Trane RTWD and RTUD Chillers R'newal Service Program Kit Installation Instructions

This document provides installation instructions for the R'newal Service Program Kit for Trane RTWD and RTUD Chillers. It is intended for use by the Trane sales and service organization in support of the R'newal service program.

Safety Warnings

WARNING: Only qualified personnel should install and service this equipment. Improper installation or servicing can lead to death or serious injury. Always observe all precautions in the literature and on equipment tags, stickers, and labels.

WARNING: Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. Follow requirements in NEC and local/state/national electrical codes.

WARNING: Failure to wear proper Personal Protective Equipment (PPE) for the job could result in death or serious injury. Technicians MUST use appropriate PPE, including cut-resistant gloves/sleeves, butyl gloves, safety glasses, hard hats, fall protection, electrical PPE, and arc flash clothing, as specified in Safety Data Sheets (SDS) and OSHA guidelines.

WARNING: Follow EHS Policies! Failure to follow instructions could result in death or serious injury. All Trane personnel must follow company Environmental, Health and Safety (EHS) policies. Non-Trane personnel should always follow local regulations.

Important Environmental Concerns

Trane advocates responsible handling of all refrigerants. Certain man-made chemicals, including CFCs and HCFCs, can affect the earth's stratospheric ozone layer. Trane supports the use of industry replacements for CFCs and HCFCs, such as HFCs and HCFCs, and emphasizes responsible management practices.

Important Responsible Refrigerant Practices

All technicians handling refrigerants must be certified according to local rules. In the USA, the Federal Clean Air Act (Section 608) mandates requirements for handling, reclaiming, recovering, and recycling refrigerants and related equipment. Adhere to all applicable laws and regulations.

Model Number Descriptions

The R'newal model number breakdown provides details for RTWD and RTUD chillers. An example model number is structured as follows:

Installation

Refer to current unit installation, operation, and maintenance literature for detailed procedures, rigging instructions, and additional information.

Table 1: Complete contents of RTWD/RTUD R'newal kit 022102530100

Part #QuantityDescription
0185037901001LABEL; PRINTED NAMEPLATE W/TRANE LOGO
ADP003722ADAPTER; 0.63 OD TUBE FOR OIL LINE CONNECTION
ADP009092ADAPTER; 0.38 OD TUBE X 7/16-20 SAE, O-RING SEAL HEX
COL037804COIL; HOLDING, 120V, 50/60 HZ (AMG 120/50-60)
COL047234COIL; SOLENOID VALVE, 120V/60 & 110V/50 HZ
COL119342COIL; AMC 120V SOLENOID 36" LEAD
CPL009342COUPLING; (INCLUDES ORING & TEFLON SEAL)
FTG001301 cartonFITTING; ACCESS, HALF UNION TYPE, 1/4" MPT OR 5/16" OD SOLDER, 6 PER CARD
GKT028244GASKET-ADAPTER,SUCTION SERVICE VALVE, NON-ASBESTOS R-123 COMPATIBLE, 0.06 THK X 2.84 OD X 2.28 ID. (PIPE SIDE)
GKT036592GASKET; 0.031 x 3.22 x 2.53, CHLOROPRENE (NON-ASBESTOS) W/ANTI-STICK COATING ONE SIDE
GKT036606GASKET; 0.031 x 4.16 x 3.38, CHLOROPRENE (NON-ASBESTOS) W/ANTI STICK COATING ONE SIDE
HTR020472HEATER; ELECTRIC, 150W, 120V
HTR040152HEATER; SUBM.OIL SEP 125W
KIT076142KIT; LIQUID LINE FILTER, (R134A) INCLUDES TWO FILTER SHELL GASKETS (THROW AWAY THE INCORRECT GASKET) AND ONE FILTER CORE.
PART-SVN216*-EN1LITERATURE; RTWD/RTUD R'NEWAL
RNG013972O-RING; 0.364 ID X 0.070 RD
RNG014122O-RING; 4.609 ID X 0.139 RD
RNG014142O-RING; 5.109 ID X 0.139 RD
RNG014152O-RING; 6.234 ID X 0.139 RD
RNG014271O-RING; 17.455 ID X 0.275 RD
RNG014282O-RING; 19.455 ID X 0.275 RD
RNG014412O-RING; 1.171 ID X 0.116 RD
RNG014432O-RING; 15.955 ID X 0.275 RD
RNG015532O-RING; 0.755 ID X 0.097 RD
RNG016972O-RING; 0.351ID X 0.072 RD
RNG017642RING-O; 0.924 ID X 0.116 RD
RNG018382O-RING; UNIFORM SIZE #248, 4.734 ID x 0.139 RD
RNG018562O-RING; NEOPRENE, 15.475 ID X 0.275 RD
RNG019212O-RING; 12.975 ID X 0.275 RD, NEOPRENE
RNG019223O-RING; 14.975 ID X 0.275 RD, NEOPRENE
RNG019232O-RING; 1.475 ID X 0.118 RD, NEOPRENE
RNG019383RING; O-RING - NEOPRENE, 17.955 ID X 0.275 RD
RNG019392RING; NEOPRENE O-RING, 5.484 ID X 0.139 RD
RNG019422RING; O-RING NITRILE, 1.359 ID X 0.139 RD, (USE W/R-134A & 'POE' OILS) UNIFORM SIZE #220
SWT023772CONTRL; HIGH PRESS CUTOUT
SWT031772SWITCH; HIGH PRESSURE CUTOUT
-1LABEL; NAMEPLATE, SERIES R R'NEWAL (BRASS)

