Copeland Scroll™ Compressor

Large ZX Condensing Unit & EMP Rack for Refrigeration Applications

User Manual

Overview

Emerson is pleased to offer Copeland Scroll Large ZX condensing unit and EMP rack for refrigeration applications.

In addition to 2-9 HP condensing unit, Emerson expands Next Generation ZX platform to 12-20 HP medium temperature and low temperature condensing unit and rack, configuring with digital modulation for best in class energy efficiency and food safety.

Emerson ZX series has been highly successful in global market and enjoys proven success with its energy savings and customer-friendly electronic features.

Disclaimer

Thanks for purchasing Copeland Scroll™ Large ZX Condensing Unit and EMP Rack from Emerson. Large ZX Condensing Unit and EMP Rack exhibit market-leading quality in terms of cooling capacity and operating range, as part of product extension for Next Generation ZX platform in larger capacity range and installation variants. The product is designed to operate reliably and to deliver high operating efficiencies in medium and low temperature refrigeration applications. It also provides constant monitoring of the compressor operating conditions and displays the running or fault conditions of the condensing unit or rack.

In order to ensure the safe and reliable operation of the unit and rack, the installation of Large ZX Condensing Unit and EMP Rack must comply with industry standards. The selection, installation and maintenance of Large ZX Condensing Unit and EMP Rack must be carried out by professionals. This user manual does not include all industry guidelines for the installation of refrigeration equipment. For loss caused by inexperienced or untrained personnel or due to wrong installation design, it will not be a reasonable reason for responsibility.

If you have any questions, please contact the local sales office for unit or rack type and serial number on the nameplate for consultation. For example, the wiring diagram supplied with each unit or rack takes precedence over the wiring diagram in this manual if any discrepancy occurs, please refer to the attached wiring diagram in the unit or rack.

ZX condensing unit introduction

ZX series condensing units have gained market popularity and have achieved great success in the Asian market with their energy-saving and friendly control experience. ZX/ZXB/ZXD/ZXL/ZXLD units in Asia are used on-site by famous end-users and cold chain retailers. ZX platform products have been widely recognized in the global market. Specially developed models have been exported to the United States, Latin America, Europe and the Middle East markets.

Receiving your unit

All units are filled with dry nitrogen at a positive pressure before transportation. The unit and package are clearly labeled. The unit shut-off valve is equipped with a maintenance interface to check the unit pressure maintenance.

Caution!

When you receive a unit from Emerson or an authorized representative, it is very important to check the pressure of each unit. If it is found that packing pressure has disappeared, please contact Emerson or an authorized representative. Failure to report this may cause subsequent failure reports to be unobstructed.

Damage to the unit caused by the transport process should fall within the category of insurance claims and not be a manufacturing defect. It is also advisable to inspect the rest of the unit for obvious physical damage and inform Emerson or an authorized representative in case any is discovered.

ZX Platform Condensing Unit and EMP Rack were designed based on three factors demanded by industry users:

Intelligent Store

Highest efficiency

Reliability

Nomenclature

Large ZX Condensing unit

Copeland Scroll™ Compressor technology

Configured with CoreSense™ Controller

Emerson unique digital technology

Enhanced vapor injection

Design features

EMP Scroll rack

Scroll rack family Condensing unit family Base model Electrical code Bill of material
LD = Digital low temp
D = Digital medium temp
LD = Digital low temp
D = Digital medium temp
ZX 160 B E TFD 551 12 to 20 HP Generation EMP D 160 E TFD 110 12 to 20 HP E = Ester Oil
TFD = 380V/420V-3ph-50 Hz
110 = With canopy
120 = Without canopy

Bill of material

Model ZXD120 ZXLD120 ZXD160 ZXLD160 ZXD200 ZXLD200 EMPD120E EMPLD120E EMPD160E EMPLD160E EMPD200E EMPLD200E
BOM 551 581 521 551 581 521 551 581 521 551 581 521 551 581 521 651 110 120 110 120 110 120 110 120 110 120 110 120
Liquid line filter dryer/ moisture indicator
Liquid receiver
Pressure relief valve on liquid receiver
Oil separator (w/ reservoir)
Oil filter
Accumulator
LP transducer
HP transducer
HP Pressure gauge
LP Pressure gauge
Fixed LP switch
Adjustable LP switch
Fixed HP switch
CoreSense™ controller
Digital modulation
Fan speed control
Sound jacket
Low ambient kit
Electronic oil level protective control
Service valves
Discharge line check valve
Suction line header
Discharge line header
Vapor injection
Liquid injection
Emergency mode
Liquid level protection (Sensor to be added)
Remote condenser
Canopy

Envelope

Large ZX Condensing unit

ZXD Digital medium temperature

Maximum suction gas temperature: 18.3°C

Fan speed control function for lower than 10°C ambient

Evaporating temperature °C

Note: ZXD120/160BE maximum evaporating temperature is 0 °C; ZXD200BE maximum evaporating temperature is -4 °C

ZXLD Digital low temperature

Maximum suction gas temperature: 5°C

Fan speed control function for lower than 10°C ambient

Evaporating temperature °C

Note: ZXLD120BE maximum evaporating temperature is 0 °C; ZXLD160/200BE maximum evaporating temperature is -4 °C

EMPD/EMPLD Envelope

EMPD Digital medium temperature

Maximum suction gas temperature: 18.3°C

Evaporating temperature °C

Note: EMPD120/160BE maximum evaporating temperature is 0 °C; EMPD200BE maximum evaporating temperature is -4 °C

EMPLD Digital low temperature

Maximum suction gas temperature: 18.3°C

Evaporating temperature °C

Note: EMPLD120BE maximum evaporating temperature is 0 °C; EMPLD160/200BE maximum evaporating temperature is -4 °C

Technical data

Large ZX condensing Unit

HP 12 16 20
Product series ZXD120BE-TFD ZXLD120BE-TFD ZXD160BE-TFD ZXLD160BE-TFD ZXD200BE-TFD ZXLD200BE-TFD
Nominal horsepower HP 12 16 20
Powered by 3PH-380V-50 Hz 1PH-220V-50 Hz ET/CT/RGT/SC OK Max SC Max SC Max SC Max SC Max SC
Performance R404A ET/AT/RGT °C -6.7/32/18.3 -32/32/5 -6.7/32/18.3 -32/32/5 -6.7/32/18.3 -32/32/5
Capacity kW 23.8 13.5 29.0 15.5 37.3 17.4
COP W/W 2.37 1.40 2.40 1.32 2.31 1.40
Sound pressure level @1m dB(A) 69 69 72
Rated load ampere A 9.6+10.1 11.1+11.1 11.1+11.1 14.6 + 14.6 14.6+14.6 14.6+14.6
Locked rotor ampere A 74 74 74 102 102 121
Compressor Oil type POE POE
Oil charge volume L 1.9+1.8 1.9+1.9 1.9 + 1.9 1.9+1.9 1.9+1.9 1.9+1.9
Number of fan 2 2 3 4 4 4
Fan diameter mm 590 590 600 600 600 600
Fan motor Air flow rpm m³/h 850 19280 850 19280 860 23400 950 23400 950 23400 950 23400
Total fan motor power W 950 950 1350 1350 1350 1350
Mounting hole mm 1090×980 (4 - Φ12.0) 1090×980 (4 - Φ12.0) 1619×1010×1124 1619×1010×1124 2033×857×1913 2033×857×1913
Oil separator oil charge L 2.5 2.5 6 6 6 6
Receiver volume L 17 17 17 17 17 17
Dimension (WxDxH) mm 1619 x 1010 x 1124 1619x1010x1124 2033 x 857 x 1913 2033 x 857 x 1913 2033 x 857 x 1913 2033 x 857 x 1913
Weight (net) kg 357kg 362kg 362kg 362kg 550kg 550kg
Weight (gross) kg 457kg 462kg 462kg 462kg 600kg 600kg

