Taco Comfort Solutions

Submittal Data Information: SCI Series Pumps

Effective: January 27, 2020

Supersedes: May 14, 2015

Model: SCI1209-1760-1.5

Document Number: 301-2768-A

General Information

Job:Engineer:
Contractor:Rep:
Item No.Model No.Impeller Dia.G.P.M.Head/FtH.P.Elec. Char.
DOE Basic Model Number: SCI1209C-A-4P-PD

Configuration: Pump + Motor + Drive

PEI Value: 0.45

Energy Rating: 55

Pump and Drive Configurations

Pump Schematic

A diagram illustrating the pump's physical layout. Key connection points are labeled:

  • DISCHARGE: Outlet port for fluid.
  • SUCTION: Inlet port for fluid.
  • 1/4" NPT GAUGE TAP: A threaded port for pressure gauge connection.
  • 1/4" NPT CASING DRAIN PLUG: A threaded port for draining the pump casing.
  • P HOLE (MOTOR): A port related to the motor assembly.
  • N HOLE (PUMP): A port related to the pump assembly.

The diagram also shows labels A, B, C, D, E, F, G, H, J, K, R, S, T, U, V indicating various dimensions and features, and notes "SUBJECT TO CUSTOMER'S MOTOR SELECTION".

Drive Options and Dimensions

The SCI Series pumps are available with different drive configurations:

  • Basic drive: Standard drive unit.
  • Drive with optional disconnect: Drive unit with an integrated disconnect switch.
  • Drive with bypass: Drive unit incorporating a bypass feature.
HP RangeFrameDimensions - Inches (mm)
208V460V575VTUV
1.5 (1.1) - 5 (4.0)1.5 (1.1) - 10 (7.5)1.5 (1.1) - 10 (7.5)Without bypass A516.5 (420)9.5 (242)9.6 (243)
1.5 (1.1) - 5 (4.0)1.5 (1.1) - 10 (7.5)1.5 (1.1) - 10 (7.5)With bypass A518.9 (478)10.3 (262)10.3 (262)

Note: 50 Cycle Performance Curves attached when applicable.

Dimensional Data (NEMA TEFC Type 12 / IP55)

Detailed dimensions for NEMA TEFC Type 12 / IP55 rated pumps.

Model No.Flange Size (Suction x Discharge)Motor FrameHP1760 RPMABC (Motor)DEFGHJKLN (Pump)PRS
ANSI Class 125ANSI Class 125ANSI Class 125 (Motor)ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125ANSI Class 125
1209-1.51 1/2 x 1 1/4 (38 x 32)145JM1.517603.50 (89)9.10 (231)5.5 (140)5.94 (151)3.50 (89)7.09 (180)10.00 (254)9.84 (250)3.75 (95)1.63 (41)5.22 (133)0.62 (16)0.34 (9)5.0 (127)7.84 (199)

English dimensions are in inches. Metric dimensions are in millimeters. Metric data is presented in (). Do not use for construction purposes unless certified.

Materials of Construction

Details on materials used for pump components, available in Bronze Fitted and All Iron configurations.

BRONZE FITTEDALL IRON
Standard Pump ConstructionOptionalStandard Pump ConstructionOptional
125# Flange250# Flange125# or 250#125# Flange250# Flange125# or 250#
CasingCast Iron ASTM A48/A48M-03 Class 30ADuctile Iron ASTM A536-84 Grade 65-45-12N/ACast Iron ASTM A48/A48M-03 Class 30ADuctile Iron ASTM A536-84 Grade 65-45-12N/A
CoverCast Iron ASTM A48/A48M-03 Class 30ADuctile Iron ASTM A536-84 Grade 65-45-12N/ACast Iron ASTM A48/A48M-03 Class 30ADuctile Iron ASTM A536-84 Grade 65-45-12N/A
ImpellerBronze ASTM B584-98A C87500Bronze ASTM B584-98A C87500N/ACast Iron ASTM A48/A48M-03 Class 30ACast Iron ASTM A48/A48M-03 Class 30AN/A
Wear RingBronze ASTM B584-98A C92200N/AN/AN/AN/AN/A
ShaftCarbon Steel AISI 1045Carbon Steel AISI 1045Stainless Steel TYPE 416"T" or 410"T" ASTM A58Carbon Steel AISI 1045Carbon Steel AISI 1045Stainless Steel TYPE 416"T" or 410"T" ASTM A58
Shaft SleeveBronze ASTM B584-98A C92200Bronze ASTM B584-98A C92200Stainless Steel TYPE 303 ASTM A276Bronze ASTM B584-98A C92200Bronze ASTM B584-98A C92200Stainless Steel TYPE 303 ASTM A276
Mech. SealCeramic/EPTCeramic/EPTC/FCeramic/EPTCeramic/EPTC/F
Seal Flush LineN/AN/ACopperN/AN/AStainless Steel

CF - Consult Factory; NA - Not Available

Dimensional Data (250 PSI)

Dimensions for pumps rated at 250 PSI.

