ZONE CONTROLS WIRE GUIDE 3/08

TACO Zone Control Product Information - DCNE

Switching Relays. Product No. Description. SR501-4. 1 Zone Switching Relay. SR501-HC-4. 1 or 2 Zone Switching Relay, High Current Capacity. SR501-OR-4.

ZVC404-EXP Zone Valve Control Connected to a MOD–CON Boiler ... 2 WIRE. ZONE VALVE. (NO END SWITCH). MUST USE JUMPER. TACO. 3 WIRE. ZONE VALVE.

PDF preview unavailable. Download the PDF instead.

Other - TacoComfortSolutions 00277 1 50 51 99 104 106 OTHER1
TACO Zone Control Product Information

Switching Relays Product No. SR501-4 SR501-HC-4 SR501-OR-4 SR502-4 SR503-4 SR504-4 SR506-4

Description 1 Zone Switching Relay 1 or 2 Zone Switching Relay, High Current Capacity 1 Zone Switching Relay with Outdoor Reset 2 Zone Switching Relay with Priority 3 Zone Switching Relay with Priority 4 Zone Switching Relay with Priority 6 Zone Switching Relay with Priority

Expandable Switching Relays ­ Expandable to 120 Zones (20 Zoning Panels)

Product No.

Description

SR501-EXP-4

1 Zone Switching Relay

SR503-EXP-4

3 Zone Switching Relay with Priority

SR504-EXP-4

4 Zone Switching Relay with Priority

SR506-EXP-4

6 Zone Switching Relay with Priority

Zone Valve Controls Product No. ZVC403-4 ZVC404-4 ZVC405-4 ZVC406-4

Description 3 Zone Valve Control with Priority 4 Zone Valve Control with Priority 5 Zone Valve Control with Priority 6 Zone Valve Control with Priority

Expandable Zone Valve Controls ­ Expandable to 120 Zones (20 Zoning Panels)

Product No.

Description

ZVC404-EXP-4

4 Zone Valve Control with Priority

ZVC406-EXP-4

6 Zone Valve Control with Priority

Add-On Power Controls (For use with all -EXP controls)

Product No.

Description

PC700

Boiler Reset Control

PC702

2-Stage Boiler Reset Control

PC705

Variable Speed Pump Injection Mixing Control

Fan Controls Product No. HAFC201-4

Description Hydro Air Fan Control with Optional Time Delays

Do it once. Do it right.

SR504-EXP Switching Relay Connected to a MOD­CON Boiler

MOD-CON BOILER

SPACE HEATING PUMP OUTPUT

DHW DEMAND

SPACE HEATER DEMAND

DHW PUMP OUTPUT
(NOT USED)

POWER CONTROLS

SLAVE PRIORITY ON

RESET

PRIMARY PUMP ON

POST PURGE ON

PRIORITY PROTECT ON

PUMP EXERCISE ON

30 SEC/2 WK

LOW LIMIT (ZC) ON

SR 504-EXP-4

THERMOSTATS

INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
NOTE 1: Terminals C are for optional 24V thermostat COMMON connections.

MASTER OFF NORMAL OFF OFF OFF OFF 4 MIN/24 HOUR OFF

X X X X A B C R WC R WC R WC

MAIN PRIORITY EXPANSION ZONE 1 ZONE 2 ZONE 3

END SWITCH

THERMOSTATS (24 VAC)

ACCESSORY PORT

FOUR ZONE EXPANDABLE SWITCHING RELAY

R WC 1 2
ZONE 4 NET PRIORITY
LED INDICATORS
POWER
ZONE 1

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

ZONE 2 ZONE 3

ZONE 4

120 VAC 120 VAC CIRCULATORS PRIORITY N/C INPUT ZC ZR PRIMARY ZONE1 ZONE2 ZONE3 ZONE4 ZONE4 120 VAC
H H N H N H NH NH NH NH N H

PRIMARY SYSTEM CIRCULATOR (OPTIONAL)

H
120 VAC INPUT
N

ZVC404-EXP Zone Valve Control Connected to a MOD­CON Boiler

SPACE HEATING PUMP OUTPUT

MOD-CON BOILER
WHITE 120 VAC INPUT
BLACK
WHITE 120 VAC INPUT
BLACK
NH
120 VAC INPUT
50

FACTORY INSTALLED TRANSFORMER

FACTORY INSTALLED TRANSFORMER

DHW DEMAND

Powered from Transformer A

Powered from Transformer B

SPACE HEATER DEMAND
DHW PUMP OUTPUT
(NOT USED)

THERMOSTATS (24 VAC)

INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
NOTE 1: Terminals C are for optional 24V thermostat COMMON connections.

