PRODUCT OVERVIEW
The front panel of the Hybrid Solar Inverter/Charger features the following components:
- 1. LCD display: Shows operating status and information.
- 2. Status indicator: Indicates operational status.
- 3. Charging indicator: Shows charging status.
- 4. Fault indicator: Lights up when an error occurs.
- 5. Function buttons: Used for navigation and selection in menus.
- 6. Grounding: Terminal for grounding the unit.
- 7. AC input: Terminal for AC power input.
- 8. AC output: Terminal for AC power output.
- 9. Battery input: Terminal for connecting the battery.
- 10. PV input: Terminal for connecting solar panels.
- 11. WIFI communication port: For optional Wi-Fi monitoring.
- 12. Power on/off switch: To turn the unit on or off.
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
Preparation
Before connecting all wirings, remove the bottom cover by unscrewing two screws.
Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Ensure sufficient clearance from other objects and surfaces as shown in the diagram to guarantee adequate heat dissipation and space for wire removal.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws. M4 or M5 screws are recommended.
Battery Connection
CAUTION: For safety operation and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter. While not always required in some applications, over-current protection is still recommended. Refer to the table below for typical amperage to determine the required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, please use the proper recommended cable, stripping length (L2), and tinning length (L1) as specified below.
Recommended battery cable stripping length (L2) and tinning length (L1):
Model | Maximum Amperage | Battery capacity | Wire Size | Cable mm² | L1 (mm) | L2 (mm) | Torque value |
---|---|---|---|---|---|---|---|
1500W-24 | 70A | 100AH | 6AWG | 13.3 | 3 | 18 | 2~3 Nm |
2500W-24 | 100A | 100AH | 4AWG | 21.15 | 3 | 18 | 2~3 Nm |
Other Models | 140A | 100AH | 2AWG | 38 | 3 | 18 | 2~3 Nm |
Please follow these steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative cables based on the recommended stripping length.
- Connect all battery packs as required. Using the recommended battery capacity is advised.
- Insert battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Verify that polarity is correctly connected at both the battery and the inverter/charger, and that battery cables are tightly screwed to the battery connector.
AC Input/Output Connection
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal, as this may cause overheating.
CAUTION!! Do not apply anti-oxidant substance on the terminals before they are connected tightly.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure that the positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended AC breaker specification is 50A.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
Model | Gauge | Torque Value |
---|---|---|
1.5KW | 12AWG | 1.4~ 1.6Nm |
2.5KW/3.2W | 10AWG | 1.4~ 1.6Nm |
5.5KW | 8 AWG | 1.4~ 1.6Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground (yellow-green)) first.
- L → LINE (brown or black)
- N → Neutral (blue)
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect PE protective conductor (Ground (yellow-green)) first.
- L → LINE (brown or black)
- N → Neutral (blue)
5. Make sure the wires are securely connected.
CAUTION: Important. Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart to allow refrigerant gas inside the circuits to balance. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check with the air conditioner manufacturer if it is equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it may still cause internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, please use the proper recommended cable size as below.
Model | Typical Amperage | Cable Size | Torque |
---|---|---|---|
1.5KW-3.2KW | 15A | 12 AWG | 1.4~1.6 Nm |
5.5KW | 18A | 12 AWG | 1.4~1.6 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider the following parameters:
- The open circuit Voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
- The open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
Solar Charging Mode
INVERTER MODEL | 1.5KW-3.2KW | 5.5KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 500VDC | 500VDC |
PV Array MPPT Voltage Range | 30VDC~500VDC | 60VDC~500VDC |
Max. PV INPUT CURRENT | 15A | 18A |
Take the 450Wp and 550Wp PV modules as an example. After considering the above two parameters, the recommended module configurations are listed in the table below.
