USER MANUAL

KNX Secure Guide
CONTENTS
Contents ........................................................................................................................................ 2 Document Updates ....................................................................................................................... 3 1 Introduction ............................................................................................................................ 4 2 Configuration .......................................................................................................................... 5
2.1 KNX Data Secure............................................................................................................... 5 2.1.1 Secure Commissioning............................................................................................... 6 2.1.2 Secure Group Communication .................................................................................. 9
2.2 KNX IP Secure ................................................................................................................. 10 2.2.1 Secure Commissioning............................................................................................. 11
3 Factory Reset ........................................................................................................................ 14 4 Observations......................................................................................................................... 15

https://www.zennio.com

Technical Support: https://support.zennio.com 2

DOCUMENT UPDATES

Version

Changes

b

Added instructions for performing a factory reset.

KNX Secure Guide
Page(s)

https://www.zennio.com

Technical Support: https://support.zennio.com 3

1 INTRODUCTION

KNX Secure Guide

So far, the data transmitted in a KNX automation installation was open and could be read and manipulated by anyone with some knowledge with access to the KNX medium, so that security is guaranteed by preventing access to the KNX bus or to the devices. The new KNX Secure protocols add additional security to the communications in a KNX installation to prevent such kind of attacks.

Devices with KNX secure will be able to communicate securely with ETS and any other secure device, as they will incorporate system for authentication and encryption of the information.

There are two types of KNX security that can be implemented simultaneously in the same installation:
KNX Data Secure: secures the communication within a KNX installation.
KNX IP Secure: for KNX installations with IP communication, secures communication via IP network.

A secure KNX device refers to a device that has the basic capability to enable secure communication, although it is not always required to do so. An unsecured communication on secured KNX devices is equal to communication established between devices without KNX security.

The use of security depends on two significant settings in the ETS project:

Commissioning security: sets whether, during the commissioning, the communication with ETS should be secure or not and opens up the possibility of activating the runtime security.

Runtime security: sets whether during runtime, communication between devices should be secure or not. In other words, it determines which group addresses are to be secure. In order to activate the security during runtime, the commissioning security must be activated.

The activation of security on KNX Secure devices is optional. If it is activated, it is set individually in the group addresses, so that all or only a part of the objects can be secured, while the rest can function normally with non-secured devices. In other words, devices with and without KNX Secure can coexist in the same installation.

https://www.zennio.com

Technical Support: https://support.zennio.com 4

2 CONFIGURATION

KNX Secure Guide

From ETS version 5.7 onwards, the use of KNX security and all its functionalities to work with secure devices is enabled.
In this section a guide for the configuration of KNX secure in ETS projects is presented.

2.1 KNX DATA SECURE
Its implementation ensures communication between end devices. Secure KNX devices will transmit encrypted telegrams to other devices that also have KNX secure.
It will be possible to choose for each group address, whether the communication will be secure or not.

USB Interface
TP Area
Data secure

Main Line Area Coupler
Line Coupler

Area Coupler
TP Area
Line Coupler

TP Line TP Line

Figure 1. KNX data secure scheme.

https://www.zennio.com

Technical Support: https://support.zennio.com 5

KNX Secure Guide
2.1.1 SECURE COMMISSIONING
When a device has a secure commissioning, the communication between ETS and the device will be carried out in safe mode. A device should have a secure commissioning configured whenever there is runtime security, i.e. one of its objects is associated to a safe group address (see section 2.1.2). Note: Please note that the presence of a secure device within an ETS project, implies the protection of the project itself with a password.
ETS PARAMETERISATION The secure commissioning can be set from the "Configuration" tab in the "Properties" window of the device.

Figure 2. KNX Data Secure ­ Secure Commissioning.
Secure Commissioning [Activated / Deactivated]: enables to choose whether ETS should communicate with the device in safe mode or not, i.e. to enable or disable KNX secure on the device.
If the "Activated" option is selected, it will be mandatory to have a password for the project.

https://www.zennio.com

Technical Support: https://support.zennio.com 6

KNX Secure Guide

Figure 3. Project ­ Set Password.
An additional way to set a password on a project is through the main window ("Overview") of ETS. When selecting the project, a section will be displayed on the right side where, under "Details", the desired password can be entered.

Figure 4. ETS - Device password.
Add Device Certificate: If secure commissioning is "Activated", ETS will, in addition to the password, request a unique certificate for the device.
The certificate to be added [xxxxxx-xxxxxx-xxxxxx-xxxxxx-xxxxxx-xxxxxxxxxxxx-xxxxxx-xxxxxx] consists of 36 alphanumeric characters generated from the serial number and the FDSK (Factory Default Setup Key) of the device. It is included with the device and contains the corresponding QR code for easy scanning.

https://www.zennio.com

Technical Support: https://support.zennio.com 7

KNX Secure Guide

Figure 5. Project ­ Add Device Certificate.
Device certificate can also be added from the main ETS window ("Overview"), by accessing the "Security" section of the new window displayed on the right side when selecting the project.