Large ZX condensing Unit

Model name EMPD120E EMPLD120E EMPD160E EMPLD160E EMPD200E EMPLD200E
Nominal HP HP 12 16 20
Compressor
Performance R404A ET/AT/RGT °C -6.7/32/18.3 -32/32/5 -6.7/32/18.3 -32/32/5 -6.7/32/18.3 -32/32/5
Capacity kW 12.7 29.2 16.9 37.6 18.5
COP W/W 1.40 2.69 1.51 2.67 1.56
Sound pressure level @1m dB(A) 67 66 66 70 72 72
Rated load ampere A 14.6+14.6 21.1 22.2 23.8 29.2 29.2
Locked rotor ampere A 74 74 100 100 100 100
Compressor Oil type POE POE
Oil charge volume L 1.9+1.9 1.9+1.9 1.9+1.9 1.9+1.9 1.9+1.9 1.9+1.9
Number of fan 3 3 4 4 4 4
Fan diameter mm 600 600 600 600 600 600
Fan motor Air flow rpm m³/h 860 23400 860 23400 950 23400 950 23400 950 23400 950 23400
Total fan motor power W 1350 1350 1350 1350 1350 1350
Mounting hole mm 1800×777 (6 - Φ14.0) 1800×777 (6 - Φ14.0) 1800×777 (6 - Φ14.0) 1800×777 (6 - Φ14.0) 1800×777 (6 - Φ14.0) 1800×777 (6 - Φ14.0)
Oil separator oil charge L 2 2 2 2 2 2
Receiver volume L 40 40 40 40 40 40
Dimension (WxDxH) mm 1619x1010x1124 1619x1010x1124 2013x858x988 2013x858x988 2013x858x988 2013x858x988
Weight (net) kg 244 254 258 262 290 290
Weight (gross) kg 324 334 338 342 370 370

Physical layout

The following picture shows the outline of 12-16HP Large ZX condensing unit.

Oil observation window

Moisture indicator observation window

Figure 1. 12-16HP Large ZX layout

The normal oil level should be lower than the upper observation port, but higher than the lower observation port. If the oil level is lower than the lower observation port, replenish oil immediately. When the unit is running, replenish from the unit's suction service valve using a high pressure oil gun.

Digital compressor

Fixed compressor

Electronic oil control

Oil filter

Filter drier

Accumulator (LT unit only)

Liquid receiver

Oil separator (reservoir)

Discharge check valve

Check valve

PHE (except for ZXD120BE)

EXV valve (except for ZXD120BE)

Upper oil sight glass

Lower oil sight glass

Moisture indicator

Figure 2. Main components of 12-16HP Large ZX

The following picture shows the outline of 12-16HP EMP Scroll Rack.

Liquid level alarm

Oil observation window

Pressure safety valve

Liquid receiver

Figure 5. EMP Rack layout

CoreSense™ controller view window

Moisture indicator observation window

High/Low pressure gauge

Fix speed compressor

Digital compressor

Electronic oil control

Oil filter drier

Dischage line check valve

Oil separator (reservoir)

Suction accumulator (Low temp model only)

Suction header

Compressor discharge service valve

Upper oil sight glass

Lower oil sight glass

Moisture indicator

Electronic expansion valve

Plate heat exchanger (except EMPD120E)

HP & LP gauge

Core type liquid filter drier

Figure 6. Main components of EMP Rack

The following pictures shows the outlines of 20HP Large ZX condensing unit and EMP scroll rack.

Fan motor terminal box

CoreSense™ controller view window

Liquid level alarm light (EMP Rack only)

Moisture indicator oberservation window

Fixed speed compressor

Digital compressor

HP guage

LP guage

Fixed speed compressor discharge line check valve

Electronic oil control

Oil filter drier

Moisture indicator

Liquid filter drier

Discharge header

HP guage LP guage

Oil separator observation window

Discharge line check valve

Check valve

Oil Separator

Liquid Receiver

Upper and lower oil level sight glass

Accumulator

Ambinet temperature sensor

Low voltage wire entry loop

High voltage wire entry loop

Liquid line service valve

Suction line service valve

BOM-651 (Large ZX w/ remote condenser)

Separate upper condenser part and lower compressor part, add condenser inlet/outlet service valve

Figure 9. 20HP layout

EMPD/EMPD Scroll rack (w/o condenser)

Offer only lower compressor part, add condenser inlet/outlet service valve

Suction header

Main components for BOM-651 (w/ remote condenser) and EMP Rack (w/o condenser) :

The main components and layout are basically same with outdoor installed version condensing unit

Bigger size oil separator and liquid receiver are configured in the consideration of larger refrigerant charge in system with condenser remotely installed

Pay attention to the location of suction pipe, discharge pipe, liquid pipe and sub-cooled pipe and avoid wrong piping connection

Liquid receiver

Pressure safety valve

Discharge line check valve

Oil separator

Check valve

Discharge pipe (Cond in)

Liquid pipe (Cond out)

Suction pipe (Evap out)

Sub-cooled liquid pipe (Evap in)

Figure 10. 20HP main components

Electrical module

Figure 3. Electrical module of 12-16HP Large ZX

Circuit breaker 1

Circuit breaker 2

Fan speed control

24V Transformer

CoreSense™ controller

Customer terminals

Contactor 1

Contactor 2

Capacitor

Internal terminals

24V Transformer

Figure 7. Electrical module of EMP Rack

Circuit breaker 1

Circuit breaker 2

Fan speed control

Alarm LED

24V Transformer

CoreSense™ controller

Customer terminals

Contactor 1

Contactor 2

Relay

Internal terminals

24V Transformer

Figure 11. 20HP electrical module

CoreSense™ controller

Liquid level alarm light 2 (only for EMP rack)

Emergency mode switch ¹ (only for short time running)

Compressor contactor

Low voltage wire entry loop

Internal terminals

Circuit breaker

Time relay (only for emergency mode)

Customer terminals

High voltage wire entry loop

LED descriptions

LED Status Description LED Status Description
On Compressor 1 is running On Browsing the service menu
Flashing Compressor 1 is ready to start Flashing Browsing the fast access menu
On Compressor 2 is running On A new alarm happened
Flashing Compressor 2 is ready to start Flashing Browsing the alarm menu
On Condensing fan is running¹ On An alarm is occuring
On Digital compressor is unloading On Reserved
Display with C
Flashing Programmable mode Reserved Reserved

Note:

This function is available in Large ZX as standard offering. For EMP rack, this function is available only when customer has connected air cooled condenser fans to rack controller.