Configuration for 450Wp Solar Panels:
SOLAR INPUT | Q'ty of panels | Total input power | Inverter Model |
---|---|---|---|
1 pcs in serial | 1 pcs | 450 W | 1.5KW-5.5KW |
2 pcs in serial | 2 pcs | 900 W | 1.5KW-5.5KW |
3 pcs in serial | 3 pcs | 1,350 W | 1.5KW-5.5KW |
4 pcs in serial | 4 pcs | 1,800 W | 1.5KW-5.5KW |
5 pcs in serial | 5 pcs | 2,250 W | 2.5KW-5.5KW |
6 pcs in serial | 6 pcs | 2,700 W | 2.5KW-5.5KW |
7 pcs in serial | 7 pcs | 3,150 W | 2.5KW-5.5KW |
8 pcs in serial | 8 pcs | 3,600 W | 3.5KW-5.5KW |
9 pcs in serial | 9 pcs | 4,050 W | 3.5KW-5.5KW |
10 pcs in serial | 10 pcs | 4,500 W | 5.5KW |
11 pcs in serial | 11 pcs | 4,950 W | 5.5KW |
12 pcs in serial | 12 pcs | 5,400 W | 5.5KW |
6 pieces in serial and 2 sets in parallel | 12 pcs | 5,400 W | 5.5KW |
Configuration for 550Wp Solar Panels:
SOLAR INPUT | Q'ty of panels | Total input power | Inverter Model |
---|---|---|---|
1 pcs in serial | 1 pcs | 550 W | 1.5KW-5.5KW |
2 pcs in serial | 2 pcs | 1,150 W | 1.5KW-5.5KW |
3 pcs in serial | 3 pcs | 1,650 W | 1.5KW-5.5KW |
4 pcs in serial | 4 pcs | 2,200 W | 2.5KW-5.5KW |
5 pcs in serial | 5 pcs | 2,750 W | 2.5KW-5.5KW |
6 pcs in serial | 6 pcs | 3,300 W | 3.5KW-5.5KW |
7 pcs in serial | 7 pcs | 3,850 W | 3.5KW-5.5KW |
8 pcs in serial | 8 pcs | 4,400 W | 5.5KW |
9 pcs in serial | 9 pcs | 4,950 W | 5.5KW |
4 pieces in serial and 2 sets in parallel | 8 pcs | 4,400 W | 5.5KW |
5 pieces in serial and 2 sets in parallel | 10 pcs | 5,500 W | 5.5KW |
PV Module Wire Connection:
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Make sure the wires are securely connected.
Final Assembly
After connecting all wirings, put the bottom cover back by screwing two screws.
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LED Indicator:
LED Indicator | Color | Status | Messages |
---|---|---|---|
AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
Flashing | Output is powered by battery or PV in battery mode. | ||
CHG | Green | Solid On | Battery is fully charged. |
Flashing | Battery is charging. | ||
FAULT | Red | Solid On | Fault occurs in the inverter. |
Flashing | Warning condition occurs in the inverter. |
Function Keys:
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. Then, press "ENTER" button to confirm the selection or ESC button to exit.