A 24 VAC B 24 VAC

POWER IN 24 VAC

FUSE 5 AMP
FUSE 5 AMP

POWER CONTROLS

X X X X A B C R WC R WC R WC R WC 1 2

MAIN PRIORITY EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 NET

END SWITCH

THERMOSTATS (24 VAC) PRIORITY

LED

ACCESSORY PORT

SLAVE PRIORITY ON
RESET

ZVC 404-EXP-4

INDICATORS

MASTER OFF

FOUR ZONE EXPANDABLE POWER

NORMAL ZONE VALVE CONTROL T STAT 1

VALVE 1

POST PURGE ON

OFF

PRIORITY PROTECTION ON

OFF

T STAT 2

VALVE 2

PUMP EXERCISE ON 30 SEC/2 WK

OFF 4 MIN/24 HOUR

T STAT 3

VALVE 3

T STAT 4

VALVE 4

PUMP END SWITCH

ZONE 4 PUMP END SWITCH

X X N/O COM N/C

24 VAC ZONE VALVES

PRIORITY

ZONE 1 ZONE 2 ZONE 3 ZONE 4 1234 1234 1234 1234

DRY CONTACTS
SPACE HEATING PUMP

2 WIRE ZONE VALVE (NO END SWITCH) MUST USE JUMPER

JUMPER 3 & 4

MOTOR END

1

SWITCH

2

3

TACO 3 WIRE ZONE VALVE

4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)

JUMPER 3 & 4
PRIORITY ZONE

SEE NOTE 2

NOTE 2: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.

Powered from Transformer A

Powered from Transformer B

TEKMAR Communication Thermostat (TN4) Connected to SR504-EXP Switching Relay

BOILER

TO: "TT" ON BOILER

TO: "TT" ON BOILER WITH DHW "TT" INPUT

R W C tn4

R W C tn4

R W C tn4

R W C tn4

POWER CONTROLS

SLAVE PRIORITY ON

RESET

PRIMARY PUMP ON

POST PURGE ON

PRIORITY PROTECT ON

PUMP EXERCISE ON

30 SEC/2 WK

LOW LIMIT (ZC) ON

SR 504-EXP-4

MASTER OFF NORMAL OFF OFF OFF OFF 4 MIN/24 HOUR OFF

X X X X A B C R WC R WC R WC

MAIN PRIORITY EXPANSION ZONE 1 ZONE 2 ZONE 3

END SWITCH

THERMOSTATS (24 VAC)

ACCESSORY PORT

FOUR ZONE EXPANDABLE SWITCHING RELAY

R WC 1 2
ZONE 4 NET PRIORITY
LED INDICATORS
POWER
ZONE 1

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

ZONE 2 ZONE 3

ZONE 4

120 VAC 120 VAC CIRCULATORS PRIORITY N/C INPUT ZC ZR PRIMARY ZONE1 ZONE2 ZONE3 ZONE4 ZONE4 120 VAC
H H N H N H NH NH NH NH N H

PRIMARY CIRCULATOR (OPTIONAL)

H
120 VAC
N INPUT

tn4 C R
TEKMAR USER SWITCH (OPTIONAL)

51

Instruction Sheet

SR503-EXP, SR504-EXP & SR506-EXP Switching Relay

Operation: When any thermostat calls for heat, the appropriate circulating pump is energized and the isolated end switch (X and X) will start the boiler.

Priority Operation: When the priority dip switch is set to ON and the priority zone is actuated, all other zones will stop operation until priority zone is satisfied. When not switched to priority, all zones will operate independently.

Mode Operation: When the dip switch is set to NORMAL, the end switch relay will be energized if any zone is in operation. When the switch is set to RESET, the end switch relay will only be energized if the priority zone is in operation, or through the operation of a plug-in reset control.

Primary Pump Operation: When the dip switch is set to OFF, the primary circulating pump output will energize when any zone calls for heat, except the priority zone. When the dip switch is set to ON, the primary circulating pump output will energize when any zone calls for heat.

Post Purge Operation: When the dip switch is set to ON, the priority zone output will stay energized for 2 minutes after its thermostat or aquastat is satisfied, but not operate the boiler.

Priority Protection Operation: When the dip switch is set to ON, and if the priority zone calls continuously for more than one hour, power is returned to all the other zones, allowing each zone to function independently. Once the priority zone is satisfied, the control's auto-reset is activated and the priority zone is again allowed to have priority for up to one hour starting from when it calls next.

