USER MANUAL
HYBRID SOLAR INVERTER/CHARGER
8.5KVA/11.0KVA 230Vac
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
[Warning] This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- [Caution] To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- [Caution] Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedures when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
- Fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input to short circuit. Do NOT connect to the mains when DC input is short-circuited.
- [Warning] Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
Features
- Pure sine wave inverter
- Inverter running without battery
- Built-in MPPT solar controller
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes the following devices to have a complete running system:
- Generator or Utility.
- PV modules (option)
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.
[Diagram Description: A central 'Hybrid Solar Inverter' is shown. To its left, connected by red DC lines, are 'Solar power (option)' and 'Generator'. Below 'Generator' is 'Utility', connected by blue AC lines. To the right of the inverter, connected by red DC lines, is 'External Battery packs'. Connected by blue AC lines to the inverter's output are 'Home Appliances'.]
Product Overview
[Diagram Description: The front view of the inverter shows numbered components: 1. LCD display, 2. Status indicator, 3. Charging indicator, 4. Fault indicator, 5. Function buttons, 6. Power on/off switch. The rear view shows numbered ports: 7. Battery negative/positive outlet hole, 8. RS232 communication port (RJ45), 9. RS485 communication port (RJ45), 10. RS232 communication port (DB9), 11. Dry contact port, 12. PV1 input, 13. PV2 input, 14. AC input, 15. AC output, 16. Grounding point.]
Note: RS232 communication port (DB9) and RS232 communication port (RJ45) cannot be used simultaneously; only one can be used at the same time.
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside the package:
- The unit x 1
- User manual x 1
- PV connector x 4
- Battery fuse x 1
Preparation
Before connecting all wirings, please take off the bottom cover by removing four screws as shown below.
[Diagram Description: Shows the inverter unit with the bottom cover detached, indicating four screws to be removed.]
Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
[Caution] SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
[Diagram Description: Shows the inverter unit with recommended clearances: 50cm above, 50cm below, and 20cm on each side for ventilation and wire access.]
Install the unit by screwing three screws. It is recommended to use M4 or M5 screws.
[Diagram Description: Shows the inverter unit with dimensions indicated: 56.4 mm, 290.0 mm, 361.4 mm, and 495.0 mm, with arrows pointing to screw holes for mounting.]
Battery Connection
[Caution] For safety operation and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested to have a disconnect device in some applications; however, it is still requested to have over-current protection installed. Please refer to the typical amperage in the table below as required fuse or breaker size.
[Warning] All wiring must be performed by a qualified personnel.
[Warning] It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable.
Recommended battery cable, Terminal size:
Model | Maximum Amperage capacity | Wire Size | Cable mm² | Terminal size(mm) | Torque value | |||
---|---|---|---|---|---|---|---|---|
L | W | D | ||||||
8.5KW | 180A | 400AH | 4AWG*2 | 25 | 37 | 22 | 8.4 | 10~12 Nm |
11.0KW | 220A | 600AH | 2AWG*2 | 38 | 37 | 22 | 8.4 | 10~12 Nm |
[Diagram Description: Shows a close-up of a battery terminal connector with dimensions labeled L, W, and D.]
Please follow below steps to implement battery connection:
- Make positive and negative cables based on recommended terminal size.
- Connect all battery packs as units require. It's suggested to use recommended battery capacity.
- Insert battery cable flatly into the battery connector of the inverter and make sure the bolts are tightened with a torque of 10-12Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and battery cables are tightly screwed to the battery connector.
[Warning] Shock Hazard: Installation must be performed with care due to high battery voltage in series.
[Caution] Do not place anything between the flat part of the inverter terminal; otherwise, overheating may occur.
[Caution] Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
[Caution] Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
AC Input/Output Connection
[Caution] Before connecting to the AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A.
[Caution] There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
[Warning] All wiring must be performed by a qualified personnel.
[Warning] It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Torque Value |
---|---|---|
All Model | 6 AWG | 1.2~ 1.4Nm |
[Diagram Description: Shows a 48V MODEL battery configuration with four 12V batteries connected in series. Arrows indicate the positive and negative connections to the inverter.]
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect PE protective conductor [Ground Symbol] first.
[Arrow Right] Ground (yellow-green) L [Arrow Right] LINE (brown or black) N [Arrow Right] Neutral (blue)
[Warning] Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect PE protective conductor [Ground Symbol] first.
[Arrow Right] Ground (yellow-green) L [Arrow Right] LINE (brown or black) N [Arrow Right] Neutral (blue) - Make sure the wires are securely connected.
