Installation Guide ICAD 600A/ICAD 1200A Quick Start Guide

1. Installation Steps

Before you start using ICAD:

⚠️ 24 Volt DC ONLY

Apply Grease as shown.

▶️ Push down the unit.

? Note! Cross tighten all 3 screws to ensure equal tightening. Max 3 Nm torque.

2. Wiring and Connections

The terminal box is not supplied by Danfoss.

Terminal Box Connections:

Ref.ColourDescription
ABlackCommon Alarm
BBrownICM fully open
CRedICM fully closed
DOrangeGND ground
EYellow+ 0/4–20 mA Input
FGreen+ 0/2–10 V input or digital input for on/off control
GBlue+ 0/4–20 mA Output
IBlack+ Fail safe supply Battery / UPS* 19 V DC
IIWhite+ Supply voltage 24 V DC
IIIBrown24 V DC

* Uninterruptable Power Supply

3. Cable Voltage Drop Considerations

Please observe cable voltage drop. Distance between the applied DC transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at all time at the ICAD terminal box*, both during standstill and during operation of ICAD, is within this range:

Prefabricated ICAD cable lengthCode numberMin. [V DC]Max. [V DC]
1.5 m027H04262126.4
3 m027H04382226.4
10 m027H04272326.4
15 m027H04352426.4

* Do not measure inside the ICAD itself.

⚠️ 24 Volt DC ONLY

4. Programming the ICAD

Note: If the keypad is not operated within 20 seconds, timeout will automatically exit programming mode.

Valve size setup (mandatory)

When powering up the ICAD, A1 will flash in the display.

Steps:

  1. Hold [2s] to enter programming mode.
  2. Press [▼] to parameter 10.
  3. Press [Edit/Enter].
  4. Press [▲] until parameter 11 (password).
  5. Press [Edit/Enter].
  6. Press [▲] until parameter 26.
  7. Press [Edit/Enter].

Select ICM size or CVE:

  • 1: ICM 20 with ICAD 600A
  • 2: ICM 25 with ICAD 600A
  • 3: ICM 32 with ICAD 600A
  • 4: ICM 40 with ICAD 1200A
  • 5: ICM 50 with ICAD 1200A
  • 6: ICM 65 with ICAD 1200A
  • 7: ICM 100 with ICAD 1200A
  • 8: ICM 125 with ICAD 1200A
  • 9: ICM 150 with ICAD 1200A
  • 10: CVE pilot with ICAD 1200A

Press [Edit/Enter] to select ICM size or CVE.

The display will show "ICM/CVE & ICAD is now calibrating".

? NOTE! If media temperature is lower than -30 °C (-22 °F) it is mandatory to set parameter i30 an i31. See separate document attached in ICAD box: document number AN285243155312.

Changing analogue input signal (optional)

Steps:

  1. Hold [2s] to enter programming mode.
  2. Press [▼] until parameter 03.
  3. Press [Edit/Enter].
  4. Press [▼] or [▲] to select analogue input signal.
  5. Press [Edit/Enter].

Available input signals:

  • 1: 0–20 mA
  • 2: 4–20 mA*
  • 3: 0–10 V
  • 4: 2–10 V

* default factory setting

The display will show "; 03" after selection.

? If A3 alarm occurs, the analogue input signal is out of range.

5. Factory reset of ICAD

Steps:

  1. ⚡ Disconnect power.
  2. Press [▼] and [▲] simultaneously while reconnecting power.
  3. Release [▼] and [▲].

? Note: If factory reset has been performed, the ICAD will start flashing A1 in the display.

For further functions, programming possibilities and factory settings, please see ICAD instruction.

⚠️ 24 Volt DC ONLY

Models: 600A, 1200A, ICAD 600A ICAD 1200A Electric Gear Drive, ICAD 600A ICAD 1200A, Electric Gear Drive, Gear Drive

PDF preview unavailable. Download the PDF instead.

AN213086423355en-000301 Danfoss A/S GPL Ghostscript 10.03.1

Related Documents

Preview Danfoss ICAD 600A/1200A Quick Start Guide: Installation and Programming
A concise guide for installing and programming Danfoss ICAD 600A and ICAD 1200A industrial valve actuators, covering setup, wiring, voltage considerations, and factory reset.
Preview Danfoss ICM/ICAD Motorized Valves: Installation, Programming, and Troubleshooting Quick Start Guide
A comprehensive guide for the installation, programming, and troubleshooting of Danfoss ICM/ICAD Motorized Valves, covering valve identification, wiring, parameter settings, and common issues.
Preview Danfoss ICAD 600A/600A-TS/1200A Actuator Installation Guide
This document provides a comprehensive installation guide for Danfoss ICAD 600A, ICAD 600A-TS, and ICAD 1200A actuators. It covers electrical connections, mechanical installation, parameter settings, and troubleshooting for these advanced actuators used with ICM, ICMTS, and CVE valves.
Preview Danfoss ICAD 600A/1200A Quick Start Guide
A quick start guide for installing and programming the Danfoss ICAD 600A and ICAD 1200A electronic expansion valve controllers, including wiring, setup, and factory reset procedures.
Preview Danfoss ICM 20-65 Motor Operated Valve Installation Guide
This guide provides detailed instructions for the installation, operation, and maintenance of the Danfoss ICM 20-65 motor-operated valve. It covers essential information regarding refrigerants, temperature and pressure ranges, technical data, installation procedures, welding, manual operation, insulation, surface treatment, assembly, tightening, and maintenance.
Preview Danfoss ICAD 600A / ICAD 1200A Quick Start Guide
A quick start guide for the Danfoss ICAD 600A and ICAD 1200A electronic control units, covering initial setup, programming, and factory reset procedures.
Preview Danfoss ICM & ICAD: Motor Operated Valves and Actuators for Industrial Refrigeration
Explore Danfoss's ICM motor-operated valves and ICAD actuators, designed for efficient and reliable performance in industrial refrigeration systems. Learn about features, applications, and technical specifications.
Preview Danfoss ICMTS Motor Operated Valve with ICAD 600A-TS Actuator: Installation Guide
This installation guide provides detailed instructions for the Danfoss Motor Operated Valve Type ICMTS with Actuator Type ICAD 600A-TS. It covers refrigerant compatibility, temperature and pressure ratings, technical data, installation procedures, welding and soldering guidelines, manual operation, insulation, surface treatment, assembly, and maintenance. Designed for high-pressure R744 applications, this valve is suitable for various industrial refrigeration systems.