ROOM THERMOSTAT T6360
HEATING CONTROLS
FEATURES
- Dual diaphragm temperature sensing element
- Suitable for surface or switch box mounting
- Heat anticipator for close temperature control
- 10 to 30°C setpoint range
- Change-over contact switching (cooling loads)
- Double insulated
OPTIONS
- Temperature setback model
- Tamper resistant model
- Model with indicator lamp
- Setting dial marked 1 to 5
- High current rated model
- Range stops
APPLICATION
The T6360 is a mains voltage Room Thermostat designed to give automatic temperature control of domestic wet central heating systems. It can be used to directly switch a circulating pump or boiler, or to operate spring return and motor open/motor close zone valves. The T6360 can switch electrical heating loads up to 10A. The T6360 thermostat can also be used for cooling applications.
INSTALLATION
The T6360 thermostat must be located where it is not subjected to extraneous heat gains, direct sunlight or draughts. Fixing screws are supplied for either surface or flush mounting box.
SPECIFICATIONS
Voltage Rating | 230VAC, +/-10%, 50…60Hz |
Switch Rating (Terminal 3) | 10A resistive, 3A inductive |
Switch Rating (Terminal 4) | 6A resistive, 2A inductive |
Switch Type | Single pole, double throw (SPDT) |
Temperature Setting Range | 10 to 30°C |
Temperature Control Accuracy | ± 0.5°C at 3°K/hour with anticipator |
Storage Conditions | -20 to 55°C |
Humidity | 10 to 90% RH, non-condensing |
Standards | CE marked |
EC Directive | EN60730-1 (1995), EN55014-1 (1997), EN55014-2 (1996) |
DIMENSIONS (mm)
The thermostat has a main body measuring 84mm in width and 84mm in height, with a depth of 37mm.
ORDERING SPECIFICATION
- T6360B1028: Standard model complete with heat anticipator and RFI suppressor
- T4360B1015: High current rated version with SPST switching and rated at 16A (resistive). Without heat anticipator
- T6360B1069: As standard model but with tamper resistant cover and setting dial
- T6360B1036: As standard model but with indicator lamp on front cover which is lit on a call for heat
- T6360B1085: As standard model but with setting dial marked 1 to 5
- T4360E1018: Model with temperature setback heater (fixed at 6°C) and SPST switching, complete with anticipator heater and RFI suppressor
- F42007562-001: Accessory footprint for use when replacing T6060 thermostats
- F42006646-001: Bag assembly containing 20 range stops and installation instructions
- F42007110-001: Opaque tamperproof dial cover
- TG510A1001: Lockable, clear plastic thermostat cover. Backplate and spare keys included.
WIRING
T6360B Wiring: Features terminals 1, 2, 3, 4. Terminal 3 is rated 10(3)A max, and Terminal 4 is rated 6(2)A max. A heating load is connected between terminals 3 and 4. The diagram indicates a 230V 50Hz supply. Note: Switching contacts are shown in the normally open position (no heat demand). Typical heating loads include motorised valves.
T4360B Wiring: Features terminals 1, 2, 3. Terminal 3 is rated 16A max. A heating load is connected between terminals 3 and 1. The diagram indicates a 230V 50Hz supply. Typical heating loads include electric heaters.
T4360E Wiring: Features terminals 1, 2, 3, 5, 6. Terminals 5 and 6 are for a setback heater. Terminals 1, 2, 3 are for the main heating load. Terminal 3 is rated 10(3)A max. A heating load is connected between terminals 3 and 2. The diagram indicates a 230V 50Hz supply. Typical heating loads include motorised valves.