Felicitysolar IVCM PRO Series Solar Inverter User Guide
IVCM PRO Series (1KW~3KW)
Document Number: 358-010424-00
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING:
This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
- CAUTION -- To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- Fuses (150A or 200A) are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
WARNING MARKS
Warning marks inform users of conditions which can cause serious physical injury or death, or damage to the device. They also tell users how to prevent the dangers. The warning marks used in this operation manual are shown below:
Symbols | Name | Instruction |
---|---|---|
[Danger Symbol] | Danger | Serious physical injury or even death may occur if not follow the relative requirements |
[Warning Symbol] | Warning | Physical injury or damage to the devices may occur if not follow the relative requirements |
[Electrostatic Sensitive Symbol] | Electrostatic sensitive | Damage may occur if not follow the relative requirements |
[Hot Surface Symbol] | Hot surface | Sides of the device may become hot. Do not touch. |
[Note Symbol] | Note | The procedures taken for ensuring proper operation. |
INTRODUCTION
Features
- Pure sine wave inverter
- Built-in MPPT solar charge controller
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload / Over temperature/ short circuit protection
- Cold start function
- Depending on the model, Turbo mode can be enabled in APL mode to use up to three times the maximum rated load
Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:
- Generator or Utility.
- PV modules (option)
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.
System Diagram Description:
A simplified system diagram shows the inverter connected to a power grid (utility), PV modules, and a load (appliances). The inverter has AC input and PV input terminals, and an AC output terminal. The diagram illustrates the flow of power.
PRODUCT OVERVIEW
Diagram Description: A front view of the Felicitysolar inverter is shown. It has a display screen and several buttons. Below the inverter, there are connection ports. To the right, a diagram shows the rear view with various ports and components labeled numerically from 1 to 18.
Component List:
- 1. LCD display
- 2. Inverter or Utility indicator
- 3. Charging indicator
- 4. Fault or warning indicator
- 5. ESC button
- 6. UP button
- 7. DOWN button
- 8. ENTER button
- 9. Input breaker
- 10. Fan
- 11. AC output port
- 12. AC input port
- 13. Battery connection port
- 14. PV input connection port
- 15. Wifi port
- 16. RS485 communication port
- 17. Dry node
- 18. Switch
SPECIFICATIONS
Table 1: Line Mode Specifications
Model | IVCM1012 PRO | IVCM2024 PRO | IVCM3024 PRO |
Rated output Power | 1000VA/1000W | 2000VA/2000W | 3000VA/3000W |
Instant Output Power (Turbo Mode) | 3000W | 4000W | 4500W |
Nominal DC Input Voltage | 12V | 24V | 24V |
Input Voltage waveform | Sinusoidal (utility or generator) | ||
Nominal Input Voltage | 230Vac | ||
Low Line voltage Disconnect | 170Vac±7V(UPS); 90Vac±7V (Appliances) | ||
Low Loss Voltage Re-connect | 180Vac±7V(UPS); 100Vac±7V (Appliances) | ||
High Line Voltage Disconnect | 280Vac±7V | ||
High Line Voltage Re-connect | 270Vac±7V | ||
Max AC Input Voltage | 300Vac | ||
Nominal Input Frequency | 50Hz/60Hz (Auto detection) | ||
Low Line Frequency Disconnect | 40±1Hz | ||
Low Line Frequency Re-connect | 42±1Hz | ||
High Line Frequency Disconnect | 65±1Hz | ||
High Line Frequency Re-connect | 63±1Hz | ||
Output Voltage Waveform | As same as input waveform | ||
Output Short Circuit Protection | Line mode: Circuit Breaker Battery mode: Electronic Circuits | ||
Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | ||
Transfer Time (Single unit) | 10ms typical (UPS); 20ms typical (Appliances) | ||
Max Bypass Overload Current | 10A | 15A | 30A |
Max Inverter/Rectifier Current | 5A/1000W | 10A/2000W | 15A/3000W |
Utility Charge Mode Specifications | |||
Nominal Input Voltage | 230Vac | ||
Input Voltage Range | 90-280Vac | ||
Nominal Output Voltage | Dependent on battery type | ||
Max Charge Current | 20A | 30A | 30A |
Charge Current Regulation | 10-20A (Adj 10A) | ||
Over Charge Protection | Yes | ||
Solar Charging & Grid Charging | |||
Max PV Open Circuit Voltage | 105V | 145V | |
Operating Voltage Range | 15-90V | 30-120V | |
Max Input Power | 800W | 1600W | |
Max Solar Charging Current | 60A | 90A | |
Max Charging Current (PV + Grid) | 80A | 95A | 95A |
Max Input Current | 35A |
Charge Algorithm
Algorithm | Three stage: Buck CC (Constant current stage) -> Buck CV (Constant voltage stage) -> Float (Constant voltage stage) |
Charging Curve Diagram Description:
A graph shows battery voltage over time during charging. It illustrates three stages: Bulk (Constant Current), Absorption (Constant Voltage), and Maintenance (Floating). The charging current percentage decreases over time.
