User Guide for HEATCRAFT models including: HCR23001_intelliGen_QuickStartGuide_071323, 25011701, 29326101, 29326201, 29326401, 29326501, 29326601, 25011701 Universal Field Mount Refrigeration Controller, Universal Field Mount Refrigeration Controller, Field Mount Refrigeration Controller, Refrigeration Controller, Controller

HCR23001 intelliGen QuickStartGuide 071323

assets.heatcraftrpd.com

Quick Start Guide

Quick Start Guide Universal Field-Mount Refrigeration Controller intelliGen™ Field Mount (iFM) Kit for Unit Coolers The intelliGen™ Field Mount Kit is designed to install in the field for

iFM Kit QuickStart

intelliGen™ refrigeration control | The Hub


File Info : application/pdf, 3 Pages, 8.09MB

PDF preview unavailable. Download the PDF instead.

intelliGen-iFM-Kit-QuickStart-2023
Quick Start Guide
Universal Field-Mount Refrigeration Controller

JULY 2023 PART NO. 25011701

intelliGenTM Field Mount (iFM) Kit for
Unit Coolers
The intelliGenTM Field Mount Kit is designed to install in the field for new unit coolers without factory mounted controls or retrofit of existing unit coolers with mechanical control to electronic control. The intelliGen control can be remote mounted away from the unit cooler at a convenient location for easy access. It is pre-assembled in a IP65 rated housing for both indoor and outdoor applications.
Components Included
The iFM kit comes with the intelliGen controller, 3 temperature sensors, 1 pressure transducer with wire harness, 1 terminal board and mounting accessories. The temperature sensors and pressure transducer harness are 25 feet in length. Other wire lengths are available as optional kit in separate part numbers.
Components Not Included
Individual system dependent components are not included in the kit but required for each installation. These components include the 24VAC control power transformer, the electronic expansion valve (EXV), the field wires for control power, fan motors, defrost heaters and solenoid valve.
Field wire runs between the intelliGen controller and the unit cooler should be in conduits and have to meet local building and electric code requirements. Conduit fittings are needed for the conduit runs. Please conduct a site survey and review your local codes for detail requirements prior to installation.

U.S. CUSTOMER SERVICE
NORMAL BUSINESS HOURS 8:00 AM - 8:00 PM EDT 800.537.7775
heatcraft.com/intelligen/support SESweb@heatcraftrpd.com

AFTER HOURS
After 5:00 PM EDT, weekends and holidays 877.482.7238

Additional system dependent parts are required for proper iFM installation. Be sure you have compatible version of the following parts for your system.

Part #

Electric Expansion Valves (EXV) Evaporator Condition

Connection Size

Capacity1 (BTUH) at 20°F SST2

Capacity1 (BTUH) at -20°F SST2

29326101 29326201 29326401 29326501 29326601

3/8" x 3/8" 3/8" x 3/8" 5/8" x 5/8" 7/8" x 1-3/8" 7/8" x 1-3/8"

12,000 52,000 78,000 182,000 269,000

11,000 48,000 71,000 167,000 246,000

1. Capacities are based on the specific condition listed for R-448A, for reference only. For other conditions and refrigerants, use the QR code link below for document to select proper valve size.
2. SST - Saturated Suction Temperature

Part # 22529601 22529602 22529603 22529701

24V AC Transformer Description 120/24VAC, 40VA 240/24VAC, 40VA 460/24VAC, 40VA 575/24VAC, 40VA

Part # 22699901 22699902 22699903 59755302 59755301

Power Harnesses and Sensor Kits Description 40ft harness for power, fan, defrost heater 25ft harness for power, fan, defrost heater 15ft harness for power, fan, defrost heater 15ft sensor kit 40ft sensor kit

Recommended Tools for Installation

Power drill & drill bits 5/16" nut driver 7/16" & 5/8" wrenches Phillips screwdriver

Precision slotted screwdriver Slotted screwdriver 5/32" Hex (Allen) key Wire stripper/crimper

intelliGenTM Field Mount Kit

Components In Unit Cooler Installation

PILOT

THIS GUIDE INCLUDES YOUR iFM INSTALATION TEMPLATE. Hold or tape flattened Quick Start Guide to the wall and use light blue guideline to mark your drill holes
prior to installation. Install upper left PILOT screw first when mounting.

