Product Overview
The Aspen Pumps Economy Hot Water condensate tank pump is designed to collect hot water from humidifier drain-down cycles and normal condensate from air conditioning or boiler systems. It discharges water to a maximum head of 6 metres.
The pump features an internal pre-wired safety float, which acts as a low-current switch to halt the drain-down cycle if the pump fails. Operation is managed by two internal float switches.
Installation Notes
This pump is designed to be installed level on its base. Ensure the discharge piping is free from kinks or obstructions and has an internal diameter of 9mm. Secure the pipes to the pump's inlet and outlet using cable ties. The pre-wired safety switch must always be utilized.
Diagrammatic representations indicate correct and incorrect installation methods. Incorrect installations include kinks in the discharge pipe [X] and improper pump orientation [X]. Correct installation requires the pump to be level [✓].
Service Guide
To prevent sludge build-up in the pump housing, flush the pump with an anti-bacterial wash every 6 months. Ensure any chemicals used are compatible with the pump's operation. Before initial use, fill the pump with water until the motor runs, checking for leaks and proper water discharge.
For further assistance, contact Aspen Pumps.
Specifications
Feature | Specification |
---|---|
Model | Economy Hot Water |
Max. Flow Rate | 900 L/h |
Max. Recommended Head | 6m |
Tank Capacity | 4 Litres |
Sound Level @ 1m | 64 dB(A) |
Power Supply | 230 VAC 50Hz 1.1A |
Operation | Continuous |
Appliance Class | Class I |
Max. Ambient Temperature | 40°C / 104°F |
Max. Water Temperature | 100°C / 212°F |
Inlet / Outlet | 40mm inlet, 10mm outlet |
IP Protection | IP20 |
Safety Switch | 5.0A Normally Closed |
Physical Dimensions | 270mm (H) x 305mm (W) x 152mm (D) |
Weight | 5.2 kg |
Performance Curve: The pump's performance is illustrated by a graph showing flow rate in Liters Per Hour against head in Meters. The curve indicates a maximum flow of approximately 900 L/h at 0m head, decreasing to 0 L/h at 6m head.
Electrical Connections
The electrical connections are as follows:
- Brown wire: Live
- Blue wire: Neutral
- Green/Yellow wire: Earth
- Two Blue wires: Safety float switch
Internal components include a Main Switch, Thermal Overload Switch (105°C, Auto Reset), Motor, Pump, and Safety Switch (NO, NC, COM).
Important Safety & Usage Notes
- This appliance should only be fitted and serviced by a competent and qualified HVAC/R installer in accordance with all relevant local and national electrical codes and regulations.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning its use by a person responsible for their safety.
- Children shall not play with the appliance.
- If the supply cord is damaged, the pump must be switched off to avoid a hazard. The entire pump will need to be replaced.
- Switch off the isolator to isolate the pump from the electrical supply or disconnect from the electrical supply following national wiring rules.
- Always disconnect the pump from the electrical supply before assembling, disassembling, or cleaning.
- This appliance is intended for indoor use only and must not be allowed to freeze.