Setting Programs:
Program | Description | Selectable option |
---|---|---|
01 Output source priority: To configure load power source priority |
Utility first (default) Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available. |
|
Solar first Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. |
||
SBU priority Utility provides power to the loads only when any one condition happens: - Solar energy is not available - Battery voltage drops to either low-level warning voltage or the setting point in program 12. |
||
SUB priority Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. |
||
02 Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) |
60A (default) |
If selected, acceptable charging current range will be from Max. AC charging current to Max. charging current of SPEC, but it shouldn't be less than the AC charging current (program 11). |
03 AC input voltage range |
Appliances (default) | If selected, acceptable AC input voltage range will be within 90-280VAC. |
UPS | If selected, acceptable AC input voltage range will be within 170-280VAC. | |
Generator | If selected, acceptable AC input voltage range will be within 90-280VAC and compatible with generators. Note: Because generators are unstable, maybe the output of inverter will be unstable too. |
|
05 Battery type |
AGM (default) | |
Flooded | ||
User-Defined | If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. | |
Lithium battery without communication | If "LIB" is selected, the battery default value is fit for lithium battery without communication battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. | |
06 Auto restart when overload occurs |
Restart disable | Restart enable (default) |
07 Auto restart when over temperature occurs |
Restart disable | Restart enable (default) |
08 Output voltage |
220V | |
230V (default) | ||
240V | ||
09 Output frequency |
50Hz (default) | |
60Hz | ||
10 Auto bypass When selecting "auto", if the mains power is normal, it will automatically bypass, even if the switch is off. |
manual(default) | |
auto | ||
11 Maximum utility charging current |
30A (default) | If selected, acceptable charging current range will be within 2-Max. AC charging current of SPEC. |
12 Setting voltage point back to utility source when selecting “SBU priority" or "Solar first" in program 01. |
48V models:46V (default) | Setting range is from 44.0V to 57.2V for 48v model, but the max setting value must be less than the value of program13 and the minimum setting value must be more than the value of 29. |
24V models:23V (default) | Setting range is from 22.0V to 28.6V for 24v model, but The max setting value must be less than the value of program13 and the minimum setting value must be more than the value of 29. | |
12V models:11.5V (default) | Setting range is from 11.0V to 14.3V for 12v model, but The max setting value must be less than the value of program13 and the minimum setting value must be more than the value of 29. | |
13 Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01. |
Battery fully charged (default) | |
48V models: | Setting range is from 48V to full (the value of program26-0.4V), but the max setting value must be more than the value of program12. | |
24V models: 12V models: |
Setting range is from 24V to full (the value of program26-0.4V), but the max setting value must be more than the value of program12. Setting range is from 12V to full (the value of program13-0.4V), but the max setting value must be more than the value of program12. |
|
16 Charger source priority: To configure charger source priority |
Solar first | Solar energy will charge battery as first priority. |
Solar and Utility (default) | Solar energy and utility will charge battery at the same time. | |
Only Solar | Solar energy will be the only charger source no matter utility is available or not. | |
If this inverter/charger is working in Battery mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient. | ||
18 Buzzer mode |
Mode1 | Buzzer mute |
Mode2 | The buzzer sounds when the input source changes or there is a specific warning or fault | |
Mode3 | The buzzer sounds when there is a specific warning or fault | |
Mode4(default) | The buzzer sounds when there is a fault | |
19 Auto return to default display screen |
Return to default display screen (default) | If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute. |
Stay at latest screen | If selected, the display screen will stay at latest screen user finally switches. | |
20 Backlight control |
Backlight on (default) | |
Backlight off | ||
23 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. |
Bypass disable | Bypass enable(default) |
25 Modbus ID Setting |
Modbus ID Setting Range : 001(default)~247 | |
26 Bulk charging voltage (C.V voltage) |
If self-defined is selected in program 5, this program can be set up. But the setting value must be more than or equal the value of program27. Increment of each click is 0.1V. 12V models: Default 14.1V, setting range is from 12.0V to 15.5V, 24V models: Default 28.2V, setting range is from 24.0V to 30.0V, 48V models: Default 56.4V, setting range is from 48.0V to 62.0V. |
|
27 Floating charging voltage |
If self-defined is selected in program 5, this program can be set up. 12V models default setting: 13.5V Setting range is from 12.0V to the value of program 26 24V models default setting: 27.0V Setting range is from 24.0V to the value of program 26 48V models default setting: 54.0V Setting range is from 48.0V to the value of program 26 |
|
29 Low DC cut-off voltage |
