Components for system solutions
MCB Miniature circuit breaker
Model: 8530/1-MCB-STA103-C6-000-3
Art. No.: 272175
Key Features
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Modular design for simple replacement or expansion
- Easy installation on mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching
- Padlocks (Accessories) provide protection against being switched on again during maintenance work
Product Overview
R. STAHL 8530 series miniature circuit breakers are overcurrent devices offering excellent current limiting for short circuits and a high switching capacity of 10, 15, or 25 kA. This design minimizes load on cables and ensures high selectivity for upstream fuses. The components feature a modular design, available in 1- to 4-pole versions and for rated currents of 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Technical Data
Explosion Protection
Application range (zones) | 1, 2 |
Application range (Zone) note | For use in Zone 21/22 when protected by Ex tb/tc enclosure |
IECEx gas certificate | IECEx FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certificate | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Declaration of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Rated operational voltage AC | 230/400 V |
Rated operational current | 6 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | without |
1st auxiliary function for AC rated voltage | - |
1st auxiliary function for rated current max. | - |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 3-pole |
Ambient Conditions
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature note | Deviating ambient temperatures based on current certificates available on request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplast |
Connection cross section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Min. tightening torque | 2 N·m |
Max. tightening torque | 3 N·m |
Connection cross-section note | 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16/10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions. |
Dimensions
Width | 83 mm |
Width, inches | 3.27 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm |
Mounting depth in inches | 5.44 in |
Weight | 1.4 kg |
Weight | 3.087 lb |
Mounting / Installation
Tightening torque | 2-3 N·m |
Tightening torque lbf in | 17.7 to 26.6 lbf-in |
Tightening torque auxiliary contact | 0.4-0.6 N·m |
Tightening torque auxiliary contact lbf in | 3.5 to 5.3 lbf in |
Technical Drawings
Tripping Characteristic C: The document includes a graph illustrating the tripping characteristic 'C' for AC and DC, showing the relationship between multiples of rated current and tripping time in seconds and minutes. This is crucial for understanding the breaker's response to overcurrents.
Dimensional Drawings: Detailed diagrams show the physical dimensions of the circuit breaker in millimeters and inches. These include overall width, length, and mounting depth, along with specific details for 3-pole configurations and connection points.
Accessories
4-way locking device
A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
Art. No.: 227232
Cylinder lock
For closing (bracket Ø 3)
Art. No.: 107115
Fastening set
A fastening set for fastening the component on the mounting plate without a DIN rail.
Art. No.: 276618
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com