Refrigeration Control System User Manual

This manual details the operation and configuration of the refrigeration control system.

Important Notice

The control panel may lock after 15 seconds of inactivity. To unlock, press and hold two buttons simultaneously for 3 seconds. Two beeps indicate the unit is unlocked.

1. Main Display Window

The main display window shows temperature values, menu codes and values, and alarming or error codes. The display flashes in setting mode and remains stable in main display mode. A beep sounds upon power-on, followed by the display of the internal appliance temperature.

2. Indicators and Descriptions

Indicator Status Meaning
❄️ Stable Lighting Refrigerating
Light flashing The compressor is waiting to start
? Stable Lighting Evaporator fan is running.
❄️? Light flashing Delaying time after defrosting
❄️? Stable Lighting Defrosting, 'DEF' is displayed
? Light Flashing Dripping during defrosting; or Delaying when waiting for hot air defrosting
? Light Flashing The door is open or not properly closed.
⚠️ Light Flashing Condense temperature sensor reached the warning value, failure warning
⚙️ Stable Lighting Auxiliary function (customized) started, Auxiliary timer closed (discharge pump manually operated)
? Stable Lighting Wifi turned on
°C Stable Lighting Display current temperature in Celsius degree
°F Stable Lighting Display current temperature in Fahrenheit degree

3. Keys and Functions

Icon Key Function
SET Setting key Enter programming mode, choose a parameter
Increase key Check parameter value, increase the value
Decrease Key Check parameter value, decrease the value
? Manual discharge key Turn on/off the drain pump
? / °C/°F Mute and 'C/'F shift Pause alarm, shift to Celsius or Fahrenheit
❄️ Manual defrost key Start or end the defrosting process
Stand-by key Return to set mode, On/stand-by

4. Main Function of the Keys

Check the Set Temperature

When the control panel is unlocked and displayed, tap the SET key. The screen will flash showing the current set temperature. Tap SET again or wait 6 seconds to return to the cabinet temperature display.

Change the Set Temperature

When unlocked, tap SET softly to display the set temperature. Use the UP (▲) and DOWN (▼) buttons to adjust the desired temperature. Holding either button for over 1 second allows for continuous adjustment. The setting mode exits automatically after 6 seconds of inactivity or upon pressing SET again.

Alarm (Mute and Ring Back)

During an alarm, accompanied by beeping sounds, an error code will appear on the main window. Tap the mute key to silence the alarm. The beep will reoccur if the alarm condition persists. The cycle repeats until the alarm is resolved.

Manual Start/End Defrost Process

Under unlocked status, press and hold the SET key for 3 seconds to initiate manual defrost. To end the defrost process, press and hold the same key for 3 seconds.

Switch Between Celsius/Fahrenheit

Under unlocked status, press and hold the 'C/°F' key for 3 seconds to switch between Celsius and Fahrenheit. The corresponding indicator light will change.

Stand-by and Work Status

Press and hold the power key (⚡) for 3 seconds to switch between stand-by and work modes. In stand-by, only the power key light is red, and all other outputs are closed.

5. Change the Parameter

Menu Search

Unlock the control. Press and hold the SET key until 'PC' is displayed. Press the UP (▲) or DOWN (▼) key until '26' appears, then press SET. Letters like 'r', 'c', 'd', 'F', 'A', 'H' will appear sequentially. Select a letter by pressing SET to confirm. For example, selecting 'r' and pressing SET will display the first parameter code ('rL') under 'temperature and sensor management'. Pressing SET again allows scrolling through all parameters starting with 'r'.

6. Check and Modify Parameter Value

Enter the menu list. Press the SET key repeatedly to find the desired parameter code. After selecting a parameter, press the UP (▲) or DOWN (▼) key to view its current value. Continue pressing UP or DOWN to modify the value. Press SET to confirm, or wait 8 seconds without action for automatic confirmation and exit.

Parameter Table Overview

The following tables list various parameters, their definitions, value ranges, units, and default settings for both refrigerator and freezer modes.

Temperature and Sensor Management Parameters:

Code Definition Minimum Value Maximum Value Unit Default (Refrigerator) Default (Freezer)
rL Lowest temperature can be set -40 / -40 rH °C / °F -5 / 23 -22 / -7
rH Highest temperature can be set rL 120 / 248 °C / °F 10 / 50 -10 / 14
St Control Temperature setting value rL rH °C / °F 1 / 33 -22 / -7
rd Temperature control Hysteresis Error 1 / 1 10 / 18 °C / °F 4 / 5 4 / 5
r1 Cabinet temperature probe compensation -10 / 14 10 / 50 °C / °F 0 / 0 0 / 0
r2 Evaporator probe temperature compensation -10 / 14 10 / 50 °C / °F 0 / 0 0 / 0
r3 Condenser probe temperature compensation -10 / 14 10 / 50 °C / °F 0 / 0 0 / 0
rA Defrost probe enable 0=disable; 1=enable / / 1 1
rB Condenser probe enable 0=disable; 1=enable / / 0 0
r0 Unit of temperature 0=Celsius; 1=Fahrenheit / / 0 0