Figure 12. 20HP service valve location

Note: Figure 12 list service valve of 20HP outdoor type condensing unit. The condenser inlet and outlet pipe valve are not listed in this picture, for details of these valve location please refer to Figure 10.

Compressor 1 (Digital) suction valve

Compressor 1 (Digital) discharge valve

Compressor 1 (Digital) EVI pipe valve

Compressor 1 (Digital) oil return hand valve

Compressor 2 (Fixed speed) oil return hand valve

Compressor 2 (Fixed speed) suction valve

Compressor 2 (Fixed speed) discharge valve

Suction pipe valve

Compressor 2 (Fixed speed) EVI pipe hand valve

Oil pipe valve

Liquid receiver valve

Condenser valve

Liquid pipe valve

Keyboard descriptions - Single button

SET

Displays target set point; In programming mode, select a parameter or confirm an operation.

Start

Hold for 5 seconds to reset any lockouts if the current state of the controller allow for it to be reset.

Up

Enter the fast access menu; In programming mode, browse the parameter codes or increases the displayed value.

Down

In programming mode it browses the parameter code or decreases the displayed value

Service

Enter the service and alarm menu.

Defrost

Hold for 3 seconds to start a manual defrost or terminate an active defrost (Not available at the moment).

Keyboard descriptions - Combined buttons

SET + ⌂

Press and hold for about 3 seconds to lock (Pon) or unlock (Pof) the keyboard.

SET + ⌃

Pressed together to exit programming mode or menu; under rtC and PAr, this combination allows the user to go back to previous level.

SET + ⌄

Pressed together for 3 seconds allows access to first level of programming mode.

SET + ⌅

Pressed together for 3 seconds allows access to EXV manual setting.

Controller display upon start-up

Step Action Phenomenon and description
1 Power on controller All LEDs will light up for 3 seconds.
2 Firmware version will be displayed for 3 seconds.
3 Parameter setting file (bin file) identifier will be displayed for 3 seconds.
4 Normal display (actual suction saturated temperature will be displayed)

Bin files number range

Bin number range Family
1-200 ZX
201-300 ZXB
301-500 ZXL
501-600 ZXD/ZXLD
601-620 EMPD
621-640 EMPLD

RTC (Real Time Clock) setting

Step Action Phenomenon and description
1 Press SET Enter menu to select PAr (parameter) or rtC
2 Press ⌂ Select rtC
3 Press SET n01, minute
n02, hour
n03, day
n04, month
n05, year (last two digits)
4 Press SET Display actual value
5 Press ⌂ Modify the value
6 Press "SET" Press SET: the value will flash for 3 seconds, then move to the next value
7 Press "SET"+⌂ Exit to rtC
8 Press "SET"+⌃ Exit to main menu (or wait for 120 seconds and exit automatically)

After installation and initial power on, it is critical to double check the parameters below:

Replacing controller

After a new controller is replaced and initial power is on, it is critical to reset parameters defined on the label below the nameplate on the unit panel. Here is an example of a label:

Controller Parameter Default Setting

MODEL Parameter Description Default Value
H01 Digital Compressor MCC 407
H02 Signal Compressor Current Protection 409
H27 Fixed Compressor MCC H27
H28 Fixed Compressor Current Protection H28
H13 MIN. Operating Voltage H13
H14 MAX. Operating Voltage H14
C07* Refrigerant 007*

Notes:*Ensure that parameter [07 is set to match the actual refrigerant used. If not, set [07 following label "Unit Operation Setting After Installation".

Notes: C07 is accessible in Pr1 parameter, and the other parameters are assessible in Pr2 parameter

The step-by-step procedure to access and modify the Pr1 and Pr2 parameters are outlined below:

Pr1 parameter (1st level) browse and modification

Step Action Phenomenon and description
1 Press SET + ⌂ Enter menu to select PAr (parameter) or rtC
2 Press ⌂ Select PAr (parameter)
3 Press "SET" Confirm, select, and browse Pr1 parameters
4 Press ⌂ Browse to Pr1 parameters
5 Press SET View the actual number of the Pr1 parameters
6 Press ⌂ Modify the actual number of the Pr1 parameters
7 Press "SET" Press SET: the number will flash for 3 seconds and confirm the modifications; Will go to the next Pr1 parameter
8 Press SET + ⌃ Exit (or exit automatically after waiting for 120 seconds)

Pr2 parameter (2nd level) browse and modification

Step Action Phenomenon and description
1 Press SET + ⌂ >3 seconds Enter Menu to select PAr (parameter) or rtC, enter into parameter browse & setting mode.
2 Press ⌂ Select PAr (parameter)
3 Press SET Confirm above selection & display Pr1 level parameters
4 Press ⌂ Find parameter "t18"
5 Press SET "PAS" will flash for 3 times, then display "0--", "0" flashes (Prompt to enter pass code "321")
6 Press ⌂ Change value to "3"
7 Press SET Display "30-", "0" flashes
8 Press ⌂ Change value to"2"
9 Press "SET" Display "320", "0" flashes
10 Press ⌂ Change value to “1”
11 Press SET Confirm password & enter into Pr2 level parameter
12 Press ⌂ Browse detailed Pr2 level parameter name
13 Press SET View current parameter setting values
14 Press ⌂ Change parameter setting values
15 Press SET Confirm the changes, changed values flash for 3 times, then display next parameter name
16 Press SET + ⌃ Display "Par", exit parameter browse & setting mode.

Quick access menu browse - Sensor status and actual values

Step Action Phenomenon and description
1 Press ⌂ Enter quick access menu, will display P1P (Press Up or Down to view other sensors)
2 Press SET View the actual value of P1P
3 Press SET Change to next sensor code
4 Press "SET"+⌂ Exit (or exit automatically after waiting for 60 seconds)

Sensor code and values descriptions

P1P Suction pressure sensor

P2P Condensing pressure sensor

P3t Digital compressor discharge line temperature sensor

P4t PHE vapor inlet temperature sensor

P5t PHE vapor outlet temperature sensor

P6t Ambient temperature sensor

P7t ON-OFF compressor discharge line temperature sensor

SH PHE superheat

OPP EXV opening percentage

LLS Solenoid valve status (not used)

Std Condensing temperature set point

Aoo Fan's analog output signal percentage

dso Percentage of PWM output driving the valve of the Digital Scroll compressor

Lt Minimum cold room temperature (unused)

Ht Maximum cold room temperature (unused)

tU1 #1 voltage sensor

tU2 #2 voltage sensor

tU3 #3 voltage sensor

tA1 #1 current sensor

tA2 #2 current sensor

Hm Time menu

(nP, noP, or nA means that the sensor does not exist; Err means that the sensor fails, out of range, disconnected, or does not configure properly)

Access alarm code (Maximum of 50 record)

Step Action Phenomenon and description
1 Press ⌂ Display SEC
2 Press SET Display A01
3 Press ⌂ Display alarm code in A01
4 Press ⌂ Display A02
5 Press ⌂ Display alarm code in A02
6 ... ...
7 Press "SET"+⌂ Exit (or exit automatically after waiting for 15 seconds)