TOP WIRING PORTS
KNOCKOUTS AVAILABLE

DISTRIBUTOR AND CONTROL END

ROOM TEMPERATURE SENSOR

ROOM TEMPERATURE SENSOR BRACKET

7 in

13.66 in

TERMINAL BOARD

SUCTION TEMPERATURE SENSOR

SUCTION TEMPERATURE SENSOR TUBE

BOTTOM WIRING PORTS
KNOCKOUTS AVAILABLE
8.60 in
1
intelliGen CONTROLLER IN IP65
2 RATED PROTECTIVE HOUSING
13.66 x 9.50 x 5.42 in)
3

PRESSURE TRANSDUCER PRESSURE

HARNESS

TRANSDUCER

COIL TEMPERATURE SENSOR

COIL TEMPERATURE SENSOR BRACKET

Remote Case Installation

Locate Remote iFM Mount Location
1 Identify a flat surface to mount the iFM kit 2 Prepare the mounting location and mark screw holes

Conduits & Wires Routing to Unit Cooler

1 Determine conduit routing based on application need

2

Determine the knockouts on the iFM housing for conduit routing

3

Determine the conduit fittings for connection to the iFM housing and the unit cooler.

4 Run wires through the conduits and fittings.

5 Connect fittings to the conduits

Note: Low voltage and sensor wires are required to be in separate conduit from the high voltage wires. Use wire sheathing provided to add additional protection.

Mount iFM Kit
1 Mount the iFM housing to the marked screw hole locations using #10 screws (provided)
2 Pull the wires through the knockouts on the iFM housing
3 Tighten the conduit fittings to the iFM housing

Room Temperature Sensor - Yellow
Pressure Transducer
Suction Temperature Sensor - Blue

EXV
Coil Temperature Sensor - green

Note: Electronic Expansion Valve (EXV) size varies by system capacity. Check system specification for proper valve size. Field installer to provide.

Suction Temperature Sensor
(Blue Wire, Included)

1

Braze the metal Suction Temp Sensor Tube onto the suction line

2 Insert the Temp Sensor into the metal tube

3 Wrap the Temp Sensor and the metal tube with Cork tapes

4 Secure the Temp Sensor with cable ties

ELECTRICAL END

Terminal Board 24VAC Transformer

!

Electronic Expansion Valve
(EXV, Not Included)

1

Field installer to provide an EXV matches the system capacity

2 Remove the EXV body from its power head

3

Braze the EXV body to connect between the distributor connection and the liquid line stub

4

Insert the power head back to the valve body and then connect the power head with harness

Coil Temperature Sensor

(Green Wire, Included)

1

Attach the Coil Temp Sensor into the channel of the mounting bracket

2

Screw tight the sensor bracket onto the coil end plate with the self-drilling screws provided

Room Temperature Sensor
(Yellow Wire, Included)

1

Drill two 1/4" holes, 1 1/4" apart at the return air area of the unit cooler

2 Insert the Room Temp Sensor bracket into the drilled holes

3 Secure the Temp Sensor to the bracket with cable ties

Pressure Transducer
(Included)
1 Locate the Schrader valve on the suction line

2 Screw the Pressure Transducer onto the Schrader valve

3

Plug in the pressure transducer harness. Make sure the harness clip is securely latched

Terminal Board
(Included)

1

Mount the terminal board to the electrical end of the unit cooler

2

Connect power wires (system power, control power, motor fans, defrost heaters and solenoid valve wires as needed)

Power Transformer
(Not Included)

1

Field installer to provide a step down transformer from system voltage to 24VAC for control power

2

Mount the transformer to the electrical end of the unit cooler

Note: 24VAC transformer varies by system input voltage. Check system specification for proper transformer primary voltage. Field installer to provide.

intelliGenTM Refrigerator Controller

Connecting Wires to the intelliGenTM Control Board

Grounded Mounting Screw
EXV Alarm Contacts
LLSV Relay

iRC-UI Connection

Chasis Ground

24V Power Supply

Door Switch
Evap Communication Connection

Grounded Mounting Screw Condensing Unit Connection Product Load Switch

Evap 2 Speed Fans Evap Fans Relay

USB Data Port

Suction Temp

Suction Pressure

Spare I/O Aux Temp

Defrost Heater Relay

Clock Battery

Room Coil Temp Temp

Grounded Mounting Screw

Get to Know the intelliGenTM Refrigeration Controller

LED Status Bar

LED Status Light Bar: Indicates the current status of all specific evaporators on the system (see below)
OLED Screen: Displays temperature, parameters and other content.
Menu Buttons: Back button to go back to Previous Menu. Home button to go back to Main Menu. Favorites button to go to your Favorites.
Knob / Enter Button: Rotate the wheel left and right to navigate between Menu Options. Press the wheel to ENTER.

Green Static
The System or EV does not have any anomalies/issues.

Red Static The System or EV has an Alarm.
Red Flashing The EV Unit where the Alarm originated.

Yellow Static The System or EV has an Error.
Yellow Flashing The EV Unit where the Error originated.

White Flashing
The EV Unit is being identified.

No LED On
The EV Unit is currently powered off or in service mode.

intelliGenTM Installation Resources & Operation Manual:
To find all intelliGen resources, including installation & operation manuals, technical bulletins, brochures, maintenance, troubleshooting information and more, simply scan the QR code or use the link below.

www.intelliGencontrols.com/resources



References

Adobe PDF library 17.00 Adobe Illustrator(R) 24.0