[Caution] Important: Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
[Caution] Appliances such as air conditioners require at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the air conditioner manufacturer if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
[Diagram Description: Shows AC input/output wiring details. The first diagram illustrates connecting input wires: Ground (yellow-green), Line (brown/black), Neutral (blue). The second diagram illustrates connecting output wires similarly. Arrows indicate the flow and connection points.]
PV Connection
[Caution] Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
[Warning] All wiring must be performed by a qualified personnel.
[Warning] It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model | Typical Amperage | Cable Size | Torque |
---|---|---|---|
All Model | 18A*2 | 10 AWG | 1.4~1.6 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeding max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode
INVERTER MODEL | 8.5KW | 11.0KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 500VDC | |
PV Array MPPT Voltage Range | 60VDC~500VDC | |
Max. PV INPUT CURRENT | 18A*2 | 18A*2 |
Take the 450Wp and 550Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed in the table below. The recommended module configurations are fit for PV1 or PV2, for example: PV1 is 8 pcs in serial and PV1 could be 8 pcs in serial too, total quantity of panels is 16pcs.
Solar Panel Spec. (reference) - 450Wp
SOLAR INPUT | Q'ty of panels | Total input power | Inverter Model |
---|---|---|---|
3 pcs in serial | 3 pcs | 1,350 W | All Model |
4 pcs in serial | 4 pcs | 1,800 W | |
5 pcs in serial | 5 pcs | 2,250 W | |
6 pcs in serial | 6 pcs | 2,700 W | |
7 pcs in serial | 7 pcs | 3,150 W | |
8 pcs in serial | 8 pcs | 3,600 W | |
9 pcs in serial | 9 pcs | 4,050 W | |
10 pcs in serial | 10 pcs | 4,500 W | |
11 pcs in serial | 11 pcs | 4,950 W | |
12 pcs in serial | 12 pcs | 5,400 W |
Solar Panel Spec. (reference) - 550Wp
SOLAR INPUT | Q'ty of panels | Total input power | Inverter Model |
---|---|---|---|
3 pcs in serial | 3 pcs | 1,650 W | All Model |
4 pcs in serial | 4 pcs | 2,200 W | |
5 pcs in serial | 5 pcs | 2,750 W | |
6 pcs in serial | 6 pcs | 3,300 W | |
7 pcs in serial | 7 pcs | 3,850 W | |
8 pcs in serial | 8 pcs | 4,400 W | |
9 pcs in serial | 9 pcs | 4,950 W |
PV Module Wire Connection:
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Make sure the wires are securely connected.
[Diagram Description: Shows two diagrams illustrating PV wire connection. The first shows a female terminal connected to a 4-6mm² cable. The second shows a male terminal connected to a 4-6mm² cable. Arrows indicate correct polarity connection to the PV input connectors.]
Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws as shown below.
[Diagram Description: Shows the inverter unit with the bottom cover being reattached using two screws.]
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. When program 16 of F0 group is set as "Model1", it could be used to deliver signal to external device when battery voltage reaches warning level. When program 16 of F0 is set as "Model2" and the unit is working in battery mode, it could be used to trigger the grounding box to connect neutral and grounding of AC output together.
Unit Status | Condition | Dry contact port: NC C NO | |
---|---|---|---|
NC & C | NO & C | ||
Power Off | Unit is off and no output is powered. | Close | Open |
Power On | Output is powered from Utility. | Open | Close |
Battery voltage or Soc < Low DC warning voltage or Soc | Open | Close | |
Program 1 of F1 set as SUB | Battery voltage or Soc > setting value program 5 of F2 or battery charging reaches floating stage | Close | Open |
Program 1 of F1 is set as SBU |
Battery voltage < Setting value program 5 of F2 Battery voltage > setting value program 6 of F2 or battery charging reaches floating stage |
Open | Close |
When program 16 of F0 is set as "Model2":
Unit Status | Condition | Dry contact port: NC C NO | |
---|---|---|---|
NC & C | NO & C | ||
Power Off | Unit is off and no output is powered. | Close | Open |
Power On | Unit works in standby mode, line mode or fault mode | Open | Close |
Unit works in battery mode or power saving mode | Close | Open |
[Diagram Description: Shows a small diagram of the Dry Contact Port with labels NC, C, and NO.]
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the side of the case) to turn on the unit.
[Diagram Description: Shows the rear panel of the inverter with an arrow pointing to the Power ON/OFF switch.]
Operation and Display Panel
The operation and display panel, shown in the below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
[Diagram Description: Shows the front panel of the inverter with labels for LCD display, LED indicators (AC/INV, CHG, FAULT), and Function keys (ESC, UP, DOWN, ENTER).]