Battery Type Setting Table:
Battery Type Setting | Battery Type | Bulk CC/CV | Float |
AGM | 14.4V/28.8V | 13.6V/27.2V | |
Flooded | 14.6V/29.2V | 13.8V/27.6V | |
Self - defined | Adjustable, up to 15V/30V | ||
Lithium |
Inverter Mode Specifications
Model | IVCM1012 PRO | IVCM2024 PRO | IVCM3024 PRO |
Rated output Power | 1000VA/1000W | 2000VA/2000W | 3000VA/3000W |
Instant Output Power (Turbo Mode) | 3000W | 4000W | 4500W |
Nominal DC Input Voltage | 12V | 24V | 24V |
Output Voltage Waveform | Pure sine wave | ||
Nominal Output Voltage | 230Vac±5% | ||
Nominal outputFrequency (Hz) | 50±0.3Hz/60Hz±0.3Hz (Auto detection) | ||
Peak Efficiency | 93% | ||
Over-Load Protection (SMPS load) | 5s@≥150% load; 10s@110%~150% load | ||
Surge Rating | 15A/3000W | ||
Capable of Starting Electric | Yes | ||
output Short Circuit Protection | Yes | ||
Cold Start Voltage | 11.5V | 23.0V | |
Low Battery Alarm | |||
@ Load < 20% | 11.0V | 22.0V | |
@ 20% ≤ Load < 50% | 10.7V | 21.4V | |
@ Load ≥ 50% | 10.1V | 20.2V | |
Low Battery Alarm Recovery | |||
@ Load < 20% | 11.5V | 23.0V | |
@ 20% ≤ Load < 50% | 11.2V | 22.4V | |
@ Load ≥ 50% | 10.6V | 21.2V | |
Low DC Input Shut-down | |||
@ Load < 20% | 10.5V | 21.0V | |
@ 20% ≤ Load < 50% | 10.2V | 20.4V | |
@ Load ≥ 50% | 9.6V | 19.2V | |
High DC Input Alarm & Fault | 15V | 30V | |
High DC Input Recovery | 14.5V | 29V | |
General Specifications | |||
Operating Temperature | -10°C~55°C | ||
Range Storage Temperature | -15°C~60°C | ||
Net Weight (Kg) | 5.5kg | 6.5kg | 6.5kg |
Product Size (D*W*H) | 340x248x107mm | 340x248x107mm | 340x290x124mm |
Package Dimension (D*W*H) | 422x330x181mm | 422x330x181mm | 422x372x198mm |
INSTALLATION
Safety Guidance
Warning marks inform users of conditions which can cause serious physical injury or death, or damage to the device. They also tell users how to prevent the dangers. The warning marks used in this operation manual are shown below:
- After receiving this product, first confirm the product package is intact. If any question, contact the logistic company or local distributor immediately.
- The installation and operation of inverter must be carried out by professional technicians who have received professional trainings and thoroughly familiar with all the contents in this manual and the safety requirements of the electrical system.
- Do not carry out connection/disconnection, unpacking inspection and unit replacement operations on the inverter when power source is applied. Before wiring and inspection, users must confirm the breakers on DC and AC side of inverter are disconnected and wait for at least 5 minutes.
- Ensure there is no strong electromagnetic interference caused by other electronic or electrical devices around the installation site.
- Do not refit the inverter unless authorized.