Evaporator Motor Parameters:

Code Definition Minimum Value Maximum Value Unit Default (Refrigerator) Default (Freezer)
F0 Evaporator motor running mode 0=synchronize with compressor, and when it starts to defrost; 1=always running, and stop when it starts to defrost; 2=start and stop on setting temperature, stop when it starts defrost; 3=synchronize with compressor, run when it starts to defrost; 4=always running even during defrosting. / / 1 0
F1 Evaporator start mode after defrosting 0=on set delay time; 1=on set start temperature / / 1 1
F2 Evaporator motor start delay time after defrost 0 20 min 3 5
F3 Evaporator motor stop temperature -40 / -40 40 / 104 °C / °F 2 2
F4 Evaporator motor start temperature -20 / -4 20 / 68 °C / °F -5 -10

Defrost Parameters:

Code Definition Minimum Value Maximum Value Unit Default (Refrigerator) Default (Freezer)
d0 Defrost type 0=electrical heating defrost; 1=hot air defrost / / 0 0
d1 Interval time between Two defrost process 0 24 hour 4 3
d2 Defrost change rules enable 0=enable; 1=disable / / 0 0
dp The longest time of defrosting 2 60 min 20 20
dt Defrost stop temperature 0 / 32 40 / 104 °C / °F 12 12
dd Delay output time after Defrost start 0 20 min 0 0
dr Dripping time after finish defrosting 0 20 min 2 2
d7 Display delay after finish defrosting 0 20 min 2 2
d8 Cabinet temperature display delay after finish defrosting 0 20 min 15 15

Other Parameters:

Code Definition Minimum Value Maximum Value Unit Default (Refrigerator) Default (Freezer)
H3 Nixie tube temperature display 0=Cabinet temperature r1; 1=defrost probe temperature r2; 2=condenser temperature r3 / / 0 0
H4 Alarm shutdown enable 0=enable; 1=disable; / / 0 0
HH Delay shutdown time after AH alarm is triggered 0 72 hour 36 36
HC Delay shutdown time after AC alarm is triggered 0 72 hour 36 36
Hr Restore factory default settings 0=null; 1=restore factory default setting / / 0 0
HL Enable WIFI communication 0=disable; 1=enable / / 0 0

Fault Codes

Code Description Cause
Err1 Sensor1 fault = cabinet temperature probe Open circuit or short circuit
Err2 Sensor2 fault = defrost probe Open circuit or short circuit
Err3 Sensor3 fault = condenser probe Open circuit or short circuit
Models: 700 Liter, 700 Liter Freezer Stainless Steel ECO, 700 Liter, Freezer Stainless Steel ECO, Stainless Steel ECO, Steel ECO, ECO

PDF preview unavailable. Download the PDF instead.

KSH TSH Manual Thermostat EN Microsoft Word 2016 www.ilovepdf.com

Related Documents

Preview GGM Gastro TKSS600SFN SF60V Exploded View and Parts List
Detailed exploded view and parts list for the GGM Gastro TKSS600SFN SF60V refrigeration unit, including part numbers, names, and quantities for assembly and maintenance.
Preview GGM Gastro Dry-Age Meat Maturing Cabinet with Salt Stones - User Manual
This document provides detailed information on the GGM Gastro Dry-Age Meat Maturing Cabinet, including its features, operation, maintenance, and troubleshooting. Learn about the dry-aging process, the benefits of salt stones, and how to control temperature and humidity for optimal meat maturation.
Preview GGM Gastro KTKF1400D Product Information Sheet
Product information sheet for the GGM Gastro KTF1400D refrigerator, detailing energy efficiency, capacity, climate class, and supplier information.
Preview GGM Gastro PVNR235 Refrigerator Operation Instructions
Comprehensive operation instructions for the GGM Gastro PVNR235 refrigerator, covering general information, structure, handling, setup, usage, maintenance, troubleshooting, and technical specifications. Includes safety guidelines and system principles.
Preview SFF546NR Blast Freezer: Technical Specifications and Parts Manual
Comprehensive technical specifications, dimensions, exploded view, spare parts list, and electrical schema for the GGM Gastro SFF546NR blast freezer.
Preview GGM Gastro TKSBL600 Vertical Cabinet Product Fiche
Product fiche for the GGM Gastro TKSBL600 vertical cabinet, detailing energy efficiency, capacity, and supplier information.
Preview GGM Gastro KTKF1400D Product Information
Product details for the GGM Gastro KTKF1400D vertical cabinet, including energy efficiency, capacity, and supplier information.
Preview GGM Gastro KTKF1400D Refrigerator-Freezer Product Sheet
Product sheet for the GGM Gastro KTKF1400D refrigerator-freezer, detailing energy efficiency, capacity, and manufacturer information.