LED Indicator
LED Indicator | Color | Status | Messages |
---|---|---|---|
AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
Green | Flashing | Output is powered by battery or PV in battery mode. | |
CHG | Green | Solid On | Battery is fully charged. |
Green | Flashing | Battery is charging. | |
FAULT | Red | Solid On | Fault occurs in the inverter. |
Red | Flashing | Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display
[Diagram Description: Shows the layout of the LCD screen divided into sections: INPUT, BATTTEMP, OUTPUT, BATTLOAD. It displays numerical values and units like kW, VA, %, °C, Hz. Icons represent PV1, PV2, L1, L2, BYPASS, ECO, Li, USER. Arrows indicate power flow directions.]
LCD Setting
- Pressing and holding the ENTER button for 3 seconds, the unit will enter setting groups mode.
- Press "UP" or "DOWN" button to select setting groups. There are 5 groups setting menus include F0/F1/F2/F3/F4, press "ENTER" button to confirm the selection or ESC button to exit.
- F0: Setting general parameters
- F1: Setting AC output parameters
- F2: Setting battery parameters
- F3: Setting time parameters
- F4: Setting systems parameters
- Press "ENTER" button to confirm the selection groups or ESC button to return selection groups or exit.
Setting F0 Programs:
Program | Description | Appliances (default) | Selectable option |
---|---|---|---|
01 | AC input voltage range | APL | If selected, acceptable AC input voltage range will be within 90-280VAC. |
UPS | If selected, acceptable AC input voltage range will be within 170-280VAC. | ||
Generator | If selected, acceptable AC input voltage range will be within 170-280VAC and compatible with generators. Note: Because generators are unstable, maybe the output of inverter will be unstable too. |
||
02 | Power saving mode enable/disable | Saving mode disable (default) | If disabled, no matter connected load is low or high, the on/off status of inverter output will not be effected. |
Saving mode enable | If enabled, the output of inverter will be off when connected load is pretty low or not detected. | ||
03 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable | Bypass enable (default) |
04 | Auto restart when overload occurs | Restart disable | Restart enable (default) |
05 | Auto restart when over temperature occurs | Restart disable | Restart enable (default) |
06 | Auto bypass When selecting "auto", if the mains power is normal, it will automatically bypass, even if the switch is off. | manual(default) | auto |
07 | Auto return to default display screen | Return to default display screen (default) | If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage / output voltage) after no button is pressed for 1 minute. |
Stay at latest screen | If selected, the display screen will stay at latest screen user finally switches. | ||
08 | Backlight control | Backlight on (default) | Backlight off |
09 | Buzzer mode | Mode1 | The buzzer sounds when the input source changes or there is a specific warning or fault |
Mode2 | The buzzer sounds when there is a specific warning or fault | ||
Mode3 | The buzzer sounds when there is a fault | ||
Mode4(default) | The buzzer sounds when there is a fault | ||
10 | Modbus ID Setting | Modbus ID Setting Range : 001(default)~247 | |
16 | Dry contact mode | Model1:(default) | It could be used to deliver signal to external device when battery voltage reaches warning level. |
Model2: | Allow neutral and grounding of AC output is connected together. This function is only available when the inverter is working with external grounding box. Only when the inverter is working in battery mode, it will trigger grounding box to connect neutral and grounding of AC output. Neutral and grounding of AC output is connected. |
Setting F1 Programs:
Program | Description | Selectable option | |
---|---|---|---|
01 | Output source priority | SUB priority (default) | Solar->Utility->Battery Solar energy is charged first and then power to the loads. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. |
SBU priority | Solar-> Battery ->Utility Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. |
||
SUF priority | Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 05 of F2 group. Solar->Utility->Battery If solar energy is sufficient to all connected loads and charge battery, the solar energy could feedback to the grid (sell power to grid) If solar energy is not sufficient to power all connected loads, utility energy will supply power to the loads at the same time. |
||
03 | Output voltage | 220V | 230V (default) |
240V | |||
04 | Output frequency | 50Hz (default) | 60Hz |
06 | Salve output source priority The priority is available after setting application period, the units will turn to salve priority in the setting period from main priority | OFF(default) | Turn off salve output source priority |
SUB priority | The function is the same as in program 01 of F1. | ||
SBU priority | |||
07 | Start timer setting for salve output source priority - Hours setting | 00 The setting range is from 00 to 23 of every day |