- All the electrical installation must conform to local and national electrical standards
- Do not touch the housing of the inverter or the radiator to avoid scald as they may become hot during operation.
- Ground with proper technics before operation.
- Do not open the surface cover of the inverter unless authorized. The electronic components inside the inverter are electrostatic sensitive. Do take proper anti-electrostatic measures during authorized operation.
- The inverter needs to be reliably grounded.
- Ensure that DC and AC side circuit breakers have been disconnected and wait at least 5 minutes before wiring and checking.
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
- The unit x 1
- User manual x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
Diagram Description: An illustration shows the bottom of the inverter with two screws indicated for removal to access internal wiring.
Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between -10°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Mounting Diagram Description:
A diagram shows the side view of the inverter mounted on a wall. It indicates recommended clearances of 50cm on the sides and 20cm above and below for heat dissipation and wire access. It also shows a vertical mounting orientation and suggests mounting on concrete or non-combustible surfaces.
INSTALLATION - Wiring
Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable.
Recommended battery cable and terminal size:
Model | Typical Amperage | Battery Capacity | Wire Size | Torque Value |
1KW/2KW | 84A | 100AH | 1*4AWG | 2~3Nm |
200AH | 2*8AWG | |||
3KW | 125A | 100AH | 1*4AWG | 2~3Nm |
200AH | 2*4AWG |
Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- The 1KW model supports only 12VDC systems. The battery string connection is shown in the chart below. For 1KW models, you are advised to connect a battery with a capacity of at least 100Ah.
Battery Connection Diagram Description:
Diagrams show how to connect batteries for 1KW and 2-3KW models. For the 1KW model, two 12V batteries are shown in series. For the 2-3KW models, two sets of two 12V batteries are shown in series, indicating parallel connection of battery banks.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative(-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 10A for 1KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
Model | Gauge | Torque Value |
1KW | 16AWG | 0.8~1.0 Nm |
2KW | 14AWG | 0.8~1.0 Nm |
3KW | 12AWG | 1.2~1.6 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor [Ground Symbol] first.
AC Wiring Diagram Description:
Diagrams illustrate the connection of AC input and output wires to the terminal blocks. It shows the correct polarity for Ground (yellow-green), Line (brown or black), and Neutral (blue) wires for both AC input and AC output. The PE protective conductor is shown connected first.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your least 2~3 connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model | Typical Amperage | Cable Size | Torque |
1KW / 2KW / 3KW | 60A | 8AWG | 1.4~1.6 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Max. power voltage (Vmp) should be during PV array MPPT voltage range.
Solar Charging Mode Table:
INVERTER MODEL | 1KW | 2KW/3KW |
Max.PV Array Open Circuit Voltage | 105V | 145V |
PV Array MPPT Voltage Range | 15Vdc~90Vdc | 30Vdc~120Vdc |
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole(+) of connection cable to positive pole(+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
PV Connection Diagram Description:
Diagrams show the connection of PV module cables to the inverter's PV input terminals. It emphasizes correct polarity for positive (+) and negative (-) conductors.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
Diagram Description: An illustration shows the bottom cover being reattached to the inverter using screws.
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external device when battery voltage reaches warning level.
Dry Contact Signal Table:
UnitStatus | Condition | Dry contact port: NC & C | Dry contact port: NO & C |
Power Off | Unit is off and no output is powered. | Close | Open |
Power On | Battery voltage < Setting value in Program 12 | NO & C | Close |
Battery voltage > Setting value in Program 13 or battery charging reaches floating stage | Close | NO & C |
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the Left side of the case) to turn on the unit.
Diagram Description: An image shows the front panel of the inverter with the ON/OFF switch highlighted on the left side.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
Diagram Description: An image of the inverter's front panel display and control buttons. It shows the LCD screen, indicator lights, and four function keys (ESC, UP, DOWN, ENTER).