Exact timing of the alarm

Step Action Phenomenon and description
1 Press ⌂ Display SEC
2 Press "SET" Display A01
3 Press ⌂ Display alarm code in A01
4 Press "SET" Display Hr
5 Press ⌂ Display the alarm exact timing: hour
6 Press ⌂ Display Min
7 Press ⌂ Display the alarm exact timing: minute
8 Press ⌂ Display dAy
9 Press ⌂ Display the alarm exact timing: day
10 Press ⌂ Display Mon
11 Press ⌂ Display the alarm exact timing: month
12 Press ⌂ Display YEA
13 Press ⌂ Display the alarm exact timing: year
14 Press "SET"+⌂ Exit (or exit automatically after waiting for 15 seconds)

Upload the parameter settings from the controller to Hot-Key

Step Action Phenomenon and description
1 Insert Hot-key when the controller is on The uPL message will appear followed by a flashing End label (Note: If Err is displayed, it means it failed to upload the program to hot-key. Please restart the process.)
2 Press ⌂
3 Press "SET" End will stop flashing
4 Turn off the controller and remove the Hot-key
5 Turn on the controller

Download the parameter settings from Hot-key to controller

Step Action Phenomenon and description
1 Turn off the controller
2 Insert Hot-key The dol message will blink followed by a flashing End label (Note: If Err is displayed, it means it failed to download the program to Hot-key. Please restart the process.)
3 Turn on the controller Controller will restart working with the new parameters after 10 seconds
4
5 Remove Hot-key

Network wiring

Dixell XWEB300D serial address

Figure 13. Correct network wiring

Figure 14. Incorrect network wiring

Dixell XWEB300D Configuration

XWEB300D is compatible with CDU/Rack if XWEB has the library of Large ZX and EMP Rack CoreSense™ controller.

Login into XWEB

Log in again and setup the ZX CDU/EMP rack

Termination resistor for XWEB300D

If XWEB300D is placed at the beginning or end of the line, please install its termination resistor by adding a jumper in position 2 (JMP2 on the back side of the unit). Do not add the jumper if XWEB300D is placed in the middle of the RS485 line.

Large ZX CDU / EMP Rack connected to XWEB300D

Large ZX CDU/EMP Rack connected to the Dixell XWEB300D with the Intelligent Store Solution module using RS485 Modbus.

Connect the ZX CDU to the ModBUS network as shown on figure 15.

Connect the network cable to the three-terminal connector on the XWEB300D port that has been configured as ModBUS port (COM 12, 13, 14).

Connect port "13" of XWEB300D to port "485 +" of CoreSense™ and port "12" of XWEB300D to port "485 -" of CoreSense for RS485 communication.

Figure 15. XWEB300D connected to the Intelligent Store Solution module

Installation

Electrical connection

Power supply

Large ZX CDU/EMP Rack are delivered with a holding charge of neutral gas. The condensing unit should be located in such a place to prevent any dirt, plastic bag, leaves, or papers from covering the condenser and its fins. The unit must be installed without restricting the airflow. A clogged condenser will increase the condensing temperature, thus reducing the cooling capacity, which leads to a high-pressure switch tripping. Clean the condenser fins on a regular basis.

Large ZX CDU/EMP Rack electrical connection to the power supply must be made by qualified technicians, who should refer to the electrical diagrams located inside the electric connection panel. The units are designed for power supply at ± 10% voltage tolerance. The circuit breaker must be switched off before opening the front panel. The unit must be grounded before electrical use.

Electrical wiring

Before commissioning, ensure the neutral "N" wire is connected to the terminal block ("N" furthest to the right). After proper connection of the ZX condensing unit, the control LED on the power board and control board will light up (see wiring diagrams for more details). Customers' wire size needs to be selected to allow for the maximum operation current of each unit.

Refrigeration piping installation

All interconnecting pipes should be of refrigeration grade, clean, dehydrated and must remain capped at both ends until installation. Even during installation, if the system is left for any reasonable period of time (e.g. two hours), pipes should be re-capped to prevent moisture and contaminants from entering the system.

Do not assume that the service connection sizes on the unit (at the service valves) are the correct size to run your interconnecting refrigeration pipes. The service valve sizes have been selected for convenience of installation, and in some cases (larger units), these may be considered too small. However, for the very short pipes within our units, these service connection sizes are adequate. All interconnecting pipes should be sized to satisfy the duty required.

The suction line of condensing unit or rack must be well insulated. Large ZX and EMP Rack are featured with vapor injection, thus the liquid line must be insulated too, because the liquid line can pick up additional heat from the ambient and adversely affect the sub-cooling desirable for the liquid refrigerant before it enters the expansion valve.

The pipe should be sized to ensure optimum performance and good oil return. The sizing must also take into account the full capacity range through which this particular unit will need to operate.

Pipe runs should be kept as short as possible, using the minimum number of directional changes. Use large radius bends and avoid trapping of oil and refrigerant. This is particularly important for the suction line. The suction line should ideally slope gently towards the unit. Recommendation slope is 1/200~1/250. P traps, double risers and reduced pipe diameters may be required for suction lines where long vertical risers cannot be avoided.All pipes should be adequately supported to prevent sagging which can create oil traps.

The recommended pipe clamp support distance is shown below:

Tube size Max distance between two clamp supports
12.7 mm (1/2 inch) 1.20 m
16.0 mm (5/8 inch) 1.50 m
22.0 mm (7/8 inch) 1.85 m
28.5 mm (1 1/8 inch) 2.20 m
34.93 mm (13/8 inch) 2.44 m

When brazing, the system should be protected with an inert gas such as nitrogen at a very low pressure. Only materials and components approved for refrigeration engineering are suitable.

It is necessary that all impurities (dirt, brazing scale, flux, etc.) are removed from the system before operation to avoid breakdowns. Many of these impurities are so small that they can pass through a filter and enter the suction side of the compressor. Other blockages can occur in the suction filter, and a high pressure drop can cause damage. For this reason, it is strongly recommended the usage of a large suction filter (which causes only a minimal drop of pressure) on all installations which are to be assembled on site in cases where the required cleanliness cannot be guaranteed. The suction filter core is highly recommended to be changed after first time 72 hours commissioning.

For selection of Emerson flow controls STAS filter drier for Large ZX or EMP Rack please contact Application Engineering in your region.

Liquid line insulation

Large ZX and EMP Rack are featured with vapor injection, the liquid line must be insulated with at least 19 mm thick, to avoid sub-cooling loss through heat absorption from ambient.

Brazing recommendations

Maintain a flow of oxgen-free nitrogen through the system at a very low pressure during brazing. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If copper oxidization is allowed to form, the copper oxide material can be swept later through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes. This minimizes any entry of contaminants and moisture.

Recommended brazing materials:

Location and fixing

Large ZX and EMP Rack should always be installed in a location free of other source of heat radiation and not be blown by wind in winter time. The place should have clean air circulation. The minimum operating space for unit or rack are described in below figures. Where multiple units or racks are to be installed in the same location, the contractor needs to consider space for each equipment carefully. The installation location should avoid the affecting to surrounding residents, without air blows directly to residents' windows.

The units or racks should be mounted on a solid concrete slab with anti-vibration pads between unit/rack feet and concrete. When the installation location is easy of water accumulation, the mounting base should have a certain height of cement base station at about 300 mm. At snowy areas, there should be additional cover be installed on top of the unit/rack besides a cement base in the bottom. The snow cover should be mounted at least 1500 mm higher than top of the unit/rack.