|
08 | Start timer setting for salve output source priority - Minutes setting | 00 The setting range is from 00 to 59 of every hour |
|
09 | End timer setting for salve output charger priority - Hours setting | 00 The setting range is from 00 to 23 of every day |
|
10 | End timer setting for salve charger source priority - Minutes setting | 00 The setting range is from 00 to 59 of every hour |
Setting F2 Programs:
Program | Description | Selectable option | |
---|---|---|---|
01 | Battery type | AGM (default) | AGM (default) |
Flooded | Flooded | ||
User-Defined | If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program03/04/08 of F2. | ||
LI1 | Support PYLON US2000 Protocol (3.5 Version) | ||
LI2 | Standard communication Protocol 2 from inverter supplier | ||
LI4 | If "LIB" is selected, the battery default value is fit for lithium battery without communication battery charge voltage and low DC cut-off voltage can be set up in program03/04/08 of F2. | ||
02 | Charger source priority: To configure charger source priority | Solar first | Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available. |
Solar and Utility (default) | Solar energy and utility will charge battery at the same time. | ||
Only Solar | Solar energy will be the only charger source no matter utility is available or not. | ||
Solar residual | Solar energy will support all connected loads as first priority, the residual energy will charge battery | ||
03 | Bulk charging voltage (C.V voltage) | 56.4V(default) | If self-defined or LIB is selected in program 01 of F2, this program can be set up. Setting range is the value of program 04 of F2 to 62.0V. |
56.4 | |||
04 | Floating charging voltage | 54.0V(default) | If self-defined or LIB is selected in program 01 of F2, this program can be set up. Setting range is from 48.0V to the value of program 03 of F2. |
54.0 | |||
05 | Setting voltage or Soc point back to utility source when selecting "SBU priority". | Lithium battery without communication: Default :46V | Setting range is from 44.0V to 57.2V, but the max setting value must be less than the value of program 06 of F2, and the minimum setting value must be more than the value of program 08 of F2 |
Lithium battery with communication: Default :50% | Setting range is from 5%~50%, but the minimum setting value must be more than the value of program 08 of F2 plus 2%. | ||
06 | Setting voltage point back to battery mode when selecting "SBU priority" in program 01(F1). | Battery fully charged (default) | If selected, acceptable voltage range will be from 48v to the value in program 03 of F2, but the minimum setting value must be more than the value of program 05 of F2. |
Default 95% | Setting range is from 60% to 100% | ||
08 | Low DC cut-off voltage or Soc | 1. If self-defined or LIB is selected in program 01 of F2, default value is 42.0V, setting range is from 40.0V to 54.0V, the max setting value must be less than the value of program 05 of F2. 2. If LIx is selected in program 01 of F2 and communication between the inverter and battery is successful, default value is 20%, the setting range value is 3%~30%, but the value must less than the value of program 05 of F2. |
|
09 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 8.5KW Model: 80A (default) | If selected, acceptable charging current range will be within 10-140A, but it shouldn't be less than the AC charging current (program 10 of F2) 11.0KW Model: If selected, acceptable charging current range will be within 10-160A, but it shouldn't be less than the AC charging current (program 10 of F2) |
10 | Maximum utility charging current | 60A (default) | If selected, acceptable charging current range will be within 2-120A, but the max setting value must be less than the value of program 09 of F2 |
11 | Slave charger source priority The priority is available after setting application period, the units will turn to salve priority in the setting period form main priority | OFF(default) | Turn off slave charger source priority |
Solar first | The function is the same as in program 02 of F2 group. | ||
Solar and Utility (default) | |||
Only Solar | |||
Solar residual | |||
12 | Start timer setting for salve charger source priority - Hours setting | 00 The setting range is from 00 to 23 of every day |
|
13 | Start timer setting for salve charger source priority - Minutes setting | 00 The setting range is from 00 to 59 of every hour |
|
14 | End timer setting for salve output charger priority - Hours setting | 00 The setting range is from 00 to 23 of every day |
|
15 | End timer setting for salve charger source priority - Minutes setting | 00 The setting range is from 00 to 59 of every hour |
|
16 | Bulk charging time (C.V stage) | Automatically (Default): AUE |
If selected, inverter will judge this charging time automatically. |
5 min | The setting range is from 5 min to 900 min. Increment of each click is 5 min. | ||
900 min | |||
