ComfortStar TIP24/CHF24CD(O) 24,000 BTU/H Heat Pump Submittal Data Sheet

System Overview

Model: TIP24/CHF24CD(O)

System Description: 24,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Certifications: AHRI Certified, UL Listed, CULUS Listed

System Performance Data

Power Supply

Normal Operational Voltage: 208/230V, 1 Phase, 60 Hz

Voltage Range: 187-253 V

Electrical

Minimum Circuit Ampacity: 25.0 A

Max. Fuse: 35.0 A

Connection Wiring: 14 AWG

Cooling Performance

ParameterValue
Rated Capacity24000 Btu/h
Capacity Range8000~25000 Btu/h
Power Input (Max)2182 W
Rated Current8.5 A
SEER220.5 Btu/W
EER211.0 Btu/W

Heating at 47F

ParameterValue
Rated Capacity25000 Btu/h
Capacity Range111840~27000 Btu/h
Power Input (Max)2093 W
Rated Current9.8 A
HSPF2-411.5 Btu/W
HSPF2-59.2 Btu/W
COP3.50 W/W

Heating at 17F

Max Capacity: 24100 Btu/h

Refrigerant Pipe Data

ParameterValue
Design Pressure550/340 PSIG
Refrigerant TypeR410A/91.7 Oz
Refrigerant Precharge25.0 ft (7.6 m)
Additional Charge per ft0.32 oz/ft (30 g/ft)
Liquid Side / Gas Side Pipe Size3/8" / 5/8" (9.52/15.9 mm)
Max. Pipe Length164.0 ft (50.0 m)
Max. Difference in Level82.0 ft (25.0 m)
Connection MethodFlared

Indoor Unit Data

Indoor Fan Motor

ParameterValue
TypeCross-Flow
ModelZKFN-45-8-1
Qty1
Input72 W
RLA- A
LRA- A
Winding Resistance- Ω
Capacitor- uF
Speed (Hi/Mi/Lo)680/624/568/512 r/min

Air Flow & Noise Level

Indoor Air Flow (Hi/Med/Lo) (No duct): 705.88/635.29/547.06 CFM

Indoor Noise Level (Hi/Med/Lo): 48/45.5/43 dB(A)

Dehumidification

Capacity: - Pint/H

Indoor Unit Dimensions

Dimensions (WxDxH): 32.68x32.68x8.07 inches (830x830x205 mm)

Packing Dimensions (WxDxH): 35.83x35.83x9.84 inches (910x910x250 mm)

Net/Gross Weight: 47.18/55.34 lbs. (21.4/25.1 kg)

Diagram Description: Illustration showing the physical dimensions and mounting points of the indoor unit, depicting its shape and fan. A table within the diagram provides specific dimensions (A, B, C, D) for 24K, 36K, and 48K capacities in millimeters and inches.

Outdoor Unit Data

Compressor

Type: DUAL ROTARY

Model: KTM240D43UKT

Brand: GMCC

Capacity: 25932.27641 Btu/h

Input: 2045 W

Rated Current (RLA): - A

Refrigerant Oil/Oil Charge: Capillary +EXV

Throttle: - ml

Outdoor Fan Motor

ParameterValue
ModelZKFN-120-8-2
Qty1
Input- W
RLA- A
Speed1150/1050/900/850 r/min

Air Flow & Noise Level

Outdoor Air Flow (Max.): 2235.30 CFM

Outdoor Noise Level: 62 dB(A)

Outdoor Unit Dimensions

Dimensions (W×D×H): 37.24x16.14x31.89 inches (946x410x810 mm)

Packing Dimensions (W×D×H): 42.91x19.69x34.84 inches (1090x500x885 mm)

Net/Gross Weight: 134.48/144.40 lbs. (61/65.5 kg)

Diagram Description: Illustration showing the physical dimensions and mounting points of the outdoor unit, with key measurements provided in inches and millimeters.

General Features

Diagram Description: Illustration detailing the wiring connection port area, showing locations for electrical connections, panel, external water pump, hanger mounts, refrigerant pipe connections (liquid and gas), and a drain hole.

PDF preview unavailable. Download the PDF instead.

Submittal TIP-24CHF24CDO-Single-zone-Light-comercial-SEER2-20221014 Acrobat Distiller 19.0 (Windows)

Related Documents

Preview ComfortStar FPA-24/CZP24CD(O) Submittal Data Sheet - 24,000 BTU/H Wall Mounted Heat Pump System
Comprehensive submittal data sheet for the ComfortStar FPA-24/CZP24CD(O) 24,000 BTU/H Wall Mounted Heat Pump System. Details include system performance, electrical specifications, cooling and heating capacities, refrigerant data, indoor and outdoor unit specifications, and general features.
Preview ComfortStar TPA-18/CZP18CD(O) Submittal Data Sheet - 18,000 BTU/H Heat Pump System
Submittal data sheet for the ComfortStar TPA-18/CZP18CD(O) wall-mounted heat pump system, detailing system performance, indoor and outdoor unit specifications, refrigerant pipe data, and general features. Includes electrical, cooling, and heating capacities, airflow, noise levels, and dimensions.
Preview ComfortStar 36,000 BTU/H Wall Mounted Heat Pump System Submittal Data Sheet
Technical submittal data sheet for the ComfortStar 36,000 BTU/H wall-mounted heat pump system (FPA-36DU/CZP36CD(O)), detailing system performance, refrigerant specifications, and unit dimensions.
Preview ComfortStar CPA-60DU/CHF60CD(O) 60,000 BTU/H Wall Mounted Heat Pump Submittal Data Sheet
This document provides detailed submittal data for the ComfortStar CPA-60DU/CHF60CD(O) 60,000 BTU/H Wall Mounted Heat Pump System. It includes comprehensive technical specifications, performance data for cooling and heating, refrigerant pipe details, indoor and outdoor unit specifications, and unit dimensions.
Preview ComfortStar CGS18CD(I)/CGS18CD(O) 18,000 BTU Wall Mounted Heat Pump Submittal Data
Detailed submittal data sheet for the ComfortStar CGS18CD(I)/CGS18CD(O) 18,000 BTU/H wall-mounted heat pump system, including performance specifications, dimensions, and features.
Preview ComfortStar CPH3H-36CD(O) Air Handler Heat Pump System Data Sheet
Detailed submittal data sheet for the ComfortStar CPH3H-36CD(O) and CPK3-36-SG3 Air Handler Heat Pump System, including specifications, performance data, and dimensions.
Preview ComfortStar TPA & TIP Series HVAC Performance Data (Cooling & Heating)
Comprehensive cooling and heating performance data tables for ComfortStar TPA and TIP series HVAC units, including models CHF09CD(O) through CHF48CD(O). Data covers various indoor and outdoor temperature conditions.
Preview ComfortStar Air Handler Heat Pump System Submittal Data Sheet: CPH3H-36CD(O) / AC3-3636A-SG3
Detailed submittal data sheet for the ComfortStar CPH3H-36CD(O) and AC3-3636A-SG3 Air Handler Heat Pump System, including efficiency, performance, electrical, piping, and dimension specifications.