Power connection side

Air flow direction

Figure 16. 12-16HP Large ZX fixing

Expansion valve selection for low ambient application

For systems expected to operate in varying ambient conditions - namely summer and winter temperatures - the expansion valve (TXV or EXV) sizing should take into consideration the maximum expected saturated condensing temperature at high ambient conditions (summer) and the minimum expected saturated condensing temperature during low ambient conditions (winter).

The chosen expansion valve's operating capacities should all be well within these limits to ensure satisfactory system performance

The liquid refrigerant from the low temperature ZXLD and EMPLD unit / rack in liquid line is subcooled to very low temperature when it goes through PHE, so system expansion valve selection should take it into consideration. The table below lists the reference liquid line temperature.

R404A Evaporation temperature °C Standard supply temperature °C
20 27 32 38 43 48
-40 -8 -1 3 8 13 19
-35 -4 2 6 11 15 21
-30 0 6 9 13 18 23
-25 5 10 13 17 21 26
-20 9 14 17 20 24 30
-15 13 18 21 24 28 34

Figure 17. 12-16HP EMP Rack fixing

Figure 18. 20HP Unit fixing

Lifting of unit/rack

Condensing unit and rack should always be kept vertical during transportation or operation. Refer to the figures below for the lifting method.

Center line

Center of gravity

Figure 19. 12-16HP Large ZX and EMP rack lifting

Figure 20. 20HP Unit lifting

Start up and operation

Before commissioning, make sure that all valves in condensing unit or rack are fully opened. Make sure that each protector's wiring is normal and in working condition.

Leak detection and pressure holding

During pressure holding, the high pressure should be less than 18 barg, and the low pressure should be less than 12 barg. Vacuum method is also allowed to detect leaks.

Vacuuming

Do not use the compressor to vacuum the system!

The evacuation procedure is based upon achieving an actual system vacuum standard and is not time dependent. Before the installation is put into commission, it has to be evacuated with a vacuum pump. Proper evacuation reduces residual moisture to 50ppm. The installation of adequately sized access valves at the furthest point from the compressor in the suction and liquid lines is advisable. To achieve undisturbed operation, the compressor valves are closed and the system is evacuated down to 0.3 mbar/0.225 Torr. Pressure must be measured using a vacuum pressure (Torr) gauge on the access valves and not on the vacuum pump; this is done to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump.

Before vacuuming, make sure the manual valves are opened. Please refer to the figure on the right, vacuum operation must be performed separately from points A, B and C.

Point A

Point B

Point C (except for ZXD120BE)

Refrigerant charging procedure

The scroll compressor design requires system charging as quickly as possible with liquid refrigerant into the liquid line. This will avoid running the compressor under conditions where there is insufficient suction gas. Sufficient gas is available to cool not only the motor but also the scrolls. Temperature builds up very quickly in the scrolls if this is not done. Do not charge vapor refrigerant into Large ZX condensing unit or EMP Rack. The suction service valves must be fully opened at any time while the compressor is running.

Refrigerant should be fully charged before start-up. The best filling port is at the liquid line service valve. If one-time charge from liquid line is not enough, charging the refrigerant at compressor running may cause to multiple pressure cut off and delayed restart, during which by-pass the low-pressure control and low-pressure protection are prohibited.

For charging adjustment, it is recommended to check the liquid sight glass just before the expansion valve.

For Large ZX unit and EMP rack, configured with PHE sub-cooler, please charge liquid refrigerant from point C. After starting up, you can continue to charge liquid refrigerant from point A. When there is insufficient refrigerant charge, there is gas in the moisture indicator, the controller will show E47 (electronic expansion fully open) or E48 (injection shortage) warnings. After there is no gas bubble in the moisture indicator, please continue to charge about 1 kg of refrigerant.

Oil charging procedure

Emerson Large ZX and EMP Rack are supplied with oil charge in compressor at the factory. Please confirm the oil level in the oil sight glass of the compressor after a short period of trial operation. If the oil level is above half of the sight glass, it can be considered sufficient oil. If oil charging is needed, charge oil through the needle valve port on the suction service valve.

When the length of one-way pipeline exceeds 20m, it is necessary to add oil at mid-glass in the upper oil sight glass of the oil reservoir before unit start up. If the oil level goes down below the lower oil sight glass after system running stable, it is suggested to add oil at least to mid-glass in the lower oil sight glass.

Qualified refrigerant and oil

Refrigerant

Refrigerant Oil
R404A Emkarate RL 32 3MAF
Mobil EAL Arctic 22 CC

Check before starting & during operation

Evaporation temperature (°C)

Oil sump temperature (°C)

Safe Area

Feasible

Insecure area (Excessive cooling diluent)

Evaporation temperature (°C)

Alarm codes

Level Description
Warning The unit (including the compressor) will keep running, but some status & data is already in an unsafe range; alarm dry-contact will not close; reset automatically
Alarm The unit (including the compressor) may run not with full functions; alarm dry-contact will not close; reset automatically
Lock The unit (including the compressor) stops working; alarm dry-contact will close; manual reset is needed

Code Description Possible reasons Action Reset
E01 Suction pressure sensor failure alarm Sensor failure or overrange operates in preset mode Function: fan speed control is disabled Reset automatically when the sensor is working
E02 Condensing pressure sensor failure alarm Sensor failure or overrange Function: discharge temperature protection is disabled Reset automatically when the sensor is working
E03 Digital compressor discharge line temperature sensor failure alarm Sensor failure or overrange Function: PHE superheat control is disabled Reset automatically when the sensor is working
E04 PHE vapor inlet temperature probe failure alarm Sensor failure or overrange Function: PHE superheat control is disabled Reset automatically when the sensor is working
E05 PHE vapor outlet temperature probe failure alarm Sensor failure or overrange Function: PHE superheat control is disabled Reset automatically when the sensor is working
E06 Ambient temperature probe failure alarm Sensor failure or overrange Related functional disabled Reset automatically when the sensor is working
E07 Fixed-speed compressor discharge line temperature sensor failure alarm Sensor failure or overrange Function: discharge temperature protection is disabled Reset automatically when the sensor is working
E09 Current overrange Digital compressor current is larger than settings Current protection function is disabled Reset automatically when the sensor is working
E10 2# current sensor fault alarm Fix speed compressor current is larger than settings Current protection function is disabled Reset automatically when the sensor is working
E11 1# voltage sensor fault alarm Voltage protection disabled Voltage protection disabled Reset automatically when the sensor is working
E12 2# voltage sensor fault alarm Voltage overrange Voltage protection disabled Reset automatically when the sensor is working
E13 3# voltage sensor fault alarm Voltage overrange Voltage protection disabled Reset automatically when the sensor is working
E20 Missing phase alarm One or two phases of the compressor power supply are missing or the voltage sensor is working abnormally The compressor will be tripped Automatically with time delay
L20 Missing phase lock Missing phase alarm happened frequently The compressor will be tripped and the unit will be locked Automatically with time delay
L21 Wrong phase sequence lock Compressor power supply has wrong sequence The compressor will be tripped and the unit will be locked Press "Start" > 5 seconds or manually power cycle

Troubleshooting

Fault phenomenon

Direct cause

Inspection analysis and adjustment

Before the following troubleshooting, first of all ensure the correctness, robustness and reliability of all wiring.