If self-defined is selected in program 5, this program can be set up. The setting value must be less than the value of program12. Increment of each click is 0.1V.Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. 12V models default setting: 10.5v Setting range is from 10.0V to 13.5V 24V models default setting: 21.0v Setting range is from 20.0V to 27.0V 48V models default setting: 42.0V Setting range is from 40.0V to 54.0V |
|
32 Bulk charging time (C.V stage) |
Automatically (Default): | If selected, inverter will judge this charging time automatically. |
5 min 900 min |
The setting range is from 5 min to 900 min. Increment of each click is 5 min. | |
33 Battery equalization |
Battery equalization | If "USE" is selected in program 05, this program can be set up. Battery equalization disable (default) |
If "Flooded" or "User-Defined" is selected in program 05, this program can be set up. | ||
34 Battery equalization voltage |
12V models default setting is 14.6V. Setting range is from floating voltage ~ 15.5V. Increment of each click is 0.1V. 24V models default setting is 29.2V. Setting range is from floating voltage ~ 30V. Increment of each click is 0.1V. 48V models default setting is 58.4V. Setting range is from floating voltage ~ 62V. Increment of each click is 0.1V. |
|
35 Battery equalized time |
60min (default) | Setting range is from 0 min to 900min. |
120min (default) | ||
36 Battery equalized timeout |
Setting range is from 0min to 900 min. | |
37 Equalization interval |
30days (default) | Setting range is from 1 to 90 days. |
39 Equalization activated immediately |
Enable | If equalization function is enabled in program 33, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows " E9 ". If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 37 setting. At this time, " E9 " will not be shown in LCD main page.. |
Disable (default) | ||
41 Automatic activation for lithium battery. Note: This function is just available for supporting lithium battery activation models, other models are reserve setting item |
Disable automatic activation (default) When Program05 is selected "LIx" or "User-Defined "as lithium battery and when the battery is not detected, the unit will activate automatically the lithium battery at a time. If you want to activate automatically the lithium battery, you must restart the unit. |
|
42 Manual activation for lithium battery. Note: This function is just available for supporting lithium battery activation models, other models are reserve setting item |
Default: disable activation When Program05 is selected "LIx" as lithium battery, when the battery is not detected, If you want to activate the lithium battery at a time, you could selected it. |
|
46 Maximum discharge current protection when selecting "single" in program 28 |
Default OFF Disable current discharge current protection function |
|
Only available in Single model. When utility is available, it turns to utility model and battery discharge stops after the battery discharge current exceeded the setting value. When utility is unavailable, warning occurs and battery discharge lasts after the battery discharge current exceeded the setting value. |
BATTERY EQUALIZATION
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 37.
- Active equalization immediately in program 39.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
SETTING FOR LITHIUM BATTERY
Setting for lithium battery without communication
This suggestion is used for lithium battery application and to avoid lithium battery BMS protection without communication. Please finish the setting as follow:
- Before starting setting, you must get the battery BMS specification:
A. Max charging voltage
B. Max charging current
C. Discharging protection voltage - Set battery type as "LIB"
AGM (default) | Flooded | User-Defined | |
---|---|---|---|
05 Battery type |
If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. | ||
Lithium battery without communication | If "LIB" is selected, the battery default value is fit for lithium battery without communication battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. |
- Set C.V voltage as Max charging voltage of BMS-0.5V.
26 Bulk charging voltage (C.V voltage) |
If self-defined is selected in program 5, this program can be set up. But the setting value must be more than or equal the value of program27. Increment of each click is 0.1V. 12V models: Default 14.1V, setting range is from 12.0V to 15.5V, 24V models: Default 28.2V, setting range is from 24.0V to 30.0V, 48V models: Default 56.4V, setting range is from 48.0V to 62.0V. |
|
27 Floating charging voltage |
If self-defined is selected in program 5, this program can be set up. 12V models default setting: 13.5V Setting range is from 12.0V to the value of program 26 24V models default setting: 27.0V Setting range is from 24.0V to the value of program 26 48V models default setting: 54.0V Setting range is from 48.0V to the value of program 26 |
|
29 Low DC cut-off voltage |
If self-defined is selected in program 5, this program can be set up. The setting value must be less than the value of program12. Increment of each click is 0.1V.Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. 12V models default setting: 10.5v Setting range is from 10.0V to 13.5V 24V models default setting: 21.0v Setting range is from 20.0V to 27.0V 48V models default setting: 42.0V Setting range is from 40.0V to 54.0V |
- Set Max charging current which must be less than the Max charging current of BMS.
