from the preceding terminal to the next. Must be mounted to a preceding terminal that passes bus power.

Diagram Description: Shows I/O Bus contacts, Terminal power bus contact, and Terminal power bus pass through. Indicates continuity of terminal power bus.

Type 2

Description: Passes terminal power bus and PE from the preceding terminal to the next. Must be preceded by a terminal that passes both terminal power bus and PE.

Diagram Description: Shows I/O Bus contacts, Terminal power bus contact, Terminal power bus pass through, Terminal PE bus contact, and Terminal power bus pass through. Indicates continuity of terminal power bus and PE.

Type 3

Description: Does not pass the terminal power bus or PE. Can be preceded by any terminal, but interrupts the terminal power bus and PE.

Diagram Description: Shows I/O Bus contacts, Terminal power bus contact, and Terminal power bus pass through. Indicates interruption of terminal power bus and PE.

Type 4

Description: Requires external voltage connection and supplies the terminal power bus to terminals to its right. Terminals to its right must support the same power bus. Does not pass terminal power or PE from preceding terminals.

Diagram Description: Shows I/O Bus contacts and Terminal power bus supply. Indicates external supply and no bus contacts.

Type 5

Description: Used to separate the terminal power bus and PE from other terminals. Can be mounted next to any terminal.

Diagram Description: Shows I/O Bus contacts and Terminal power bus supply. Indicates separation of bus and PE.

PDF preview unavailable. Download the PDF instead.

pxiodiscrete Aspose Ltd. Aspose for Java 22.3

Related Documents

Preview BX-8NN8TN2 Discrete Combo Module Cut Sheet - AutomationDirect
Technical specifications and product details for the AutomationDirect BX-8NN8TN2 discrete combo module, featuring 8 input and 8 output points, 48 VDC operation, and sinking/sourcing capabilities. Includes agency approvals and dimensional drawing links.
Preview AutomationDirect BRX Micro PLC System: Overview and Specifications
Discover the AutomationDirect BRX Micro PLC system, a versatile and compact modular solution for industrial automation. This document details its features, MPU form factors, expansion modules, and technical specifications for building robust control systems.
Preview AutomationDirect UT Series Ultrasonic Sensors - M30 Metal Discrete/Analog Output
Explore the AutomationDirect UT Series of M30 (30mm) metal ultrasonic sensors, offering discrete and analog output options. These sensors feature a 10-30 VDC operating voltage, IP67 rating, and are available with adjustable sensitivity for discrete models. Learn about their specifications, wiring diagrams, dimensions, and compatible mounting accessories.
Preview SureMotion XYZ Gantry Assembly User Manual
User manual for AutomationDirect's SureMotion XYZ Gantry systems, detailing assembly of LAHP linear actuators, bracket combinations, and sensor installation for multi-axis motion control.
Preview CLICK PLUS C2-08DR-6V Option Slot Module Specifications
Detailed specifications for the CLICK PLUS C2-08DR-6V Option Slot Module, including discrete and analog I/O capabilities, wiring diagrams, and general operating parameters. This module offers 4 DC inputs, 4 relay outputs, 4 analog voltage inputs, and 2 analog voltage outputs.
Preview AutomationDirect CLICK PLC Family Overview and Specifications
Comprehensive overview of the AutomationDirect CLICK PLC family, including CLICK and CLICK PLUS models. Details system configuration, communication options, analog I/O, and a comparison of features. Lists various PLC units, power supplies, input/output modules, and programming software.
Preview CLICK Stackable I/O Module Specifications - C0-04DA-2
Detailed specifications for the AutomationDirect CLICK Stackable I/O Module, model C0-04DA-2. This 4-channel analog voltage output module offers 12-bit resolution and a 0-10V output range, requiring external 24VDC power. The document includes wiring diagrams, output specifications, general operating conditions, power budgeting information, and hardware/software compatibility for the CLICK PLC family.
Preview AutomationDirect Wiring Accessories: Crimping Tools Guide
Comprehensive guide to Zoller+Fröhlich and AutomationDirect crimping tools, including K70ZA series fixed tools and DN-CT series interchangeable die tools for various wire sizes and terminal types.