Thermo™ Expansion Valve Series TIH: Installation and Operation Guide

Emerson Climate Technologies GmbH

Am Borsigturm 31 | 13507 Berlin | Germany

General Information

The TIH series of Thermo™-Expansion Valves are designed for air conditioning, heat pumps, and commercial refrigeration applications. The TIH is ideal for those applications requiring hermetic/compact size combined with stable and accurate control over wide load and evaporating temperature ranges.

Safety Instructions

Mounting Location

Valves may be installed in any position but should be located as close as possible to the distributor or evaporator inlet. Fig. 1 shows the heat pump application.

Brazing

(Fig. 2) Perform and consider the brazing joint as per EN 14324. Before and after the brazing clean tubing and brazing joints. To avoid oxidization, it is advised to purge the system with an inert gas such as nitrogen while brazing. Do not exceed the max. body temperature of 120°C!

Installation

Warning: Do not bend the capillary tube at the interface to the head of the valve. Allowed: distance N (10 mm) and radius R (5 mm).

Fig. 3: Securely fasten the bulb with straps provided. Insulate the bulb with a suitable material. The location of the bulb on the suction line is dependent on the size of the suction line (see Fig. 4). Be sure that the external equalizer line cannot siphon oil from the suction line. The expansion valve must be protected against all contaminants. Install a filter drier before the valve. Install a sight glass before the valve.

Pressure Test

After completion of installation, a pressure test must be carried out as follows:

Warning: Failure to do so could result in loss of refrigerant and personal injury. The pressure test must be conducted by skilled persons with due respect regarding the danger related to pressure.

Leakage Test

Conduct a tightness test according to EN 378-2 with appropriate equipment and method to identify leakages of external joints.

Operation

Check for leaks; sufficient refrigerant charge and be sure no flash gas is present before attempting to check the valve operation.

Proper Operation of Charges

The maximum bulb temperature is limited to:

Charge Code Charge Max. bulb Temperature
Z1/Z3, M1/M3, N1/N3, C1/C3 MOP +120°C
M0/M2, C0/C2 liquid +100°C
N0/N2, B0/B2 liquid +80°C

Warning: Valves with gas charge feature MOP function and operate properly only if the temperature at the bulb is below the temperature at the head of the valve and at the capillary tube (see Fig. 5). If the valve head becomes colder than the bulb, malfunction of the expansion valve occurs (i.e., erratic low pressure or excessive superheat).

Factory Settings

The table below provides the factory setting position of the superheat adjusting stem and shows the number of turns clockwise when adjusting the stem fully open counterclockwise.

Charge Code Number of turns (360°) Charge Code Number of turns (360°)
Z1/Z3 +5.5 - -
M1/M3 +2.5 M0/M2 +2.5
N1/N3 +5.5 N0/N2 +4.5
- B0/B1 +3.5
C1/C3 +1.5 C0/C2 +3

TIH in Systems with Nonstandard Refrigerants

The following refrigerants can be used with standard available charges when factory setting to be readjusted for optimum superheat level. The readjustment depends on operating evaporating temperature and it is as guideline as follows:

Refrigerant Charge code Evaporating temperature (°C)
+5 0 -10 -20 -30
Number of turns
R32 Z1 -1 0 0 0 -
R452B Z1 +2.5 +2.5 +2.5 +2.5 -
R454B Z1 +3 +3 +3 +3 -
R450A M0 +2.5 +2 +1 +0.5 -
R454C N1 0 0 0 0 -
R454C N0 +0.5 +0.5 0 -0.5 -
R1234YF C1 0 0 0 +0.5 -
R1234YF C0 0 0 0 +1 -
R454A B0 -2 -2 -1 -0.5 0
R455A B0 +1.5 +1.5 +1.5 +1.5 +1.5

Note: Change of static superheat will shift MOP point in reverse direction. Note2: TIH for R134a with MOP (M1) shall not be used for R450A.

Warning: There are max. 12 turns on the adjustment stem (from left stop to right stop). When the stop is reached, any further turning will damage the valve.