Model No.Flange Size (Suction x Discharge)HP1760 RPMABKS
ANSI Class 250ANSI Class 250ANSI Class 250ANSI Class 250
1209-1.51 1/2 x 1 1/4 (38 x 32)1.517603.75 (95)9.36 (238)1.88 (48)8.09 (206)

Maximum Assembly Weight

Motor FrameWeight Lbs (Kg)
145JM135 (61)

Operating Specifications

StandardOptional
FlangeANSI Class 125ANSI Class 250
Pressure175 PSIG* (1210 KPA)300 PSIG** (2070 KPA)
Temperature250°F (120°C)250°F (120°C)

Motors: All NEMA Standard (T Frame)

* In accordance with ANSI Standard B16.1 Class 125

** In accordance with ANSI Standard B16.1 Class 250 Dim.

Performance Curve Description

The document includes a performance curve graph illustrating the relationship between pump head and flow rate. The graph features:

  • X-axis: Flow in Gallons Per Minute (GPM), ranging from 0 to 100.
  • Y-axis (Left): Head in Feet (ft), ranging from 0 to 60.
  • Y-axis (Right): Head in Kilopascals (kPa), ranging from 0 to 200.
  • Multiple performance lines are shown, corresponding to different operating frequencies (e.g., 20Hz, 40Hz, 60Hz) and potentially motor/drive configurations.

This curve helps in selecting the appropriate pump operating point for specific system requirements.

Specifications

Motor Design Data

HP:
Volts:
Frequency:
Phase:

Drive Data

Protocols (Standard):BACnet, Modbus RTU, N2 Metasys, FLN Apogee, FC Protocol
Protocols (Optional):LonWorks®, DeviceNet, Profibus
Enclosure:NEMA Type 1 / IP21
I/O (Standard):6 Digital Inputs / 2 Digital Outputs, 1 Analog Current Output / 2 Analog Inputs, 2 Pulse Inputs, 2 Form C Relays
Additional Control Options:None, General Purpose I/O, Relay Card, 24VDC Supply, Analog I/O
Electrical Configuration:Basic (no disconnect), Mechanical disconnect, Fused disconnect, 2 Contactor Bypass - Drive Fusing & Main Disconnect (5kA SCCR), 2 Contactor Bypass - Main Fusing & Disconnect (100kA SCCR), 3 Contactor Bypass - Drive Fusing & Main Disconnect (5kA SCCR), 3 Contactor Bypass - Main Fusing & Disconnect (100kA SCCR)
ENI/RFI Control:Integrated filter designed to meet EN61800-3
Harmonic Suppression:Dual DC-link chokes (Equivalent: 5% AC line reactor), Supporting IEEE 519-1992 requirements
Cooling:Fan-cooled through back channel
Ambient Temperature:-10°C to 45°C up to 1000 meters above sea level (-14°F to 113°F up to 3300 feet above sea level)

Control Connections

Analog input (follower signal):2; selectable voltage or current, direct and inverse acting
Digital inputs (programmable):6 (2 can be used as digital outputs)
Analog outputs (programmable):1; 0/4 to 20 mA
Relay outputs (programmable):2 standard Form C 240 V AC, 2 A; 1 or 3 additional optional
Auxiliary voltage:+24 V DC, maximum 200 mA
Communication port:1 RS485, 1 USB

PDF preview unavailable. Download the PDF instead.

301-2768-A SCI1209-1760-1.5 TEFC 012720 Adobe PDF Library 15.0 Adobe InDesign 15.0 (Macintosh)

Related Documents

Preview Taco SR502/503/504/506-5 Switching Relay Instruction Sheet
Comprehensive instruction sheet for Taco's SR502, SR503, SR504, and SR506-5 switching relays, covering installation, operation, wiring, troubleshooting, and specifications for HVAC zone control systems.
Preview Taco 007e ECM High-Efficiency Circulator Pump: Features, Specifications, and Applications
Comprehensive guide to the Taco 007e ECM High-Efficiency Circulator pump, detailing its advanced features, technical specifications, materials, installation applications for hydronic and potable water systems, and performance characteristics.
Preview Taco 1600 Series In-Line Pumps: Reliable & Efficient Water Circulation
Discover the Taco 1600 Series In-Line Pumps, engineered for ultimate reliability, ease of installation, and quiet performance in heating, air conditioning, pressure boosting, and water supply applications. View detailed features, specifications, and dimensions.
Preview Taco SR501-4 Switching Relay Instruction Sheet and Wiring Guide
Detailed instruction sheet for the Taco SR501-4 Switching Relay, covering features, operation, wiring diagrams, specifications, troubleshooting, and warranty information for HVAC professionals.
Preview Taco FI Series End Suction, Base Mounted Pumps - Product Information and Repair Parts
Comprehensive guide to Taco FI Series end suction, base-mounted pumps, including performance curves, features, and detailed repair parts lists for frame assemblies and pump heads. Covers various models and frame styles (H, J, L) with part numbers and specifications.
Preview Taco ZVC406-5 Zone Valve Control: Installation and Operation Manual
Comprehensive guide for the Taco ZVC406-5 Zone Valve Control, covering installation, operation, wiring, specifications, troubleshooting, and warranty information. Learn how to optimize heating system comfort and efficiency.
Preview Taco ACT/ACTF Air Separator Installation, Operation & Maintenance Manual
Comprehensive guide for installing, operating, and maintaining Taco ACT/ACTF Air Separators. Covers system types, maintenance procedures, safety warnings, and typical piping diagrams for hydronic heating and cooling systems.
Preview TACO Zone Control Product Information and Wiring Guide
Comprehensive overview of TACO zone control products, including switching relays, zone valve controls, and add-on power controls, with detailed product information, specifications, and wiring diagrams for HVAC systems.