RTAM MINI RCBO 6kA 1P+N (Switched Neutral)

Instruction Leaflet DOC:RCBOMINI2022

Product Images and Dimensions

The document displays images of the RTAM MINI RCBO unit, showing its compact design and connection terminals. Dimensional drawings indicate the unit's size, with key measurements provided: 47.3mm width, 69.5mm height, and 43.7mm depth. The wiring diagram illustrates the connection points for Line (L), Neutral (N), and Load (L OUT, N OUT), along with the incoming supply and outgoing load connections.

Technical Information

Series RTAM
Rating (A) 6, 10, 16, 20, 25, 32, 40
Tripping curve B, C
Number of Poles 1P + N (switched neutral)
Residual Operating Current(ΙΔη) 30mA
Type A
Voltage(V) 230V
Frequency 50/60Hz
Rated short circuit capacity 6kA
IP RATING IP20 EN 60529
Torque 2.5Nm / 1.2Nm
Maximum cable capacity 16mm² (Lin) 10mm² (Lout Nout)
Neutral cable length 450mm (can be cut to suit)
Complies with IEC 61009-1, IEC 61009-2-2

MINI RCBO Series (RTAM) Description

The MINI RCBO with switched LINE and NEUTRAL is designed for protection against overload, short circuit, and earth leakage. It is Type A, suitable for AC and pulsating DC sensitivity, with a short circuit capacity of 6kA and a maximum rating of 40A. Its compact size enhances working space within FuseBox consumer units, simplifying installation, connection, and testing. The flying neutral cable can be cut to size but must be terminated.

Testing Note: Line and Neutral conductors do not need to be disconnected for IR (insulation resistance) testing if the lever is in the OFF position.

Neutral Cable CSA

6A 2.5 mm²
10A 2.5 mm²
16A 2.5 mm²
20A 2.5 mm²
32A 4.0 mm²
40A 4.0 mm²

Installation and Connections

  1. RCBO must be installed by a qualified electrician in accordance with the current IET Wiring Regulations BS 7671.
  2. Total load must not exceed the rating of the RCBO or any additional limitation.
  3. Installation:
    • RCBO range designed to fit FuseBox consumer units and modular enclosures.
    • 35mm top hat din rail mounting.
    • Clip securely onto the din rail, ensuring the din rail clip at the bottom is pushed in, locking the RCBO onto the din rail. Ensure the lever is in the OFF position.
    • Cut, dress, and connect cables as shown in the wiring diagram.
    • Line (Lin) terminal connects to the bus bar.
    • Neutral flying lead connects to the neutral terminal bar (can be cut to size).
    • Connect the load to the L OUT and N OUT terminals at the top of the RCBO. Connect the Load earth to the terminal bar.
  4. Connections:
    • Before powering up the circuit, check all connections are TORQUED. Loose connections can cause fires.

Testing

  1. CONNECTIONS TO THE MINI RCBO DO NOT REQUIRE TO BE DISCONNECTED IF THE LEVER IS IN THE "OFF" POSITION.
  2. On completion of the installation, it must be tested in accordance with the latest edition of the IET Wiring Regulations for Electrical Installations (BS 7671).

Operation of the TEST button on RCBO

If newly fitted systems do not trip on the TEST button or using an RCD tester, the problem is normally caused by an earth to neutral fault on the circuit (PME supply). Installers can check the RCBO by removing the LOAD connections and applying power. If the TEST button works, the fault is in the circuit.

RCBO TEST

RCBOS ARE MANUFACTURED IN ACCORDANCE WITH IEC 61009-1 AND MUST BE TESTED TO THIS SPECIFICATION USING A CALIBRATED TEST METER.

General type RCBO will not trip RCBO must trip within
0.5ΙΔη 300ms
1Δη 40ms
51Δη

What to do if a RCBO trips

  1. Reset tripped RCBO to ON position.
  2. If RCBO trips again, disconnect all appliances connected to this circuit.
  3. Switch RCBO to ON position and connect 1 appliance at a time to see which one trips the RCBO.
  4. Once the faulty appliance has been identified, DO NOT USE appliance until it has been checked.
  5. Switch RCBO to ON position.
  6. If fault does not clear, phone a qualified electrician to check installation.

Environment

WASTE ELECTRICAL PRODUCTS SHOULD NOT BE DISPOSED OF IN HOUSEHOLD WASTE. CONTACT YOUR RETAILER OR LOCAL AUTHORITY FOR RECYCLING INFORMATION.

Visit www.fusebox.co.uk

After installation and testing of this product it is essential that the INSTRUCTION LEAFLET is available for reference.

Models: 1PN Switched Neutral, 1PN, Switched Neutral, Neutral

File Info : application/pdf, 2 Pages, 254.12KB

FuseBox-MINI-RCBO-1PN-SW-Instruction-leaflet-2022

References

Microsoft Word for Microsoft 365

Related Documents

Preview FuseBox MINI RCBO 6kA 2P Type A Technical Data Sheet
Detailed technical specifications, part numbers, dimensions, and tripping characteristics for the FuseBox 2021 MINI RCBO 6kA 2 pole (B CURVE) TYPE A series (6A-40A). Includes compliance and connection details.
Preview FuseBox 2024 MINI AFDD/RCBO Technical Data and Installation Guide
Detailed technical specifications, installation, and testing information for the FuseBox 2024 MINI AFDD/RCBO (Arc Fault Detection Device/Residual Current Circuit Breaker with Overcurrent Protection). Includes ratings, tripping curves, wiring, and LED indicators for electrical safety.
Preview FuseBox 3P+N 10kA RCBO: Technical Data, Specifications, and Installation Guide
Comprehensive technical datasheet for FuseBox 3P+N 10kA RCBOs (Type A, B & C curves). Includes specifications, part numbers, dimensions, installation, and testing procedures.
Preview FuseBox 3P + N 10kA RCBO - Technical Specifications
Detailed technical specifications for the FuseBox 3-pole + Neutral 10kA RCBO, including electrical features, part numbers, and performance characteristics. Available in Type A, 06A to 50A.
Preview FuseBox F3 Series Consumer Unit User Guide & Installation
Official user guide for FuseBox F3 Series consumer units. Provides essential installation, technical, safety, and troubleshooting information for electricians and users.