Note: This kit includes parts for various unit sizes; some parts may not be required for your specific unit.

Table 2: RTWD general component location

Graphic CalloutPart #UnitQuantity
Condenser (see Figure 1, p. 10)
1RNG01441All unit sizes2
2RNG01856 SUPPLY080, 090, 100, 110, 120, 130, 1401
RNG01938 SUPPLY150, 160, 180, 200
RNG01428 SUPPLY220, 250
3RNG01922 RETURN080, 0901
RNG01856 RETURN100, 110, 120, 130, 140
RNG01938 RETURN150, 160, 180, 200
RNG01428 RETURN220, 250
4RNG01923All unit sizes2
Evaporator (see Figure 2, p. 10)
5RNG01922 SUPPLY080, 100, 110, 120, 130, 140, 1501
RNG01921 SUPPLY090
RNG01427 SUPPLY160, 220, 250
RNG01443 SUPPLY180, 200
5RNG01922 RETURN080, 100, 110, 120, 130, 140, 1501
RNG01921 RETURN090
RNG01938 RETURN160, 220, 250
RNG01443 RETURN180, 200
6RNG01764All unit sizes2
7ADP00372All unit sizes2
Unit Front (see Figure 3, p. 11)
8RNG01838080, 090, 1001
RNG01414110, 120, 130, 140, 150, 200, 220, 250
RNG01939160, 180
9RNG01838080, 0901
RNG01414100, 110, 120, 130, 140, 150
RNG01939160, 180, 220
RNG01415200, 250
10COL04723All unit sizes2
11COL11934All unit sizes1
12SWT03177All unit sizes1
13HTR02047All unit sizes1
14COL04723All unit sizes2
15COL11934All unit sizes1
16SWT03177All unit sizes1
17HTR02047All unit sizes1
18GKT02824080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
19GKT02824080, 090, 1001
GKT03660110, 120, 130, 140, 150
20GKT02824080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
21GKT02824080, 090, 1001
GKT03660110, 120, 130, 140, 150
22HTR04015All unit sizes2
23GKT03659080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
24GKT03659080, 090, 1001
GKT03660110, 120, 130, 140, 150, 160, 180, 200, 220, 250
Unit Back (see Figure 4, p. 12)
25KIT07614All unit sizes2
26FTG00130All unit sizes1
27COL03780All unit sizes2
28COL03780All unit sizes2
29ADP00909All unit sizes2
30CPL00934All unit sizes2

Table 3: RTUD general component location

Graphic CalloutPart #UnitQuantity
Evaporator (see Figure 2, p. 10)
5RNG01921 SUPPLY080, 090, 1001
RNG01922 SUPPLY110, 120, 130, 140, 150
RNG01443 SUPPLY160, 180, 200, 220, 250
5RNG01921 RETURN080, 090, 1001
RNG01922 RETURN110, 120, 130, 140, 150
RNG01443 RETURN160, 180, 200, 220, 250
6RNG01764All unit sizes2
7ADP00372All unit sizes2
Unit Front (see Figure 3, p. 11)
8RNG01412080, 0901
RNG01414100, 110, 120, 130, 140, 150, 160
RNG01939180, 200
RNG01415220, 250
9RNG01412080, 0901
RNG01414100, 110, 120, 130, 140, 150, 160, 180
RNG01939200, 220
RNG01415250
10COL04723All unit sizes2
11COL11934All unit sizes1
12SWT02377All unit sizes1
13HTR02047All unit sizes1
14COL04723All unit sizes2
15COL11934All unit sizes1
16SWT02377All unit sizes1
17HTR02047All unit sizes1
18GKT02824080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
19GKT02824080, 090, 1001
GKT03660110, 120, 130, 140, 150, 160, 180, 200, 220, 250
20GKT02824080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
21GKT02824080, 090, 1001
GKT03660110, 120, 130, 140, 150, 160, 180, 200, 220, 250
22HTR04015All unit sizes2
23GKT03659080, 0901
GKT03660100, 110, 120, 130, 140, 150, 160, 180, 200, 220, 250
24GKT03659080, 090, 1001
GKT03660110, 120, 130, 140, 150, 160, 180, 200, 220, 250
Unit Back (see Figure 4, p. 12)
25KIT07614All unit sizes2
26FTG00130All unit sizes1
27COL03780All unit sizes2
28COL03780All unit sizes2
29ADP00909All unit sizes2
30CPL00934All unit sizes2