Pump Exercise Operation: When the dip switch is set to ON, the solid state timer cycles all the circulating pumps that are attached to the Expandable Switching Relay at the selected time interval. The time interval can be set for the pumps to run for either 30 seconds every 2 weeks or for 4 minutes every 24 hours.

Low Limit (ZC) Operation: When the dip switch is set to ON and the boiler drops below the set low limit (terminal ZC connected to boiler), all zone circulating pumps will stop. When the boiler rises above the set low limit, the zone circulating pumps are allowed to operate.

End Switches (Dry Contacts): The main end switch closes when any zone thermostat calls for heat and the mode switch is set to NORMAL. The main end switch also closes when the mode switch is set to RESET and a PC Series boiler reset power control is calling for heat. The priority end switch closes only when the priority zone thermostat or aquastat is calling for heat.

Expansion Connections: Set the expansion switch to MASTER on the switching relay that has the designated priority zone or is utilizing the PC Series plug-in option. Set all other daisy chained controls to SLAVE. Using thermostat wire (18-22 gauge) connect between terminals A, B, C on the master control to the corresponding A, B, C on the SLAVE control(s). Controls may be daisy chained up to 20 zoning panels using any combination of -EXP controls (120 zones if all are 6 zone panels).

Thermostat Input (24 vac):

R Hot side of transformer. Connect to R on thermostat. W Switched R signal from thermostat. Connect to W on thermostat. C Common side of transformer. Connect to COM on
thermostat (optional). NET Network terminals 1 & 2 are tied together for wiring convenience when using communicating style thermostats (optional).

120 VAC Connections (N is Neutral, H is Hot):

Power Input Primary Zone 1-5 Priority Zone 6 N/C Zone 6

Connect 120 Volt AC power Primary Pump (optional) Circulator Zones Priority Zone (if enabled) or Zone 6 Normally closed terminals for the Priority Zone. WIll deactivate on a Priority Zone call.

Cold Start Boiler Application
TO: "TT" ON BOILER

TO: "TT" ON BOILER WITH DHW "TT" INPUT

THERMOSTATS

POWER CONTROLS

SLAVE PRIORITY ON

RESET

PRIMARY PUMP ON

POST PURGE ON

PRIORITY PROTECT ON

PUMP EXERCISE ON

30 SEC/2 WK

LOW LIMIT (ZC) ON

MASTER

OFF
NORMAL X X X X A B C R W C R W C R W C R W C R W C R W C 1 2

OFF

MAIN PRIORITY EXPANSION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 NET

OFF

END SWITCH

THERMOSTATS (24 VAC)

PRIORITY

OFF

OFF 4 MIN/24 HOUR OFF

ACCESSORY PORT

SIX ZONE EXPANDABLE SWITCHING RELAY

LED INDICATORS
POWER

ZONE 1

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

FUSE 6 AMP

ZONE 2 ZONE 3

ZONE 4

120 VAC

120 VAC CIRCULATORS

PRIORITY N/C INPUT

ZC ZR PRIMARY ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 ZONE6 120 VAC

H H N H N H NH NH NH NH NH NH N H

ZONE 5 ZONE 6
SR 506-EXP-4

PRIMARY CIRCULATOR (OPTIONAL)
Dip Switch Settings:
SLAVE ZONE PRIORITY ON
RESET PRIMARY PUMP FUNCTION ON
POST PURGE ON PRIORITY PROTECTION ON
PUMP EXERCISE ON 30 SEC/2 WK
LOW LIMIT (ZC) ON

120 VAC INPUT
MASTER OFF NORMAL OFF OFF OFF OFF 4 MIN/24 HOUR OFF

External Diagnostics: Externally visible lights show full functionality of the switching relay. The green light should always be on, indicating that power is connected. When the thermostat calls for heat, both the appropriate circulator and red indicating light are energized.

For more wiring diagrams, visit www.taco-hvac.com.

Specifications:

PRODUCT NUMBER

NUMBER OF ZONES

INPUT VOLTAGE

MAXIMUM COMBINED LOAD

TYPE 1 ENCLOSURE WIDTH HEIGHT DEPTH

SR506-EXP-4 6 with Priority 120/60/1 VAC

20 amps

121/4"

8"

3"

All circulator relay connections, including ZC/ZR, are rated 1/3 hp (6 FLA, 36 LRA) at 120 VAC. End switch connections are rated 24 VAC, 1 amp.