Fault phenomenon Direct cause Inspection analysis and adjustment
1 Compressor does not start The controller did not receive a start signal Check whether the low pressure reaches the low pressure set point
Contactor failure or wiring failure Check terminal No. 3 and NEUTRAL neutral line for 220VAC
Controller failure Check whether the wiring of terminal block No. 3 to controller input DI1 is reliable
Electricity failure Normal shutdown will not start within 3 minutes, waiting time exceeds 3 minutes
The fuse is blown Check whether the contactor coil A1 has 220V AC. If there is 220VAC, check the virtual connection of the compressor terminal and the contactor coil terminal or replace the contactor; if no 220VAC, check if the controller C2 FireWire is connected properly
Air switch trip Replace the controller
Contactor failure Need to confirm that the power supply voltage and waveform are normal
Unit control is in protection status (alarm code display) Replace the fuse and monitor the current after restart
Power supply phase error (L21) Need to confirm whether over current, whether leakage, grounding is normal, whether the air switch itself is faulty
Power Phase Loss (E20 or L20) Need to confirm whether the contact is stuck, whether the starting voltage is insufficient
Three-phase voltage imbalance Check whether it is a true protection action or a malfunction due to a fault code
Compressor Overcurrent (E23/L23: Digital Compressor, E31/L31: Constant Speed Compressor) Refer to Article 14 [Phase of three phases] Related Content
Exhaust pressure too high protection (E40 or L40) Refer to Article 13 [Three-phase phase loss] Related content
Inspiratory pressure too low protection (E41) Need to confirm whether there is a virtual connection of the power line, whether it is used in a phase of high-power single-phase electrical appliances
Excessive exhaust temperature protection (E44/L44: digital compressor, E55/L55: fixed speed compressor) Refer to Article 15 [Overcurrent Errors] Related Content
User-side temperature controller instruction shutdown Refer to Article 2 [Exhaust Pressure High Protection] Related Content
Controller failure or transformer failure Refer to Sections 3, 4 [Insufflation Pressure Protection] Related Content
Built-in compressor protection (E28: digital compressor, E32: fixed speed compressor) Refer to Article 5 [Exhaust temperature protection is too high] Related content
Power supply voltage is too low Need to confirm whether it has reached the temperature set point, whether it enters the defrost program, whether the thermostat is faulty
Capacitor failure Need to confirm the controller display is on replace the controller to see if the fault still exists
Refer to section 1 [Compressor does not start] for detailed system check]
2 Code "E40 or L40" Discharge pressure High protection or lock Shutoff valve or other system valve forgot to open If the high pressure is high (high pressure protection value 30 kg): Shutoff valve or other system valve forgot to open
The ambient temperature is too high or the air intake channel is blocked The ambient temperature is too high or the air intake channel is blocked
Condensing fan is working abnormally Condensing fan is working abnormally
Dirty condenser surface Dirty condenser surface
Too much refrigerant Too much refrigerant
Air inside the system Air inside the system
Over-throttle Over-throttle
High pressure switch failure High pressure switch failure
FireWire to C2 port is open all the way FireWire to C2 port is open all the way
Controller failure Controller failure
Wrong controller Wrong controller
Low pressure switch and wiring fault Low pressure switch and wiring fault
Shutoff valves in the system does not open properly Shutoff valves in the system does not open properly
3 Code "E41" suction pressure Low protection (limited to medium temperature unit) System lack of refrigerant System lack of refrigerant
Abnormal evaporator, heat exchanger is too small Abnormal evaporator, heat exchanger is too small
Expansion valve opening is too small Expansion valve opening is too small
Filter plugging, suction pipe pressure drop too high Filter plugging, suction pipe pressure drop too high
Part selection deviation Part selection deviation
4 Suction pressure is too low If the "E40 or L40" is reported at the same time the fan is not working, please check: 1. If the two fuses next to the contactor are damaged; 2. Check the terminal block and the controller under the line wiring for loose or wrong connection
Controller shows error, replace controller
The controller for medium tempearure unit ZXD and the low temperature unit ZXLD must be used in one-to-one correspondence.
Ensure that the low pressure switch should be closed (turned on) when the low pressure is greater than 1 kg
Check the system valves one by one
Need to confirm whether the charge is insufficient, whether the system leaks. If the system leaks, need to find leak point and handle properly
Need to confirm whether the evaporator fan and the motor are abnormal, whether it is defrosting, defrosting is not clean, whether the drainage is not smooth, and whether the sundries obstruct the airflow passage.
Whether the expansion valve is blocked or if the expansion valve is improperly adjusted. Whether temperature package leaks
Need to confirm whether filter is dirty, if it is blocked by ice, if it needs to be replaced, replace the filter or replace the filter core
Evaporator selection is too small, or the expansion valve selection is too small, or the unit selection is too large. Recheck the load and select the model. Whether medium temperature units are used for low temperature applications
5 Code "E44/L44" Digital compressor discharge gas overheating alarm or locked Low pressure during normal operation Measure operating low pressure. Need to confirm whether the low pressure set in controller is correctly, whether the controller or low pressure switch is faulty. If there is a fault, replace the corresponding device. Also refer to [3. suction pressure Low protection ] Related Content
High pressure during normal operation To measure the operating high pressure, make sure that the high pressure switch is working properly. If there is a fault, replace the corresponding device. Also refer to [2. Discharge pressure High protection Or lock]
Suction superheat is too high Need to confirm whether there is lack of refrigerant, whether the opening of the expansion valve is too small, whether insufficient insulation of the suction pipe
Injection system failure A) The need to confirm whether the electronic expansion valve failure: coil damage, dirty or ice blocking.
B) Need to confirm if the filter before the electronic expansion valve is blocked.
C) It is necessary to confirm whether the inlet/ temperature sensor for PHE is faulty or missing. Refer to the sensor temperature-resistance characteristics table in this manual.
D) It is necessary to confirm whether insufficient charging leads to gas-liquid two-phase in the liquid pipe, so that the injection circuit cannot take liquid properly.
E) Need to confirm if the controller is faulty.
Refrigerant mixed with impurities, refrigerant composition changes Re-evacuation and charge of qualified refrigerant
System lacks of refrigerant 1, the sight glass should be full glass status.
2, the liquid pipe should have sufficient subcooling.
Compressor failure Need to confirm whether the charge is insufficient, whether the system leaks. If leaks need to find leak point and handle properly
Discharge temperature sensor and wiring fault (measured discharge temperature is less than 125 degrees) It is necessary to confirm whether the compressor current corresponds to operating high and low pressure. If not, the compressor may have worn
Expansion valve opening too large Check if the sensor fails and check if the sensor falls out. Refer to the sensor temperature-resistance characteristics table in this manual
Abnormal evaporator, heat exchanger is too small Need to confirm whether the expansion valve is oversized and whether it is excessive opening
Too much refrigerant Need to confirm whether the evaporator fan and the motor are abnormal, whether it is defrosting, defrosting is not clean, whether the drainage is not smooth, and whether the sundries obstruct the airflow passage.
6 The system continues to have liquid, back For non-azeotropic refrigerants, such as R404A, release some of the refrigerant from the stop valve of the liquid tube, and release slowly to prevent excessive loss of the lubricant. For non-azeotropic refrigerants, such as R404A, release some of the refrigerant from the stop valve of the liquid tube, and release slowly to prevent excessive loss of the lubricant.
Suction superheat less than 5K (such as frost o compressor body in medium tempearature unit)
7 Frequent compressors start up If the compressor starts frequently during the defrosting process: Need to confirm whether the unit selection is too large, the expansion valve selection is too small. Consider taking all indoor evaporator synchronization defrosting procedures
Operating suction pressure low due to low load Check if the low pressure rises during stop, replace the corresponding equipment (coil or valve body) when confirming the failure of the solenoid valve.
Leakage of liquid line solenoid valve Measure the pressure change at compressor suction and evaporator outlet during the shutdown process. It may be that the compressor suction pressure has decreased to the stop setting and the evaporator side liquid refrigerant has not completely evaporated. Need to improve piping design
Too much pressure drop in suction piping It is normal phenomenon. At first time start after power on or over 1 hour shut off, the unit is in initial start procedure, during which the compressor will strat up 3 times with 3 seconds running in each time, each time with 20 seconds interval.
If the compressor is frequently started during normal operation: Refer to [Compressor overcurrent], [Discharge pressure high pressure], [Suction pressure too low protection], [Discharge gas overheating] related content for detailed system check
The unit is at initial startup Check if the temperature difference between the start and stop of the thermostat is too small, and whether the thermostat fault frequently issues a stop command. If there is a fault, replace the corresponding device
Frequent compressor protection (alarm code display) Try to replace the controller and see if the fault persists
Thermostat failure Measure operating low pressure. Need to confirm whether the low pressure set is correctly, whether the low pressure switch is faulty? If there is a fault, replace the corresponding device. Also refer to the relevant content of Article 3 [suction pressure Low protection]
Controller failure
Low pressure during normal operation