Diagram Descriptions

Figure 1: Condenser (RTWD only) - This figure illustrates the condenser unit, showing various components labeled with numbers corresponding to parts in the tables.

Figure 2: Evaporator (RTWD shown; RTUD is similar) - This figure displays the evaporator unit, indicating component locations with numerical callouts that align with the parts lists.

Figure 3: Unit Front (RTWD shown; RTUD is similar) - This diagram shows the front of the unit, highlighting key components and their corresponding part numbers and quantities.

Figure 4: Unit Back (RTWD shown; RTUD is similar) - This illustration depicts the rear of the unit, detailing the placement of various parts with numerical references.

Models: PART-SVN216B-EN, RTWD, Water Cooled Chiller, RTWD Water Cooled Chiller, Chiller, RTUD

File Info : application/pdf, 16 Pages, 1.60MB

PDF preview unavailable. Download the PDF instead.

PART-SVN216B-EN 02112022 Acrobat Distiller 21.0 (Windows)

Related Documents

Preview BACnet Communication Interface for Chiller (BCI-C) Integration Guide
This guide provides information on the BACnet Communication Interface for Chillers (BCI-C), a non-programmable communications module that allows HVAC equipment to communicate on a BACnet network. It covers the BACnet protocol, rotary switches and LEDs, data point definitions, and chiller model compatibility.
Preview Trane Multi-Speed Heat Pumps and Air Conditioners Installer's Guide
This installer's guide from Trane provides comprehensive instructions for the safe and effective installation of Trane Multi-Speed Heat Pumps and Air Conditioners, including model series 5TWX and 5TTX, covering safety, refrigerant handling, electrical, and system setup.
Preview Trane 5TWR4 Heat Pumps: Installation and Operation Manual
Comprehensive guide for installing and operating Trane's 5TWR4 series heat pumps. Covers safety, unit setup, refrigerant handling, electrical connections, troubleshooting, and performance specifications.
Preview Trane Single Packaged Heat Pump, Priority, Two Stage, Convertible, 2-5 Ton, R-454B Product Data and Specifications
Comprehensive product data, specifications, optional equipment, and safety information for Trane's 2-5 Ton Single Packaged Heat Pump systems (R-454B). Details include model numbers (5WCZ5024-5WCZ5060), performance metrics, mechanical features, installation clearances, and available accessories for commercial and residential applications.
Preview Trane Link Variable Speed Air Conditioners: Product Data, Specs & Features
Comprehensive product data, mechanical specifications, sound data, optional accessories, and model nomenclature for Trane Link Variable Speed Air Conditioners (4TTV7X24A1000A, 4TTV7X36A1000A, 4TTV7X48A1000A, 4TTV7X60A1000A). Includes rating conditions and system requirements.
Preview Trane Tracer SC+ System Controller and Tracer Synchrony User Interface Product Catalog
A comprehensive product catalog detailing the Trane Tracer SC+ System Controller and its associated Tracer Synchrony User Interface. This catalog covers system architecture, user interface navigation, system control applications, unit control options, hardware components, and specifications. It highlights features such as energy savings, remote access, and support for open protocols like BACnet and LonTalk.
Preview Trane Air-Fi™ Wireless Communications Sensor (WCS) Quick Reference Guide
This guide provides quick reference information for the Trane Air-Fi™ Wireless Communications Sensor (WCS), detailing how to adjust room temperature, system settings, fan speed, manage occupancy, and understand error codes. It includes safety warnings and battery life indicators.
Preview Trane RTAC Rotary Chiller Tracer AdaptiView Display Upgrade Kit Installation Instructions
This document provides detailed installation instructions for the Trane Tracer AdaptiView Display Upgrade Kit for RTAC Rotary Chillers, replacing older DynaView systems. It covers safety, required tools, step-by-step procedures, and integration options.