Superheat Adjustment

If the superheat must be adjusted for the application proceeds as follows:

  1. Remove the seal cap from the bottom of the valve.
  2. Turn the adjustment screw clockwise to increase the superheat and counterclockwise to decrease the superheat.

Changes in Superheat (K) per stem turn depending on evaporating temperature and refrigerant:

Refrigerant Evaporating temperature (°C)
-30 -20 -10 0 +5
R410A 1.3 1.0 0.8 0.6 0.5
R32 1.3 1.0 0.7 0.6 0.5
R452B 1.4 1.1 0.8 0.6 0.6
R454B 1.5 1.1 0.8 0.6 0.6
R407C 2.3 1.6 1.2 0.9 0.8
R448A 2.0 1.5 1.1 0.9 0.8
R449A 2.0 1.5 1.1 0.9 0.8
R134a - 2.5 1.8 1.4 1.2
R513A - 2.3 1.7 1.3 1.2

Note: Change of static superheat will shift MOP point in reverse direction.

Note2: TIH for R134a with MOP (M1) shall not be used for R450A.

Technical Data

Max. working pressure PS 46 bar
Factory test pressure PT 50.6 bar
Medium temperature TS -40…+70°C
Dimensions Fig. 8

Service / Maintenance

Defective TIH must be replaced. Repair is not possible.

Models: Thermo Expansion Valve Series TIH

File Info : application/pdf, 7 Pages, 2.06MB

PDF preview unavailable. Download the PDF instead.

thermo--expansion-valve-series-tih-operating-instructions-en-gb-6375270

References

Adobe PDF Library 20.6.66

Related Documents

Preview Emerson Suction Accumulators A-Series: Operating Instructions
Comprehensive operating instructions for Emerson's Suction Accumulators A-Series, covering general information, safety, installation, operation, maintenance, technical data, and classification for various refrigerants.
Preview Emerson TXV Connect Kits: Thermostatic Expansion Valves for HVACR
Emerson TXV Connect Kits provide a universal solution for residential air conditioning and heat pump upgrades, offering advanced thermostatic expansion valves and adapters for efficient installation and improved performance. Key benefits include time savings, cost-effectiveness, ease of installation, and energy efficiency.
Preview Copeland Scroll™ Variable Speed Compressors YHV0182P* to YHV0382P* Application Guidelines
Comprehensive application guidelines for Emerson's Copeland Scroll™ Variable Speed Compressors (YHV0182P* to YHV0382P*), detailing safety, product description, installation, electrical connections, start-up, operation, maintenance, repair, and troubleshooting procedures. Covers technical specifications, operating envelopes, and best practices for system integration.
Preview Emerson Ogólny Katalog Produktów 2018: Rozwiązania HVACR
Przegląd produktów Emerson, Copeland i Alco Controls z 2018 roku, obejmujący sprężarki spiralne, tłokowe, agregaty skraplające i sterowniki dla branży HVACR. Zawiera dane techniczne i specyfikacje.
Preview Copeland Reciprocating Compressors - Emerson Commercial & Residential Solutions
Comprehensive guide to Copeland reciprocating compressors from Emerson, detailing product range, nomenclature, performance specifications, operating envelopes, dimensional drawings, wiring diagrams, and system practice for commercial refrigeration applications. Covers R22, R134a, and R404A refrigerants.
Preview Emerson Electronic Valves and Controls: Energy Saving Solutions for Refrigeration & HVAC
Explore Emerson's EX4-EX8 series electronic control valves and EXD controllers for efficient energy management in industrial cooling, air conditioning, and heat pump applications. Discover features, applications, and product specifications.
Preview Emerson KTM Series E01 Process Trunnion Mounted Ball Valve Datasheet
Comprehensive technical datasheet for the Emerson KTM Series E01 Process Trunnion Mounted Ball Valve, detailing features, specifications, dimensions, materials, and selection criteria for industrial process applications in refining, petrochemical, chemical, pulp and paper industries.
Preview Emerson PS1/PS2 Pressure Controls Operating Instructions
Comprehensive operating instructions for Emerson's PS1 and PS2 series pressure controls, covering installation, function, electrical connections, setpoint adjustment, and maintenance for refrigeration and heat pump systems.