CLICK Stackable I/O Module Specifications

Model: C0-04DA-2

Part Number: C0-04DA-2

Price Code: $00c8h

4-Channel Analog Voltage Output Module

This module provides 4-channel analog voltage output with a 12-bit resolution. The output range is 0-10V. It requires external 24VDC power and includes a removable terminal block (AutomationDirect p/n C0-8TB).

Wiring Diagram

The diagram shows the C0-04DA-2 module with connections for CH1, CH2, CH3, and CH4 outputs. Each channel has a load connected. The 'OV' terminals are internally connected. The diagram also illustrates the 24VDC power supply input (+24V and OV).

Output Specifications

Module Output Specifications
Specification Value
Outputs per Module 4
Output Range 0-10 V
Resolution 12-bit, 2.44 mV per count
Output Type Voltage sourcing at 10mA max. (1 common)
Output Value in Program Mode Determined by CPU
Output Value in Fault Mode 0 V
Output Impedance 0.2 Ω typical
Load Impedance >1000Ω
Maximum Capacitive Load 0.01 uF maximum
Allowed Load Type Grounded
Maximum Inaccuracy 0.5% of range
Max. Full Scale Calibration Error (Not including Offset) ±0.2% of range maximum voltage
Max. Offset Calibration Error ±0.2% of range maximum
Accuracy vs. Temperature +75 PPM/°C maximum full scale calibration change (±0.0025% of range/°C)
Max. Crosstalk at DC, 50/60Hz -72 dB, 1 LSB
Linearity Error (End to End) +4 LSB max., (±0.1% of full scale); monotonic with no missing codes
Output Stability and Repeatability ±2% LSB after 10 minute warmup period typical
Output Ripple 0.1% of full scale
Output Settling Time 0.3 ms maximum, 5us minimum (full scale range)
All Channel Update Rate 10ms
Max. Continuous Overload Outputs current limited to 40mA typical; continuous overloads on multiple outputs can damage module.
Field to Logic Side Isolation 1800 VAC applied for 1 second (100% tested)
Type of Output Protection 0.1 µF transient suppressor
Output Signal at Power Up and Power Down 0 V
External 24VDC Power Required 85mA
Base Power Required (24VDC) 20mA
Terminal Block Replacement Automation Direct p/n C0-8TB
Drawing Link PDF
Weight 2.9 oz [82g]

ZIPLink Pre-Wired PLC Connection Cables and Modules for CLICK PLC

AutomationDirect offers ZIPLink solutions for simplified wiring. These include pre-wired cables and DIN rail mount connector modules that reduce installation time and complexity.

  • 11-pin connector cable: ZL-CO-CBL11 (0.5 m length), ZL-CO-CBL11-1 (1.0 m length), ZL-CO-CBL11-2 (2.0 m length)
  • ZL-RTB20 20-pin feed-through connector module

The image shows examples of ZIPLink cables and a feed-through connector module.

Important Note

NOTE: When using this module, you must also use CLICK programming software and PLC firmware version V1.40 or later.

General Specifications for All CLICK Stackable I/O Modules

These general specifications apply to all CLICK Stackable I/O Modules. Refer to the appropriate I/O temperature derating charts for specific operating conditions based on your application's ambient temperature.

General Specifications
Specification Value
Operating Temperature Analog, analog combo I/O modules only: 32°F to 140°F [0°C to 60°C]; All other modules: 32°F to 131°F [0°C to 55°C]
Storage Temperature -4°F to 158°F [-20°C to 70°C]
Ambient Humidity 30% to 95% relative humidity (non-condensing)
Environmental Air No corrosive gases. Environmental pollution level is 2 (UL840)
Vibration All other modules: IEC60068-2-6 (Test Fc)
Shock MIL STD 810C, Method 516.2, IEC60068-2-27, JIS C60068-2-27, Category [f], Procedure [VIII]
Noise Immunity EN61131-2, EN61000-4-2 (ESD), EN61000-4-3 (RFI), EN61000-4-4 (FTB), EN61000-4-5 (Surge), EN61000-4-6 (Conducted), EN61000-4-8 (Power frequency magnetic field immunity)
Emissions EN55011:1998 Class A; EN61000-6-4:2007+A1:2011
Agency Approvals UL508, UL61010-2-201 (File No. E157382); CE (EN61131-2); CUL Canadian C22.2
Other RoHS 2011/65/EU Amendment (EU)2015/863

NOTE: These modules are available to use with CLICK or CLICK PLUS systems.

PDF preview unavailable. Download the PDF instead.

c004da2

Related Documents

Preview AutomationDirect CLICK PLC Hardware User Manual: Installation, Operation, and Specifications
Official user manual for AutomationDirect CLICK PLC hardware. Covers installation, programming, specifications, troubleshooting, and maintenance for the CLICK PLC series.
Preview AutomationDirect PLC Systems Overview: Programmable Logic Controllers
A comprehensive guide to AutomationDirect's range of Programmable Logic Controllers (PLCs), detailing product families like CLICK, Do-more, Productivity Series, LS Electric XGB, and ProductivityOpen. Features, benefits, pricing, programming software, and industrial automation solutions are covered.
Preview AutomationDirect CLICK PLUS C2-01CPU Quick Start Guide
A quick start guide for the AutomationDirect CLICK PLUS C2-01CPU, covering installation, hardware setup, wiring, and basic connectivity.
Preview AutomationDirect CLICK PLC Family Overview and Specifications
Comprehensive overview of the AutomationDirect CLICK PLC family, including CLICK and CLICK PLUS models. Details system configuration, communication options, analog I/O, and a comparison of features. Lists various PLC units, power supplies, input/output modules, and programming software.
Preview CLICK PLUS C2-08DR-6V Option Slot Module Specifications
Detailed specifications for the CLICK PLUS C2-08DR-6V Option Slot Module, including discrete and analog I/O capabilities, wiring diagrams, and general operating parameters. This module offers 4 DC inputs, 4 relay outputs, 4 analog voltage inputs, and 2 analog voltage outputs.
Preview CLICK PLUS Applications Guide: Programming Patterns and Node-RED Integration
A comprehensive guide detailing programming patterns, advanced math logic, and Node-RED project examples for the AutomationDirect CLICK PLUS PLC. Learn to implement latching coils, timers, state machines, motion control, and integrate with Node-RED for data acquisition, web services, databases, and IoT.
Preview CLICK PLUS PLC Maintenance Guide - C2-USER-M
This chapter of the CLICK PLUS PLC Hardware User Manual (C2-USER-M) details essential maintenance procedures to ensure the longevity and reliable operation of the PLC. It covers checking LED indicators, performing project backups, verifying operating environment conditions (temperature, humidity), confirming operating voltage, inspecting physical condition, and checking project functionality via the CLICK programming software. Safety warnings regarding hot-swapping are also included.
Preview Do-more! BRX PLC Error Codes and System Locations Guide
Comprehensive guide to Do-more! BRX PLC error codes, system locations, and memory locations with system-assigned nicknames. Includes program check rules and detailed descriptions for troubleshooting and system configuration.