Fault phenomenon Direct cause Inspection analysis and adjustment
Compressor reverse running Swap any two-phase wiring Swap any two-phase wiring
8 Abnormal noise The compressor is overloaded Check if the high-pressure pressure is running high, whether the low-pressure pressure is low, and whether the pressure ratio is too large.
The compressor oil level is too low or too high Confirm the oil level and perform oil drain or replenishment
Too much refrigerant Release some of the refrigerant from the stop valve liquid line slowly to prevent excessive loss of lubricating oil
Continuous liquid back Check if compressor oil tank temperature is low
System with liquid start Check whether the compressor crankcase heater is working during compressor stops and whether the liquid solenoid valve leaks.
Compressor internal failure Check if the compressor current corresponds to operating high and low pressure. If it is too high, it may indicate that the inside of the compressor may have worn
Unit resonance Try to press each pipe, bracket, housing, condenser, etc., and observe if the noise changes. After confirming the source of noise, reinforce, separate, or add sponge cushions to the corresponding parts.
Unit contacts surrounding objects Ensure that the space around the unit is clean and open, and that the unit body does not touch other objects (such as wires, sundries, etc.)
Unit installation is loose Re-confirm that the feet of the unit are firmly installed, no nuts in loose and no feet are impending
9 Cooling capacity cannot meet load demand Low condensing pressure Low Ambient Kit (BOM-*81) should be selected in extremely low ambient areas, check if the fan speed control is normal
The unit is operating normally Check if the unit operating is normal by checking if high pressure, low pressure, current, discharge temperature, return gas temperature, oil temperature are within a normal range. If yes, it is possible that the outdoor or indoor equipment selection is too small, and the system needs to be redesigned.
Unit protection Refer to above related content for detailed system check
The compressor itself is working abnormally Refer to section 1 [Compressor does not start] for detailed system check]
Flash gas before system expansion valve The liquid line should be full of liquid before expansion valve (sight glass should be installed before the expansion valve)
Liquid supply pipe insulation for units with PHE The liquid supply pipe should be well insulated for units with PHE
System lack of refrigerant 1, the sight glass should be full glass liquid
2, (for units with PHE) The liquid pipe should have sufficient subcooling, check whether the charge is insufficient and whether the system is leaking. If the system leaks, need to find leaking point and fix it
Abnormal application status Check the working status of the evaporator, check if the cooler's door is closed, check the goods temperature when putting into the cooler
10 Controller has no display Circuit breaker cannot be turned on after closing When the breaker is closed, the breaker has 380V input voltage and output voltage Any line-to-neutral voltage is 220VAC
Natural wiring error Whether the two fuses next to the contactor are damaged
Broken fuse Measure whether the transformer input has 220V voltage and whether the output has 24V voltage. If the output is abnormal, replace the transformer.
Transformer damage Power off and power on the unit, after re-start the controller, if the fault disappears, the fault can be ignored. If the fault continues, replace the controller
11 Controller does not work Controller code does not change or garbled Check if the fan blade is damaged
Controller failure Check if fan motor malfunctions
Check if the fan capacitor is damaged
If above causes are excluded, replace the controller
12 The condenser fan is not running, or in abnormal operation Controller H25 parameter setting error Controller H25 parameter setting error
The condensing fan speed control is based on the condensing temperature collected, when condensing temperature sensor failures, will use ambient temperature sensor for speed control, if both sensors fail, the fan will be fully open. Refer to the sensor temperature-resistance characteristics table in this manual
13 Code "E20" or "L20" three-phase phase missing The phase sequence of the unit incoming 3-ph lines is incorrect Check the label of the unit and check whether the parameters of the controller H25 are set correctly. The three-phase power is set to Yes and the single-phase is No. Please pay special attention to this after replacing the controller
14 Code "L21" three-phase phase Fault Controller three-phase error Check the three-phase incoming line of the unit and exchange the two phases of the breaker input line.
Check whether the three-phase input of R, S, T in the lower left corner of the controller is consistent with the phase sequence on the terminal of the compressor (U, V, W). Take special attention when replacing a new controller.