Function Key Table:
Function Key | Icon | Description |
ESC | [ESC Icon] | To previous page |
UP | [UP Icon] | To go to previous selection |
DOWN | [DOWN Icon] | To go to next selection |
ENTER | [ENTER Icon] | To confirm the selection or go to next page |
LED Indicator Table:
LED Indicator | Icon | Description |
Inverter | [Inverter LED Icon] | The inverter runs in off-grid mode, and the LED light will always be on. When the inverter is running in mains mode, the LED light will always flash. The inverter is not running in off-grid mode or mains mode, and the LED light is off. |
Battery | [Battery LED Icon] | Charging the battery, the LED flicker. Battery is full, the LED light will always-on. The battery is not charged, the LED light will go out. |
Fault | [Fault LED Icon] | If inverter in fault event, the LED light will always-on. If inverter in warning event, the LED light will flash. Inverter work normally, the LED light will go out. |
Buzzer Information
Turn on/off the inverter, the buzzer will last for 2.5s. Press any button, the buzzer will last for 0.1s. Hold on the "ENTER" button, the buzzer will last for 3s. If in fault event, the buzzer will keep going. If in warning event, the buzzer will beep discontinuous (Check more information on the chapter of "Warning Code Table").
LCD Display Icons
Output Information
Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100%. ?
Indicates Lithium battery type. ?
Indicates communication is built between inverter and battery. ?
Mode operation Information
- Indicates the utility.
- Indicates load is supplied by utility directly.
- Indicates that the load has an output.
- Indicates the inverter/charger is working.
- Indicates the PV panels.
- Indicates PV MPPT is working.
- Indicates the WIFI link. ?
- Indicates machine model.
Input Source Information
Indicate input voltage, input frequency, PV voltage, PV power, battery voltage and charger current.
Configuration Program and Fault Information
- Indicates the setting programs.
- Indicates the warning and fault codes.
- Warning: [Warning Icon] flashing with warning code.
- Fault: [Fault Icon] lighting with fault code.
Mute Operation
Indicates unit alarm is disabled.
LCD Operation Flow Chart
Flow Chart Description:
A flowchart illustrates the navigation through the inverter's LCD menu. It shows how to access the Base Information Page, Setting Page, and Rated Information Page using the ENTER, UP, DOWN, and ESC buttons.
Base Information Page
The base information will be switched by pressing "UP" or "DOWN" key. The selectable information is switched as below order:
Base Information Screens:
Input voltage / output voltage
Utility voltage is 230V, output voltage is 230V
Input frequency / output voltage
Utility frequency is 50.0Hz, output voltage is 230V
Battery voltage / Output voltage
Battery voltage is 13.0V, output voltage is 230V
Charging current / Output voltage
Charging current is 60A, output voltage is 230V
Battery voltage / Output frequency
Battery voltage is 13.0V, output frequency is 50.0Hz
Battery voltage / Load percentage
Battery voltage is 13.0V, load percentage is 40%
Battery voltage / Load VA
Battery voltage is 13.0V, output wattage is 1.00kVA
Battery voltage / Load wattage
Battery voltage is 13.0V, output wattage is 1.00kW
PV voltage / Output voltage
PV voltage is 80V, output voltage is 230V
PV power / Output voltage
PV power is 800W, output voltage is 230V
Battery voltage / Discharging current
Battery voltage is 13.0V, discharging current is 77A
Setting Page
Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.