All thermostat connections supply a 24 VAC class 2 output.

Features:
Front External Indicator Lights Ideal for Retrofitting Primary Circulator Output Simplified Wiring Plug-In Power Controls Sealed Relays Compact Design Fuse Protected 100% Factory Tested Two Isolated End Switches

Expandable to 20 Zoning Panels (120 zones if all are 6 zone panels)
Contractor Friendly PC Board Layout Universal Thermostat Compatibility UL Approved 24 volt Power Input or Output
Terminal Extended 3 Year Warranty Made in the USA

WARNING: Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only. 120 VAC wiring must have a minimum temperature rating of 75°C. Failure to follow this instruction can result in personal injury or death and/or property damage. 12-18 gauge wire recommended for 120 VAC connections, 14-22 gauge wire for thermostat connections, and 14-22 gauge wire for 24 VAC source connections.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Do it Once. Do it Right.®
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.
Visit our web site at: http://www.taco-hvac.com

Printed in USA Copyright 2010
TACO, Inc.
99

104

TACO Zone Controls Cross-Reference

TACO

ARGO

SWITCHING RELAYS
1 Zone Switching Relay (DPDT) 1 Zone Switching Relay 1 Zone Switching Relay with Outdoor Reset 2 Zone Switching Relay with Priority 3 Zone Switching Relay with Priority 4 Zone Switching Relay with Priority 6 Zone Switching Relay with Priority
EXPANDABLE SWITCHING RELAYS
1 Zone Switching Relay with Priority 3 Zone Switching Relay with Priority 4 Zone Switching Relay with Priority 6 Zone Switching Relay with Priority
ZONE VALVE CONTROLS
3 Zone Valve Control with Priority 4 Zone Valve Control with Priority 5 Zone Valve Control with Priority 6 Zone Valve Control with Priority
EXPANDABLE ZONE VALVE CONTROLS
4 Zone Valve Control with Priority 6 Zone Valve Control with Priority

SR501 SR501-HC SR501-OR SR502 SR503 SR504 SR506

AR822II
AR-861-2II (3) AR-861-3II (3)

SR501-EXP SR503-EXP SR504-EXP SR506-EXP

ARM-3P (5,6) ARM-4P (5,6) ARM-6P (5,6)

ZVC403 (7) ZVC404 (7) ZVC405 (7) ZVC406 (7)

AZ-3 AZ-4P AZ-5 AZ-6P

ZVC404-EXP ZVC406-EXP

ERIE

HONEYWELL

SR100
SR201 SR301 SR601 R601 (4)

RA89A (2), RA845A (1), RA832A (1), R8845U, RA889A

AQ25042B (9)

VL500 (8) VL500 (8)
AQ25044B (9)

TACO Zone Control Product Information

Switching Relays Product No. SR501-4 SR501-HC-4 SR501-OR-4 SR502-4 SR503-4 SR504-4 SR506-4

Description 1 Zone Switching Relay 1 or 2 Zone Switching Relay, High Current Capacity 1 Zone Switching Relay with Outdoor Reset 2 Zone Switching Relay with Priority 3 Zone Switching Relay with Priority 4 Zone Switching Relay with Priority 6 Zone Switching Relay with Priority

Expandable Switching Relays ­ Expandable to 120 Zones (20 Zoning Panels)

Product No.

Description

SR501-EXP-4

1 Zone Switching Relay

SR503-EXP-4

3 Zone Switching Relay with Priority

SR504-EXP-4

4 Zone Switching Relay with Priority

SR506-EXP-4

6 Zone Switching Relay with Priority

Zone Valve Controls Product No. ZVC403-4 ZVC404-4 ZVC405-4 ZVC406-4

Description 3 Zone Valve Control with Priority 4 Zone Valve Control with Priority 5 Zone Valve Control with Priority 6 Zone Valve Control with Priority

Expandable Zone Valve Controls ­ Expandable to 120 Zones (20 Zoning Panels)

Product No.

Description

ZVC404-EXP-4

4 Zone Valve Control with Priority

ZVC406-EXP-4

6 Zone Valve Control with Priority

Add-On Power Controls (For use with all -EXP controls)

Product No.

Description

PC700

Boiler Reset Control

PC702

2-Stage Boiler Reset Control

PC705

Variable Speed Pump Injection Mixing Control

Fan Controls Product No. HAFC201-4

Description Hydro Air Fan Control with Optional Time Delays

CONTROLS MADE EASY.®
TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436.
Visit our web site at: http://www.taco-hvac.com

Printed in USA Copyright 2013