17 | Battery equalization | If "USE" is selected in program 01 of F2 group, this program can be set up. | Battery equalization disable (default) |
Battery equalization | If "Flooded" or "User-Defined" is selected in program 01 of F2, this program can be set up. | ||
18 | Battery equalization voltage | 58.4V (default) | Setting range is from 48v~ 62V. Increment of each click is 0.1V (The minimum value should be greater than the floating recharge value). |
58.4 | |||
19 | Battery equalized time | 60min (default) | Setting range is from 0min to 900min. Increment of each click is 5min. |
20 | Battery equalized timeout | 120min (default) | Setting range is from 0min to 900 min. Increment of each click is 5 min. |
21 | Equalization interval | 30days (default) | Setting range is from 1 to 90 days. Increment of each click is 1 day |
22 | Equalization activated immediately | Enable | If equalization function is enabled in program 17 of F2, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows "[Warning Symbol]". If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 21 of F2 setting. At this time, "[Warning Symbol]" will not be shown in LCD main page. |
Disable (default) | |||
23 | Manual activate the lithium battery setting | Active | Default: disable activation When program 01 of F2 is selected "LIx" as lithium battery, when the battery is not detected, If you want to activate the lithium battery at a time, you could selected it. |
24 | Automatic activation for lithium battery | Auto | Default: disable activation When program 01 of F2 is selected "LIx" as lithium battery, when the battery is not detected, the unit or PV will activate automatically the lithium battery at a time. If you want to activate automatically the lithium battery, you must restart the unit. |
25 | Max battery discharge current setting | OFF(default) | When the battery discharge current more than the setting value, the unit will stop discharging and go to bypass mode or standby mode. The setting range is from 50 to 500 |
Setting F3 Programs:
Program | Description | Selectable option | |
---|---|---|---|
01 | Time setting -Year | 000,001...099 | For year setting, the range is from 00 to 99. |
02 | Time setting-Month | 001,002...012 | For month setting, the range is from 1 to 12. |
03 | Time setting-Day | 001,002...031 | For day setting, the range is from 1 to 31. |
04 | Time setting -Hour | 000,001...023 | For hour setting, the range is from 0 to 23. |
05 | Time setting -Minute | 000,001...059 | For minute setting, the range is from 0 to 59. |
06 | Time setting -Second | 000,001...059 | For second setting, the range is from 0 to 59. |
Setting F4 Programs:
Program | Description | Selectable option | |
---|---|---|---|
01 | Reset all stored data of PV generated power and output load energy | Reserve data(default) | Reset generated energy data |
YES |
LCD display description
The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. All of the information could be shown in 1/2/3 area of LCD.
[Diagram Description: Shows the LCD screen layout with three main display areas labeled 1, 2, and 3. It includes INPUT/OUTPUT sections, battery temperature, load information, and various icons representing PV, AC, battery, bypass, etc.]
Item | 1 area data | 3 area data | For Example |
---|---|---|---|
1 | Input voltage | Output voltage | Input Voltage=220V, output voltage=220V (Default Display Screen) [Diagram: Shows LCD segments displaying '220' for input and output voltage.] |
2 | Input frequency | Output frequency | Input frequency=50Hz, Output frequency=50Hz [Diagram: Shows LCD segments displaying '50.0 Hz' for input and output frequency.] |
3 | Output active power | Output apparent power | Active power=3.02KW, Apparent power=4.0KVA [Diagram: Shows LCD segments displaying '3.02 kW' and '4.00 kVA'.] |
4 | Input active power | PV feedback power | active power=800w, feedback power=0w [Diagram: Shows LCD segments displaying '800 W' for input power and '000 W' for PV feedback power.] |
5 | Battery voltage | Load percentage | Battery voltage=50V, Load percentage=80% [Diagram: Shows LCD segments displaying '50.0 V' for battery voltage and '080 %' for load percentage.] |
6 | Charging power | Charging current | Total charging power=1.8KW, Charging current=36A. Icon AC and PV is light showing that AC grid and PV charging battery at the same time. [Diagram: Shows LCD segments displaying '1.80 kW' for charging power and '036 A' for charging current, with AC and PV icons lit.] |
7 | Total PV power | Discharge current | PV power=8.6KW, Battery discharge current is 0 A [Diagram: Shows LCD segments displaying '8.60 kW' for PV power and '000 A' for discharge current.] |
8 | PV1 power | PV2 power | PV1 power =4.5kw, PV2 power =4.3kw [Diagram: Shows LCD segments displaying '4.50 kW' for PV1 power and '4.30 kW' for PV2 power.] |
9 | PV1 voltage | PV1 current | PV voltage=360V, PV current=12A [Diagram: Shows LCD segments displaying '360 V' for PV1 voltage and '012 A' for PV1 current.] |