Figure 6. ETS ­ Add device certificate.
During the first secure commissioning, ETS replaces the FDSK of the device with a new key (Tool Key) that is generated individually for each device.
If the project is lost, all tool keys will be lost with it, therefore, the devices cannot be reprogrammed. In order to be able to recover them, the FDSK must be reset.
The FDSK can be restored in two ways: after an unloading, provided that it is performed from the project in which the first commissioning was carried out, or after a manual factory reset (see section 3).

https://www.zennio.com

Technical Support: https://support.zennio.com 8

KNX Secure Guide
2.1.2 SECURE GROUP COMMUNICATION
Each object of a secure device can transmit its information in encrypted form, thus establishing security in communication or operation.
For an object to have KNX security, it has to be configured from the group address itself, i.e. the address to which the object will be associated.
ETS PARAMETERISATION The communication security settings are defined from the "Configuration" sub-tab in the "Properties" window of the group address.

Figure 7. KNX Data Secure ­ Group Address Security.
Security [Automatic / On / Off]: in "Automatic" setting, ETS decides whether encryption is activated if the two linked objects can communicate securely.
Notes:  All object linked to a secure group address shall be secure objects.  Same device can have both secure and non-secure group address.
Secure Objects can be identified with a "blue shield".

https://www.zennio.com

Figure 8. Secure Object.
Technical Support: https://support.zennio.com 9

KNX Secure Guide
2.2 KNX IP SECURE
KNX IP security is designed for KNX installations with IP communication. Its implementation ensures the secure exchange of KNX data between systems via secure KNX devices with IP connection. This type of security is applied on bus interfaces and only in the IP medium, i.e. secure telegrams are transmitted between secure KNX IP couplers, devices and interfaces. In order for the transmission of telegrams on a main line or sub-line to also be secure, security must be activated on the KNX bus (see section 2.1).
IP Interface Backbone IP

TP Area

Area Coupler

Data secure

Line Coupler

Area Coupler
TP Area
Line Coupler

TP Line TP Line

Figure 9. KNX IP Secure scheme

https://www.zennio.com

Technical Support: https://support.zennio.com 10

KNX Secure Guide
2.2.1 SECURE COMMISSIONING
In this type of security, in addition to secure commissioning in section 1.1.1, "Secure Tunneling" can also be activated. This parameter can be found in the "Settings" tab of the device properties window on the right-hand side of the ETS screen.
ETS PARAMETERISATION The commissioning and tunneling security settings are defined from the "Configuration" tab in the "Properties" window of the device.

Figure 10. KNX IP Secure - Secure Commissioning and Tunneling.
In addition to Secure Commissioning and the button Add Device Certificate, previously explained on section 2.1.1, will also appear:
Secure Tunneling [Enabled / Disabled]: parameter only available if secure commissioning is enabled. If this property is "Enabled", the data transmitted through the tunnel connections will be secure, i.e. the information will be encrypted through the IP medium. Each tunnel address will have its own password.

https://www.zennio.com

Technical Support: https://support.zennio.com 11

KNX Secure Guide
Figure 11. Tunneling Address Password.
The IP tab of the product also contains the Commissioning Password and the Authentication Code, which are required to make any secure connection to the device.

Figure 12. Commissioning Password and Authentication Code.
Note: It is recommended that the authentication code for each device be individual (and preferably the default set in ETS).
The commissioning password will be requested when the IP Interface is selected in ETS to connect to it (the authentication code is optional):

https://www.zennio.com

Technical Support: https://support.zennio.com 12

KNX Secure Guide
Figure 13. Request for Commissioning Password when selecting a secure IP Interface.

https://www.zennio.com

Technical Support: https://support.zennio.com 13

3 FACTORY RESET

KNX Secure Guide

To prevent a device from becoming unusable in the event of losing the project and/or the Tool Key with which it is programmed, it is possible to return it to the factory state restoring the FDSK by following the steps below:
1. Put the device in safe mode. This is achieved by powering it up with the programming button pressed until the programming LED flashes.
2. Release the programming button. It keeps flashing. 3. Press the programming button for 10 seconds. While pressing the button, it lights
in red. The reset occurs when the LED turns off momentarily.
This process, apart from the Tool Key, also deletes the BCU password and resets the individual address to the value 15.15.255.
An unload of the application program also deletes the Tool Key and the BCU password, although in this case the ETS project with which it was programmed is required.

https://www.zennio.com

Technical Support: https://support.zennio.com 14

4 OBSERVATIONS

KNX Secure Guide

Some considerations for the use of KNX security:
Individual address change: in a project with several already programmed secure devices that share group addresses between them, changing the individual address in one of them makes it necessary to program the rest of the devices that share group addresses with it.
Programming a reset device: when trying to program a factory reset device, ETS detects that the FDSK is being used and asks for confirmation to generate a new Tool Key in order to reprogram the device.
Device programmed in another project: if you try to download a device (safely or not) that has already been safely programmed in another project, you will not be able to download it. You will have to recover the original project or perform a factory reset.
BCU key: this password is lost either by manual factory reset or by unloading.

https://www.zennio.com

Technical Support: https://support.zennio.com 15

Join and send us your inquiries about Zennio devices:
https://support.zennio.com
Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo. Spain Tel. +34 925 232 002 www.zennio.com info@zennio.com

