Zennio RemoteBOX ZSYRBOX
Technical Documentation
Features
- Remote control with Zennio Remote
- Compatibility with ZenVoice through license
- Supports KNX Data Secure
- External 24-29 VDC power supply
- Ethernet connection RJ45 10/100Mbps Base T
- 10 logic functions
- Total data saving on KNX bus failure
- Integrated KNX BCU (TP1-256)
- Dimensions 67 x 90 x 36 mm (2 DIN units)
- DIN rail mounting according to IEC 60715 TH35, with fixing clamp
- Conformity with the CE, RCM directives (marks on the right side)
Figure 1: RemoteBOX
Diagram showing the RemoteBOX with numbered components:
- 1. External Power Supply
- 2. Ethernet connector
- 3. Multifunction reset LED
- 4. Multifunction reset button
- 5. Programming button
- 6. Programming LED
- 7. Synchronization LED
- 8. IP connection LED
- 9. KNX connector
- 10. Without use
- 11. Server connection status LED
Button Descriptions:
- Programming button: Short press to set programming mode. Holding while plugging into the KNX bus enters safe mode. Pressing for 10 seconds in safe mode performs a KNX Secure factory reset.
- Multifunction Reset button: Short press performs a webtools password reset (associated LED flashes yellow).
LED Descriptions:
- Programming LED: Programming mode indicator (red). Blinks red every half second in safe mode. Flashes red during start-up (reset or after KNX bus failure) if not in safe mode.
- Synchronization LED: Shows device is unloaded or desynchronized (red); synchronizing (yellow flashing); synchronized (green).
- IP connection LED: Shows connection to Ethernet with assigned IP address (green) or no connection/unassigned IP address (red).
- Server connection status LED: Shows correct connection with server (green); connection with failures (yellow); no connection (red).
General Specifications
Concept | Description |
---|---|
Type of device | Electric operation control device |
Voltage (typical) | 29 VDC SELV |
Voltage range | 21-31 VDC |
KNX supply voltage (typical) | 29 VDC |
KNX supply maximum consumption | 4.0 mA |
Connection type | Typical TP1 bus connector for 0.8 mm Ø rigid cable |
External power supply voltage | 24-29 VDC |
External power supply maximum consumption | 42 mA (24 VDC) - 35 mA (29 VDC) |
Operation temperature | 0.. +55 °C |
Storage temperature | -20 .. +55 °C |
Operation humidity | 5.. 95% |
Storage humidity | 5..95% |
Complementary characteristics Protection class | Class B |
Operation type | III |
Device action type | Continuous operation |
Electrical stress period | Type 1 |
Degree of protection | IP20, clean environment |
Installation | Independent device to be mounted inside electrical panels with DIN rail (IEC 60715) |
Minimum clearances | Not required |
Response on KNX bus failure | Data saving according to parameterization |
Response on KNX bus restart | Data recovery according to parameterization |
Operation indicator | The programming LED indicates programming mode (red). The synchronization LED shows that the device is unloaded or desynchronized (red); synchronizing (yellow flashing); synchronized (green). The IP connection LED shows that the device is connected to Ethernet and has an IP address assigned (green) or not (red). The server connection status LED shows a correct connection with the server (green); connection with failures (yellow) or without connection (red). In case of firmware update, all LEDs will blink red except the programming LED. |
Weight | 91 g |
Housing material | PC FR VO halogen free / 75 °C (housing) - 125 °C (connectors) |
Maximum consumption in the worst-case scenario (KNX Fan-In model).
External Power Supply and Connections
Concept | Description |
---|---|
Voltage | 24-29 VDC |
Current | 42 mA (24 VDC) - 35 mA (29 VDC) |
Connection method | Screw terminal block (0.5 Nm max.) |
Cable cross-section | 0.5-2.5 mm² (IEC) / 26-12 AWG (UL) |
Pairing Instructions
- From Zennio Remote: Select the device in the Zennio Remote APP and enter the pairing password (from the sticker or a customized one).
- From Webserver tools: Access the remote control tab, click on "New pairing", and the pairing code with a QR will appear.
- Pairing through object: A 1-bit object is sent to generate a pairing code request, and a text string is received with the code or an error message if pairing is not possible.
Attaching RemoteBOX to DIN rail:
Diagram illustrating the process of attaching the RemoteBOX to a DIN rail.
Removing RemoteBOX from DIN rail:
Diagram illustrating the process of removing the RemoteBOX from a DIN rail.
Figure 2: Mounting RemoteBOX on DIN rail
Diagram showing the RemoteBOX mounted on a DIN rail.
Safety Instructions and Additional Notes
- Installation must be performed by qualified professionals according to applicable laws and regulations.
- Do not connect mains voltage or any other external voltage to the KNX bus to avoid risks to the system. Ensure adequate insulation between mains/auxiliary voltage and the KNX bus or other accessory wires.
- Keep the device away from water (including condensation) and do not cover it during use.
- The WEEE logo indicates that the device contains electronic parts and must be disposed of according to instructions at https://www.zennio.com/en/legal/weee-regulation.
- This device contains software subject to specific licenses. Details are available at https://zennio.com/licenses.
For further information, visit www.zennio.com.
Related Documents
![]() |
Zennio Z41, Z41 Lite, Z41 Pro Firmware-Update Anleitung Diese Anleitung beschreibt detailliert die Durchführung von Firmware-Updates für Zennio Z41, Z41 Lite und Z41 Pro Geräte über USB und Ethernet. Enthält Schritt-für-Schritt-Anweisungen und Fehlerbehebung. |
![]() |
Zennio KNX Secure Guide: Enhancing KNX Installation Security A comprehensive guide from Zennio detailing KNX Secure protocols, including KNX Data Secure and KNX IP Secure. Learn about secure commissioning, group communication, IP tunneling, device certificates, factory resets, and essential considerations for robust KNX system security. |
![]() |
Zennio IRSC-Open Manual: Control Your Devices with KNX This manual provides a comprehensive guide to the Zennio IRSC-Open, a KNX system component that allows for the control of infrared-based audio/video devices. Learn about IR transmission, capturing IR codes with the Z38i, configuring commands, and creating macros for advanced automation. |
![]() |
Zennio Smart Home & Building Automation: Touch Panels, Controls, and Actuators Discover Zennio's extensive range of smart home and building automation solutions, featuring advanced touch panels, intuitive room controllers, versatile capacitive switches, video intercom systems, access control, and powerful actuators for lighting, HVAC, and more. Enhance comfort, security, and energy efficiency with Zennio's innovative KNX technology. |
![]() |
Zennio Square TMD-Display ZVI-SQTMDD User Manual User manual for the Zennio Square TMD-Display (ZVI-SQTMDD), a 5-button capacitive touch panel with graphic display for KNX building automation systems, covering features, installation, and configuration. |
![]() |
Zennio Z50, Z70 v2, Z100: Full Color Capacitive Touch Panel User Manual User manual detailing the Zennio Z50, Z70 v2, and Z100 full-color capacitive touch panels. Covers features, installation, configuration, and operation for integrated room control in smart environments. |
![]() |
Zennio KES Plus KNX Energy Meter User Manual - Smart Energy Monitoring Comprehensive user manual for the Zennio KES Plus KNX Energy Meter (ZIO-KESP). Learn about its features for monitoring electrical energy consumption, costs, and CO2 emissions in single and three-phase KNX installations, enabling smart energy savings. |
![]() |
Zennio Webserver Tools User Manual A comprehensive user manual for Zennio's Webserver Tools, detailing features such as server access, device information, license management, intercom functionality, contact management, data logging, screensaver configuration, and network settings. |