02 Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) |
60A (default) | If selected, acceptable charging current range will be within 1- Max. charging current of SPEC, but it shouldn't be less than the AC charging current (program 11) |
- Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01.The setting value must be ≥Low DC cut-off voltage+1V, or else the inverter will have a warning as battery voltage low.
12 Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. |
48V models:46V (default) Setting range is from 44.0V to 57.2V for 48v model, but the max setting value must be less than the value of program13. |
24V models:23V (default) Setting range is from 22.0V to 28.6V for 24v model, but The max setting value must be less than the value of program13. 12V models:11.5V (default) Setting range is from 11.0V to 14.3V for 12v model, but The max setting value must be less than the value of program13. |
Remark:
- You'd better to finish setting without turning on the inverter (just let the LCD show, no output).
- When you finish setting, please restart the inverter.
Fault Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
01 | Over temperature of inverter module | 01- |
02 | Over temperature of DCDC module | 02- |
03 | Battery voltage is too high | 03- |
04 | Over temperature of PV module | 04- |
05 | Output short circuited. | 05- |
06 | Output voltage is too high. | 06- |
07 | Overload time out | 07- |
08 | Bus voltage is too high | 08- |
09 | Bus soft start failed | 09- |
10 | PV over current | 10- |
11 | PV over voltage | 11- |
12 | DCDC over current | 12- |
13 | Over current or surge | 13- |
14 | Bus voltage is too low | 14- |
15 | Inverter failed (Self-checking) | 15- |
18 | Op current offset is too high | 18- |
19 | Inverter current offset is too high | 19- |
20 | DC/DC current offset is too high | 20- |
21 | PV current offset is too high | 21- |
22 | Output voltage is too low | 22- |
23 | Inverter negative power | 23- |
Warning Indicator
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
02 | Temperature is too High | Beep three times every second | 02- |
04 | Low battery | Beep once every second | 04- |
07 | Overload | Beep once every 0.5 second | OVER LOAD |
10 | Output power derating | Beep twice every 3 seconds | 10- |
14 | Fan blocked | None | 14- |
15 | PV energy is low | Beep twice every 3 seconds | 15- |
19 | Lithium Battery communication is failed | Beep once every 0.5 second | 19- |
21 | Lithium Battery over current | None | 21- |
E9 | Battery equalization | None | E9- |
bP | Battery is not connected | None | bP- |
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 1.5KW | 1.5KW | 2.5KW | 3.2KW | 5.5KW |
---|---|---|---|---|---|
Input Voltage Waveform | Sinusoidal (Utility or Generator) | ||||
Nominal Input Voltage | 230Vac | ||||
Low Loss Voltage | 170Vac±7V (UPS) 90Vac±7V (Appliances) | ||||
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | ||||
High Loss Voltage | 280Vac±7V | ||||
High Loss Return Voltage | 270Vac±7V | ||||
Max AC Input Voltage | 300Vac | ||||
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | ||||
Low Loss Frequency | 40±1Hz | ||||
Low Loss Return Frequency | 42±1Hz | ||||
High Loss Frequency | 65±1Hz | ||||
High Loss Return Frequency | 63±1Hz | ||||
Output Short Circuit Protection | Battery mode: Electronic Circuits | ||||
Efficiency (Line Mode) | >95% ( Rated R load, Battery full charged ) | ||||
Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.