10 | PV2 voltage | PV2 current | PV voltage=320V, PV current=13A [Diagram: Shows LCD segments displaying '320 V' for PV2 voltage and '013 A' for PV2 current.] |
11 | DAY | Generation power/day | Generation power/day=10KWh [Diagram: Shows LCD segments displaying 'DAY' and '0.10 kW'.] |
12 | MON | Generation power /month | Generation power /month=310KWh [Diagram: Shows LCD segments displaying 'MON' and '310 kW'.] |
13 | YEA | Generation power /year | Generation power /year=3.6mWh [Diagram: Shows LCD segments displaying 'YEA' and '03.6 W'.] |
14 | TTL | Total generation power | Total generation power=13.6mWh [Diagram: Shows LCD segments displaying 'TTL' and '13.6 W'.] |
15 | Year month day | 2024/03/25 [Diagram: Shows LCD segments displaying date '24 03 25'.] |
|
16 | Hour second minute | 16:25 03s [Diagram: Shows LCD segments displaying time '16 03 25'.] |
|
17 | Max lithium battery charging voltage | Max lithium battery charging current | Only communication between the inverter and battery is successful, communication successful icon LI will be flashing, there is some information showing on the LCD [Diagram: Shows LCD segments displaying 'BATT 56.0 V' and 'BATT 040 A'.] |
18 | Model code Version part1 | Model code Version Part2 | Model code Version Part3 [Diagram: Shows LCD segments displaying '240 3 201'.] |
19 | Model code Version part1 | Model code Version Part2 | Model code Version Part3 [Diagram: Shows LCD segments displaying '19 00 60'.] |
20 | CPU type | HD | Hardware Version [Diagram: Shows LCD segments displaying '000 Hd 000'.] |
16 | xx1:Indicating that lithium battery charging is prohibited; x1x: Indicating that the lithium battery is prohibited; 1xx: Indicating that the lithium battery requires forced charging [Diagram: Shows LCD segments 'BATT 000' and '001'.] |
||
17 | Lithium battery SOC(%) | 099% [Diagram: Shows LCD segments 'BATT 099%'.] |
Fault Reference Code
There are seven groups about fault code; a fault code consists of group code and number; group code is first and number is last, such as C0.
- A: Inverter group fault code
- B: battery group fault code
- C: PV group fault code
- D: Output group fault code
- E: Parallel group fault code
- F: Other group fault code
- G: Grid group fault code
Fault Code | Fault Event | Icon on |
---|---|---|
A0 | Output short circuited. | [ERROR Icon] |
A1 | Output voltage is too high. | [ERROR Icon] |
A2 | Over current or surge | [ERROR Icon] |
A3 | Over DC voltage in AC output | [ERROR Icon] |
A4 | Inverter current offset is too high | [ERROR Icon] |
A5 | Output voltage is too low | [ERROR Icon] |
A6 | Inverter negative power | [ERROR Icon] |
B0 | Battery voltage is too high | [ERROR Icon] |
B1 | DCDC over current | [ERROR Icon] |
B2 | DC/DC current offset is too high | [ERROR Icon] |
C0 | PV over current | [ERROR Icon] |
C1 | PV over voltage | [ERROR Icon] |
C2 | PV1 current offset is too high | [ERROR Icon] |
C3 | PV2 current offset is too high | [ERROR Icon] |
D0 | Overload time out | [ERROR Icon] |
D1 | Op current offset is too high | [ERROR Icon] |
F0 | Over temperature of inverter module | [ERROR Icon] |
F1 | Over temperature of PV module | [ERROR Icon] |
F2 | Over temperature of DCDC module | [ERROR Icon] |
F3 | Bus voltage is too high | [ERROR Icon] |
F4 | Bus soft start failed | [ERROR Icon] |
F5 | Bus voltage is too low | [ERROR Icon] |
Warning Indicator
There are seven groups about warning code; a warning code consists of group code and number; number is first and group code is last, such as 0C.
- A: Inverter group fault code
- B: battery group fault code
- C: PV group fault code
- D: Output group fault code
- E: Parallel group fault code
- F: Other group fault code
- G: Grid group fault code
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
0B | Battery low | Beep once every second | [06 Icon] |
1B | Battery is not connected | None | [16 Icon] |
2B | Battery equalization | None | [26 Icon] |
3B | Battery low and it isn't up to the setting value of program 06 of F2 group | Beep twice every 3 seconds | [36 Icon] |
4B | Lithium battery communication is abnormal | Beep once every 0.5 second | [46 Icon] |
5B | Battery discharge overcurrent | None | [56 Icon] |
1C | PV energy is too weak | Beep twice every 3 seconds | [1C Icon] |
0D | Overload | Beep once every 0.5 second | [0D Icon] |
1D | Output power derating | Beep twice every 3 seconds | [1D Icon] |
0F | Temperature is too High | Beep three times every second | [0F Icon] |
BATTERY EQUALIZATION
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.
1. How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods:
- Setting equalization interval in program 37.
- Active equalization immediately in program 39.
2. When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.
[Diagram Description: A charging stage graph showing voltage levels over time. It depicts stages: BULK, ABSORPTION, FLOAT, EQUALIZE, and FLOAT again. Equalize Voltage is shown as the highest level, followed by Absorption Voltage, and then Float Voltage.]
3. Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
[Diagram Description: A charging stage graph similar to the previous one, but specifically highlighting 'Equalize Charging Time'. It shows BULK, ABSORPT., FLOAT, and EQUALIZE stages, with a duration indicated for the EQUALIZE stage.]
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
SETTING FOR LITHIUM BATTERY
Lithium Battery Connection
If choosing lithium battery for the inverter, you are allowed to use the lithium battery only which we have configured. There are two connectors on the lithium battery: RS485 port of BMS and power cable.
Please follow below steps to implement lithium battery connection:
- Assemble battery terminal based on recommended battery cable and terminal size (same as Lead acid, see section Lead-acid Battery connection for details).
- Connect the end of RS485 port of battery to BMS(RS485) communication port of inverter.
[Diagram Description: Shows the rear panel of the inverter with ports labeled, including 'WIFI(OPTIONAL)', 'AC INPUT', 'AC OUTPUT', 'POS BATTERY NEG-', and communication ports like 'RS485'.]
Lithium battery communication and setting
If choosing lithium battery, make sure to connect the BMS communication cable between the battery and the inverter. This communication cable delivers information and signal between lithium battery and the inverter. This information is listed below:
- Re-configure charging voltage, charging current, and battery discharge cut-off voltage according to the lithium battery parameters.
- Have the inverter start or stop charging according to the status of lithium battery.
Connect the end of RS485 of battery to RS485 communication port of inverter
Make sure the lithium battery RS485 port connects to the inverter is Pin to Pin; the communication cable is inside of the package and the inverter RS485 port pin assignment is shown as below:
Pin number | RS485 Port |
---|---|
PIN1 | RS485-B |
PIN2 | RS485-A |
PIN7 | RS485-A |
PIN8 | RS485-B |
Setting for PYLON US2000 lithium battery
1. PYLONTECH US2000 lithium battery setting:
Dip Switch: There are 4 Dip Switches that set different baud rate and battery group address. If switch position is turned to the "OFF" position, it means "0". If switch position is turned to the "ON" position, it means "1".
- Dip 1 is "ON" to represent the baud rate 9600.
- Dip 2, 3 and 4 are reserved for battery group address.
- Dip switch 2, 3 and 4 on master battery (first battery) are to set up or change the group address.
NOTE: "1" is upper position and "0" is bottom position.
[Diagram Description: Shows a row of four dip switches labeled 1, 2, 3, 4. Switch 1 is shown in the 'ON' position. Below this, a diagram shows the rear panel of a lithium battery unit with RS485 and CAN ports.]
2. Process of install
- Step 1. Use the RS485 cable to connect the inverter and Lithium battery.
- Step 2. Switch on Lithium battery.
[Diagram Description: Shows the lithium battery unit with RS485 cable connected and the power switch in the 'ON' position.]
- Step 3. Press more than three seconds to start Lithium battery; power output ready.
- Step 4. Turn on the inverter.
- Step 5. Be sure to select battery type as "Li2" in LCD program 5. If communication between the inverter and battery is successful, the battery icon [Li Icon] on LCD display will light.
[Diagram Description: Shows the lithium battery unit with RS485 cable connected, power switch ON, and a 'READY' indicator.]
Setting for lithium battery without communication
This suggestion is used for lithium battery application and to avoid lithium battery BMS protection without communication; please finish the setting as follow:
A. Recommended method 1: Set battery type as "LIB" in program 01 of F2;
B. Recommended method 2: Setting as follow:
- Before starting setting, you must get the battery BMS specification:
A. Max charging voltage
B. Max charging current
C. Discharging protection voltage - Set battery type as "LIB" in program 01 of F2;
- Set C.V voltage as Max charging voltage of BMS-0.5V in program 03 of F2;
- Set floating charging voltage as C.V voltage in program 03 of F2;
- Set Low DC cut-off voltage ≥ discharging protection voltage of BMS+3V;
- Set Max charging current in program 09 of F2 which must be less than the Max charging current of BMS.
- Setting voltage point back to utility source when selecting "SBU priority" in program 05 of F2.
The setting value must be ≥ Low DC cut-off voltage+2V, or else the inverter will have a warning as battery voltage low.
Remark:
- You'd better to finish setting without turn on the inverter (just let the LCD show, no output);
- When you finish setting, please restart the inverter.