Setting Items Table:
Setting items: | Selectable option | Description |
00 Exit setting | ESC | |
01 Output voltage setting | 220V | Output voltage configuration |
230V | ||
240V | ||
02 Output frequency setting | 50Hz | Output frequency configuration |
60Hz | ||
03 Utility input range setting | APL | APL should be selected, when the utility is not well. |
UPS | ||
04 Output source priority | Utility >> PV >> Battery | Utility provides power to the loads first. PV and battery will provide power to loads only when utility is not available. |
PV >> Utility >> Battery | ||
PV >> Battery >> Utility |
Charger Priority Table:
Charger priority | Setting | Description | |
05 | PV first | CHS 05 50 | PV will charge battery first. Utility will charge battery only when PV is unavailable. |
PV and Utility | CHS 05 SAU | PV and utility will charge battery together. | |
PV Only | CHS 05 050 | Only PV can charge the battery. |
Max Charging Current Tables:
Max charging current (Utility charge current + PV charging current) | Setting | Description | |
06 | 1KW-2KW model | 6CC 06 80 | Setting range is from 10A to 80A. Increment of each click is 1A. |
3KW model | 6CC 06 90 | Setting range is from 10A to 90A. Increment of each click is 1A. | |
Max utility charging current setting | |||
07 | 1KW-2KW model | CHC 07 20 | Setting range is from 10A to 20A. Increment of each click is 10A. |
3KW model | CHC 07 30 | Setting range is from 20A to 30A. Increment of each click is 10A. |
Battery Type Setting Table:
Battery type setting | Setting | Description | |
08 | The battery type is AGM | 6At 08 AGn | |
The battery type is Flooded | 6AE 08 FLd | ||
The battery type is self-defined | 6AE 08 USE | If "Self-defined" or "Lib" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 9, 10 and 11. If "Lib" is selected, inverter can charge Lithium battery when the Lithium battery need to be activated. Please make sure Lithium battery is connected before you start up inverter. If inverter doesn't connect battery or Lithium battery, do not select "Lib" battery type. | |
The battery type is Lib | 6AE 08 L16 |
Setting Page (Continued)
Bulk Charging Voltage Setting Table:
Bulk charging voltage setting (C.V voltage) | Setting | Description | |
09 | 12V model | 6V 09 14.1 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 12.0V to 15.0V. Increment of each click is 0.1V |
24V model | 6V 09 28.2 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 24.0V to 30.0V. Increment of each click is 0.1V |
Floating Charging Voltage Table:
Floating charging voltage | Setting | Description | |
10 | 12V model | FLU 10 13.5 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 12.0V to 15.0V. Increment of each click is 0.1V |
24V model | FLY 10 27.0 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 24.0V to 30.0V. Increment of each click is 0.1V |
Low DC Cut-off Voltage Table:
Low DC cut-off voltage | Setting | Description | |
11 | 12V | 600 11 11.5 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 10.5V to 13.5V. Increment of each click is 0.1V |
24V | 600 11 23.0 | If "self-defined" or "LIb" is selected in program 8, this program is enabled. Setting range is from 21.0V to 17.0V. Increment of each click is 0.1V |
Setting Battery Voltage Point Back to Utility Table:
Setting battery voltage point back to utility when selecting "SBU priority" in program 4 | Setting | Description | |
12 | 12V | 660 12 11.5 | Setting range is from 11.0V to 13.5V. Increment of each click is 0.1V |
24V | 660 12 23.0 | Setting range is from 22.0V to 17.0V. Increment of each click is 0.1V |
Setting Battery Voltage Point Back to Battery Mode Table:
Setting battery voltage point back to battery mode when selecting "SBU priority" in program 4 | Setting | Description | |
13 | 12V | 660 13 13.5 | Setting range is from 12.0V to 15.0V. Increment of each click is 0.1V |
24V | 660 13 27.0 | Setting range is from 24.0V to 30.0V. Increment of each click is 0.1V |
Overload Bypass Function Table:
Overload bypass function | Setting | Description | |
14 | Enable | 660 13 FUL | Battery should be charged to float charging stage. |
Disable | 6LP 14 di 5 | If enabled, the inverter will switch to utility mode if overload happens in battery mode. | |
Enable | 6LP 14 ENA |
Overload Restart Function Table:
Overload restart function | Setting | Description | |
15 | Disable | OLF 15 di 5 | If it is enabled, the inverter will auto restart when overload occurs. |
Enable | OLF 15 ENA |
Over Temperature Restart Function Table:
Over temperature restart function | Setting | Description | |
16 | Disable | OF 16 di 5 | If it is enabled, the inverter will auto restart when over temperature occurs. |
Enable | OF 16 ENA |
Backlight of LCD Table:
Backlight of LCD | Setting | Description | |
17 | Disable | 6L 17 di 5 | If selected, LCD backlight will be off after no button is pressed for 60s. |
Enable | 6L 17 ENA | If selected, LCD backlight will be always-on. |
Auto Return to the First Page of Display Screen Table:
Auto return to the first page of display screen | Setting | Description | |
18 | Disable | 6FP 18 di 5 | If selected, the display screen will stay at latest screen user finally switches. |
Enable | 6FP 18 ENA | If selected, it will automatically return to the first page of display screen (Input voltage/ output voltage) after no button is pressed for 60s. |
Buzzer Alarm Table:
Buzzer Alarm | Setting | Description | |
19 | Disable | 6EP 19 di 5 | If selected, buzzer is not allowed to beep. |
Enable | 6EP 19 ENA | If selected, buzzer is allowed to beep. |
Turbo Mode Table:
Turbo Mode | Setting | Description | |
20 | Disable | EF6 20 di 5 | If selected, inverter cannot overload derated output. |
Enable | EF6 20 ENA | If selected, inverter starts the overload derated output. Max 3KVA load. |
Rated Information Page
The rated information will be switched by pressing "UP" or "DOWN" key. The selectable information is switched as below order:
Rated VA / WATT
Rated VA is 1KVA, WATT is 1KW
Rated battery voltage / Max. charge current
Rated battery voltage is 12V, Max charge current is 80A
Firmware version
Firmware version is 201
Max PV Voltage / Max MPPT Current
Max PV Voltage is 105V, Max MPPT Current is 60A
Turbo mode
In order to avoid operation failure caused by charging overload protection, Turbo mode is automatically activated when the total output power exceeds the rated output power, so that the product can power high-power devices at the rated output power. When using Turbo mode, note the following:
- Turbo is enabled by default. To disable Turbo, you can set it in the Settings or APP.