Table 2 Inverter Mode Specifications
INVERTER MODEL | 1.5KW | 1.5KW | 2.5KW | 3.2KW | 5.5KW |
---|---|---|---|---|---|
Rated Output Power | 1.5KVA/1.5KW | 2.5KVA/2.5KW | 3.2KVA/3.2KW | 5.5KVA/5.5KW | |
Output Voltage Waveform | Pure Sine Wave | ||||
Output Voltage Regulation | 230Vac±5% | ||||
Output Frequency | 50Hz or 60Hz | ||||
Peak Efficiency | 94% | ||||
Surge Capacity | 2* rated power for 5 seconds | ||||
Nominal DC Input Voltage | 12Vdc | 24Vdc | 48Vdc | ||
Cold Start Voltage | 11.0Vdc | 23.0Vdc | 46.0Vdc | ||
Low DC Warning Voltage Just for AGM and Flooded | 11.0Vdc @ load < 20% 10.7Vdc @ 20% ≤ load < 50% 10.1Vdc @ load ≥ 50% | 22.0Vdc 21.4Vdc 20.2Vdc | 40.4Vdc 42.8Vdc 44.0Vdc | ||
Low DC Warning Return Voltage Just for AGM and Flooded | 11.5Vdc @ load < 20% 11.2Vdc @ 20% ≤ load < 50% 10.6Vdc @ load ≥ 50% | 23.0Vdc 22.4Vdc 21.2Vdc | 46.0Vdc 44.8Vdc 42.4Vdc | ||
Low DC Cut-off Voltage Just for AGM and Flooded | 10.5Vdc @ load < 20% 10.2Vdc @ 20% ≤ load < 50% 9.6Vdc @ load ≥ 50% | 21.0Vdc 20.4Vdc 19.2Vdc | 42.0Vdc 40.8Vdc 38.4Vdc |
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL | 1.5KW | 1.5KW | 2.5KW | 3.2KW | 5.5KW |
---|---|---|---|---|---|
Max Charging Current (PV+AC) (@ VI/P=230Vac) | 100Amp | 60Amp | 80Amp | 100Amp | 100Amp |
Max Charging Current (AC)(@ VI/P=230Vac) | 60Amp | ||||
Bulk Charging Voltage Flooded Battery AGM / Gel Battery | 14.6Vdc 14.1Vdc | 29.2Vdc 28.2Vdc | 58.4Vdc 56.4Vdc | ||
Floating Charging Voltage | 13.5Vdc | 27Vdc | 54Vdc | ||
Overcharge Protection | 15.5 Vdc | 33Vdc | 63Vdc | ||
Charging Algorithm | 3-Step |
Solar Input
INVERTER MODEL | 1.5KW | 1.5KW | 2.5KW | 3.2KW | 5.5KW |
---|---|---|---|---|---|
Rated Power | 2000W | 2000W | 3000W | 4000W | 5500W |
Max. PV Array Open Circuit Voltage | 500Vdc | ||||
PV Array MPPT Voltage Range | 30Vdc~500Vdc | ||||
Max. Input Current | 15A | 15A | 15A | 15A | 18A |
Max. Charging Current(PV) | 100A | 60A | 100A | 100A | 100A |
Table 4 General Specifications
INVERTER MODEL | 1.5KW | 1.5KW | 2.5KW | 3.2KW | 5.5KW | |
---|---|---|---|---|---|---|
Operating Temperature Range | -10°C to 55°C | |||||
Storage temperature | -15°C~ 60°C | |||||
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |||||
Dimension(D*W*H), mm | 330x278x98 | 438x295x105 | ||||
Net Weight, kg | 3.8 | 3.95 | 8.2 |
TROUBLE SHOOTING
Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
---|---|---|---|
Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
No response after power on. | No indication. | 1. The battery voltage is far too low. 2. Battery polarity is connected reversed. |
1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS→Appliance) |
Buzzer beeps continuously and red LED is on. | Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. |
LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. | |
Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
Fault code 02 | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
Fault code 03 | Battery is over-charged. | Return to repair center. | |
The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | ||
Fault code 06/22 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
Fault code 08/09/15 | Internal components failed. | Return to repair center. | |
Fault code 13 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
Fault code 14 | Bus voltage is too low. | If the wires is connected well, please return to repair center. |