Fault phenomenon Direct cause Inspection analysis and adjustment
15 Code "E28" controller outputs digital compressor operation instructions, No current detected Built-in compressor protection Measure the resistance between the terminals of the compressor to determine if the resistance is infinite and whether the three-phase resistance is balanced. After the compressor is fully cooled, try to start again. If normal operation can be performed again, please refer to [Compressor overcurrent], [Discharge pressure high protection], [Suction pressure low protection] and [Discharge gas overheating] to perform detailed system checks.
Compressor motor burned Measure the resistance between the terminals of the compressor. If it is confirmed that the compressor is faulty, replace the compressor. After restarting, you must refer to [Compressor overcurrent], [Discharge pressure high protection], [Suction pressure low protection], [Discharge gas overheating] to perform detailed system checks.
Compressor mechanical failure Measure the resistance between the terminals of the compressor. If it is confirmed that the compressor is faulty, replace the compressor. After restarting, you must refer to [Compressor overcurrent], [Discharge pressure high protection], [Suction pressure low protection], [Discharge gas overheating] to perform detailed system checks.
16 Code "E23/L23" Digital Compressor Over current alarm or lock Contactor and wiring fault Check the three-phase voltage at the lower end of the contactor to determine whether there is loose or virtual connection, and replace the contactor.
Controller failure Replace the controller.
Controller current protection setting wrong Check whether the controller H07/H09 (digital compressor) and H27/H28 (fix speed compressor) parameter values are consistent with the unit label. Especially when replacing a new controller, adjust the controller parameters to match the unit's labeling requirements.
Code "E31/L31" Fix Speed Compressor Over current alarm or lock Contactor failure Check the three-phase voltage at the lower end of the contactor to determine whether there is loose or virtual, resulting in excessive current due to missing phase.
Internal damage to the compressor Check the actual operating current of the compressor, and determine whether the operating current is too high by refering to the high and low pressures.
17 Code "E03"(digital compressor), "E07"(fix speed compressor) discharge line temperature sensor error Discharge line temperature sensor falls out or is not heat insulated well Check if the temperature sensor is out or the heat insulation is not good
The sensor itself fails It is recommended to replace the temperature sensor directly
18 Code "E01" Suction pressure transducer failure Actual suction pressure exceeds the transducer measuring range Find out why the pressure is abnormal, like if there is no refrigerant in the system, or if the refrigerant is too much, so the pressure in the suction is too high.
Pressure is normal, sensor connection or sensor itself fails Check if the sensor wiring is normal and there is no blockage in the pressure tube where the sensor is located. Try replacing the sensor to see if it can eliminate the fault.
19 Code "L86" Controller internal memory EEPROM is abnormal Controller internal memory is abnormal Check whether the external device has remote communication with the controller, and whether there is any abnormality in the remote communication wiring and signal transmission. If the signal continues to be written into the controller, it will cause its memory to be damaged, and each writing requires a write completion instruction. Try to restart the controller if it can be solved. After the above troubleshooting, if the controller is still abnormal, replace the controller.

Temperature sensor resistance table

Temperature (°C) -30 -10 25 60 80 100 120
Discharge line temperature sensor resistance (Ω) 1522k 457k 86k 21k 11k 5.8k 3.4k
Condensing tempreature, PHE vapor inlet and outlet temeprature and ambient temperature sensor resistance (Ω) 111k 67.7k 42.5k 27.3k 17.9k 10k 5.82k

Wiring diagram

ZXD160, ZXLD120/160 Condensing unit

ZXD120 Condensing unit

ATTENTION:Unit Must Be Grounded!

ZXD120 Condensing Unit Wiring Diagram

TFD - 380/420V, 50Hz, 3Ph

NOTES:

1. Dashed line " " is wired by installer.

2. Neutral "N" and Earth "E" wirings are not shown in harnesses for clarity.

EMPD/EMPLD Rack Wiring Diagram

TFD-380/420V, 50Hz, 3Ph

NOTES:

1.Dashed line "--" is wired by installer.

2. Neutral "N" and Earth "E" wirings are not shown in harnesses for clarity.

20HP wiring diagram

ZXD/ZXLD Condensing Unit Wiring Diagram

TFD-380/420V, 50Hz, 3Ph

NOTES:

1. Dashed line "--" is wired by installer.

2. Neutral "N" and Earth "E" wirings are not shown in harnesses for clarity.

3. The Paddle Switch only SHORT-TERM in emergency situation.

WIRE COLOR NOTE:

BU--Blue

BK-Black

OG-Orange

BN---Brown

GNYE--Yellow/Green

YE--Yellow

WH--White

RD-Red

General information

Technical data are correct at the time of printing. Updates may occur, and should you need confirmation of a specific value, please contact Emerson clearly stating the information required.

Emerson cannot be held responsible for errors in capacities, dimensions, etc., stated herein. Products, specifications and data in this literature are subject to change without notice.

The information given herein is based on data and tests which Emerson believes to be reliable and which are in accordance with today's technical knowledge. It is intended for use by persons having the appropriate technical knowledge and skill, at their own discretion and risk. Emerson's products are designed and adapted for fixed locations. For mobile applications, failures may occur.

The suitability for this has to be assured from the plant manufacturer, which may include making appropriate tests.

Note: The components listed in this catalogue are not released for use with caustic, poisonous or flammable substances. Emerson cannot be held responsible for any damage caused by using these substances.

About Emerson

Emerson (NYSE: EMR), headquartered in St. Louis, Missouri (USA), is a global technology and engineering company providing innovative solutions for customers in industrial, commercial, and residential markets. Emerson's Automation Solutions business helps process, hybrid, and discrete manufacturers maximize production, protect personnel and the environment while optimizing their energy and operating costs. Emerson's Commercial and Residential Solutions business helps ensure human comfort and health, protect food quality and safety, advance energy efficiency, and create sustainable infrastructure. For more information visit Emerson.com.

Notes

Models: Copeland Scroll Compressor, Large ZX Condensing Unit EMP Rack for Refrigeration Applications

File Info : application/pdf, 31 Pages, 6.60MB

PDF preview unavailable. Download the PDF instead.

user-manual-large-zx-condensing-unit-emp-rack-for-refrigeration-applications-en-sg-6221866

References

Adobe PDF Library 15.0

Related Documents

Preview Copeland Scroll ZX Condensing Unit User Manual
User manual for the Copeland Scroll ZX Condensing Unit, covering features, installation, operation, and troubleshooting for refrigeration applications.
Preview Copeland Large ZX Condensing Unit User Manual
Comprehensive user manual for the Copeland Large ZX Condensing Unit, covering installation, operation, safety, troubleshooting, and technical specifications. Includes details on CoreSense controller, networking, and system start-up procedures.
Preview Copeland™ Compressors and Condensing Units for Refrigeration Applications
Explore the comprehensive range of Copeland™ compressors and condensing units designed for various refrigeration applications. This brochure details product lines including ZX, KHZ, F-Series, Semi-Hermetic, Multi-Compressor Racks, and Water-Cooled units, highlighting their features, specifications, and applications.
Preview Copeland Intelligent Store Solutions: Boosting Convenience Store Expansion & Efficiency
Discover how Copeland Intelligent Store Solutions helped a leading online-to-offline (O2O) convenience store chain exceed its expansion targets, improve operational efficiency, and achieve significant energy savings through advanced refrigeration and store management systems.
Preview Groupes de Condensation Copeland ZX : Guide d'Installation Abrégé
Ce guide fournit des informations essentielles pour l'installation et la configuration des groupes de condensation Copeland série ZX, en se concentrant sur le régulateur XMC25D et ses paramètres. Découvrez les fonctions des LED et les procédures de configuration.
Preview Copeland Scroll ZSI Compressor for Refrigeration Applications
Comprehensive catalog detailing Copeland Scroll ZSI compressors for refrigeration applications, featuring CoreSense technology, liquid injection, performance tables, technical data, and application guidelines.
Preview Copeland Scroll Compressors ZR24KRE-ZR190KRE Application Guidelines
Emerson's Copeland Scroll™ compressors (ZR24KRE to ZR190KRE) application guidelines detail installation, operation, safety, and troubleshooting for comfort, precision, and process cooling. Essential for system designers and technicians.
Preview Groupes de réfrigération extérieurs Copeland ZX - Guide d'installation abrégé
Guide d'installation abrégé pour les groupes de réfrigération extérieurs Copeland ZX, couvrant les étapes d'installation, la configuration du régulateur XMC25D, la description des indicateurs LED, et un menu détaillé des alarmes et de leurs causes/actions.