- The Turbo mode is disabled in the following three scenarios: (1) The mains is connected and in mains mode (2) The mains is set to UPS mode (3) When the Turbo mode is set to off
- Turbo mode is more suitable for heating and motor equipment, but not for all electrical appliances, some electrical appliances equipped with voltage protection (such as precision instruments, etc.) do not apply to Turbo mode. To confirm whether the device can use the Turbo mode, refer to the actual test.
Warning Code Table
When fault event happens, the fault LED is flashing. At the same time, warning code, icon [Warning Icon] is shown on the LCD screen.
Warning Code | Warning Information | Audible Alarm | Trouble Shooting |
03 | PV charging overcurrent | Restart the unit, if the error happens again, please return to repair center. | |
04 | PV temperature is too high | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
05 | High PV voltage | Beep three times every second | Please check the voltage of the solar panel, it should be less than 95V. If the voltage is ok, please contact your installer. |
06 | The PV relay voltage is abnormal | Internal components failed. Restart the unit, if the error happens again, please return to repair center. | |
07 | PV relay short circuit | Check if the Fans wiring connected well. Replace the fan. | |
08 | Fan 1 is locked. | ||
09 | Fan 2 is locked. | ||
10 | Overload | Beep twice every second | Reduce the loads. |
11 | Low battery | The battery voltage is too low, it should be charging. | |
16 | The communication between the primary and secondary cpus is faulty | Beep three times every second | Internal components failed. Restart the unit, if the error happens again, please return to repair center. |
Fault Code Table
When fault event happens, inverter will cut off output, and the fault LED is solid on. At the same time, fault code, icon [Fault Icon] and ERROR are shown on the LCD screen.
Fault Code | Fault Information | Trouble Shooting |
07 | Battery voltage is too high | Check if spec and quantity of batteries are meet requirements. |
17 | Overload protection | Reduce the loads nd Restart the machine. |
19 | Output short circuit | Check if wiring is connected well and remove abnormal load. |
21 | OP current sensor failed | Restart the unit, if the error happens again, please return to repair center. |
22 | Output voltage is too low | Reduce the connected load. |
23 | Output voltage is too high | Restart the unit, if the error happens again, please return to repair center. |
24 | Excessive inverter current | Reduce the connected load by switching off some equipment. |
25 | The inverter hardware current is too large | Reduce the connected load by switching off some equipment. |
26 | The soft start of the inverter voltage fails | Restart the unit, if the error happens again, please return to repair center. |
29 | The inverter current sensor is faulty | Please return to repair center. |
30 | Bus voltage is too low | Restart the unit, if the error happens again, please return to repair center. |
31 | Bus voltage is too high | AC Surge or internal components failed. Restart the unit, if the error happens again, please return to repair center. |
33 | Bus soft start fail | Internal components failed. Restart the unit, if the error happens again, please return to repair center. |
34 | Overtemperature occurs in radiator 1 | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. |
35 | Overtemperature occurs in radiator 2 | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. |
50 | EEPROM fault | Please return to repair center. |
90 | DSP BootLoad is not written | Please return to repair center. |