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | 8.5KW | 11.0KW |
---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±7V (UPS) 90Vac±7V (Appliances) |
|
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
|
High Loss Voltage | 280Vac±7V | |
High Loss Return Voltage | 270Vac±7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short Circuit Protection | Battery mode: Electronic Circuits | |
Efficiency (Line Mode) | >95% (Rated R load, battery full charged ) | |
Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated. | [Diagram Description: A graph showing Output Power vs. Input Voltage. The curve shows Rated Power up to 90V, then drops to 50% at 90V, increases to Rated Power at 170V, and stays at Rated Power until 280V Input Voltage.] | |
Output power derating: When battery voltage drops to 50.5V(8.5K)/ 55.0V(11K), the output power will be derated. | 8.5KW Output power derating [Diagram Description: A graph showing Output Load vs. Battery Voltage. The curve shows Rate Power from 50.5V to 42.0V, then drops to Rate Power*0.75 from 42.0V down to a lower voltage.] |
11.0 KW Output power derating [Diagram Description: A graph showing Output Load vs. Battery Voltage. The curve shows Rate Power from 55.0V to 42.0V, then drops to Rate Power*0.75 from 42.0V down to a lower voltage.] |
Table 2 Inverter Mode Specifications
INVERTER MODEL | 8.5KW | 11.0KW |
---|---|---|
Rated Output Power | 8.5KVA/8.5KW | 11.0KVA/11.0KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 60Hz or 50Hz | |
Peak Efficiency | 94% | |
Overload Protection | 5.5s@≥140% load; 10.5s@100%~140% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 48Vdc | |
Cold Start Voltage | 46.0Vdc | |
Low DC Warning Voltage Just for AGM and Flooded |
@ load < 20% @20% ≤ load < 50% @ load ≥ 50% |
44.0Vdc 42.8Vdc 40.4Vdc |
Low DC Warning Return Voltage Just for AGM and Flooded |
@ load < 20% @ 20% ≤ load < 50% @ load ≥ 50% |
46.0Vdc 44.8Vdc 42.4Vdc |
Low DC Cut-off Voltage Just for AGM and Flooded |
@ load < 20% @ 20% ≤ load < 50% @ load ≥ 50% |
42.0Vdc 40.8Vdc 38.4Vdc |
Table 3 Charge Mode Specifications
INVERTER MODEL | 8.5KW | 11.0KW | |
---|---|---|---|
Utility Charging Mode | Charging Current (Max) (AC+PV) | 140Amp | 160Amp |
AC Charging Current (Max) | 120Amp (@ VI/P=230Vac) | ||
Bulk Charging Voltage | Flooded Battery: 58.4Vdc AGM / Gel Battery: 56.4Vdc |
||
Floating Charging Voltage | 54Vdc | ||
Overcharge Protection | 63Vdc | ||
Charging Algorithm | 3-Step | ||
Charging Curve | [Diagram Description: A graph showing Battery Voltage, per cell, and Charging Current, % over Time. It illustrates the 3-Step charging process: BULK (Constant Current), ABSORPTION (Constant Voltage), and MAINTENANCE (Floating). The curve shows voltage rising during BULK, staying constant during ABSORPTION, and dropping during FLOAT, while current decreases over time.] | ||
Solar Input | Rated Power | 5000W*2 | 5500W*2 |
Max. PV Array Open Circuit Voltage | 500Vdc | ||
PV Array MPPT Voltage Range | 60Vdc~500Vdc | ||
Max. MPPT Charge Current | 140A | 160A | |
Max. Input Current | 18A*2 | 18A*2 |
Table 4 General Specifications
INVERTER MODEL | 8.5KW | 11.0KW |
---|---|---|
Safety Certification | CE | |
Operating Temperature Range | -10°C to 55°C | |
Storage temperature | -15°C~ 60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension(D*W*H), mm | 540x403x122 | |
Net Weight, kg | 14.4 | 14.8 |
TROUBLE SHOOTING
Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
---|---|---|---|
Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low | 1.Re-charge battery. 2.Replace battery. |
No response after power on. | No indication. | 1.The battery voltage is far too low. 2.Battery polarity is connected reversed. |
1.Check if batteries and the wiring are connected well. 2.Re-charge battery. 3.Replace battery. |
Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
When the unit is turned on, internal relay is switched on and off repeatedly. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1.Check if AC wires are too thin and/or too long. 2.Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
Green LED is flashing. | Set "SBU" or "SUB" as the priority of output source. | Change output source priority to Utility first. | |
Buzzer beeps continuously and red LED is on. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
Fault code D0 | Overload error. The inverter is overload 100% and time is up. | Reduce the connected load by switching off some equipment. | |
Fault code A2 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
Fault code F2 | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
Fault code B0 | Battery is over-charged. | Return to repair center. | |
Fault code A1/A5 | The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | |
Fault code F3/F4 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
Fault code A2 | Internal components failed. | Return to repair center. | |
Fault code F5 | Over current or surge. | Restart the unit; if the error happens again, please return to repair center. | |
Fault code A3 | Bus voltage is too low. | If the wires is connected well, please return to repair center. | |
Another fault code | Output voltage is unbalanced. | Return to repair center. |