Daikin DZK Zoning Kit and FXMQ-PBVJU DC-Ducted Ceiling Unit

ENERGY-INTELLIGENT™ HEATING AND COOLING SYSTEMS

The Daikin Zoning Kit (DZK)

The optional DZK increases the flexibility of Daikin VRV and SkyAir systems for residential and commercial applications. It adds a Zoning Box to an indoor unit fan coil (FXMQ_P or FBQ_P series), allowing several separate ducts to supply air to different, individually-controlled zones. A zone can be a room, part of a room, or several rooms. This flexible and scalable Zoning Kit integrates seamlessly with the indoor unit fan coil controls.

The DZK system controls work with the regular Daikin zone controller (e.g., BRC1E73) to establish the required set-point, fan speed, and mode of operation, which is then requested to the VRV indoor unit via the Daikin zone controller. This allows the internal DZK control algorithms to monitor the number of zone dampers in operation and their positions, adjusting the VRV indoor unit operation accordingly.

The DZK system is not directly compatible with Daikin centralized control options such as iTM and iTC.

DZK BACnet® Gateway Module [NEW]

If VRV systems are installed with the DZK system to achieve various zoning solutions, and there is a requirement to monitor and control the DZK zone dampers from a centralized control system, the DZK BACnet Gateway module can be utilized. The DZK BACnet Gateway module is compatible with any BACnet/IP compatible Building Management System.

Zoning Box with Control Board

The Zoning Box in the DZK mounts easily on Daikin's Indoor Unit FXMQ_P or FBQ_P series fan coils. It comprises an enclosure, individually motorized dampers, and a control box. It is available in different sizes and damper configurations. By utilizing ducts for air supply, it can control the air temperature in up to 6 zones. The wired thermostat and wireless thermostats provide temperature inputs and user interfaces for programming and adjustment of control functions for each zone.

Wireless Thermostat

The wireless backlit touch-screen thermostat for the DZK can control the temperature for a zone while displaying the air temperature, system time, and day of the week. Additional functions include adjusting set point temperature, automatic configuration, local ventilation activation, and vacation mode. A wireless thermostat is required for zones not controlled by a wired thermostat.

Wired Thermostat

The wired thermostat for the DZK features a graphical colored, touch-screen interface with text menus, intuitive icons, and guided scheduling capability. It displays temperatures and operating values, and selects the operating mode for the system. At least one wired thermostat is required per DZK.

Typical Zoning Kit Configuration (4 Zones)

Diagram illustrating a typical zoning kit configuration for 4 zones, showing connections between the Zoning Box Control Box, Navigation Remote Controller, Wired Thermostat, Wireless Thermostats, Zoning Box, and the Indoor Unit Fan Coil (FXMQ-P or FBQ-P).

DZK Kit Structure and General Technical Data

DZK Product Number Zoning Box with Control Board Wired Thermostat Wireless Thermostat BACnet® Gateway Heat Pump Changeover Master
KIT STRUCTURE Compatible with Indoor Unit Fan Coils FXMQ15-24PBVJU FBQ18-30PVJU
Yes No Yes Yes - -
Compatible with Indoor Unit Fan Coils FXMQ30-54PBVJU FBQ36-42PVJU
No Yes Yes - - -
Number of Zones Compatibility Maximum 4 Maximum 5 Maximum 4 Maximum 6 - -
Number of Air Duct Outlets x Diameter ("") 4 x Ø8 5 x Ø6 4 x Ø8 6 x Ø6 - -
Required Quantity One Per Indoor Unit Fan Coil One Per Indoor Unit Fan Coil One Per Indoor Unit Fan Coil One Per Indoor Unit Fan Coil Minimum One Per Indoor Unit Fan Coil Number of Zones Minus Number of Wired Thermostats
DZK030E4-2 Required for BACnet/IP DZK030E5-2 Required for BACnet/IP DZK048E4-2 Required for BACnet/IP DZK048E6-2 Required for BACnet/IP DZK-MTS-2-W Required for BACnet/IP DZK-ZTS-2-W Required for BACnet/IP
One Per DZK Zoning Box with BACnet/IP One Per VRV HP System, if 2 to 16 DZK Units (without BACnet) in the Same VRV System
TECHNICAL DATA Height ("") 10.43 10.43 53.46 - 3.58 1.6 1.75
Width ("") 43.58 20.24 23.32 - 4.13 2.7 2.32
Depth ("") 18.04 - - - 0.94 1.2 0.67
Weight (lbs) - - - 0.4 0.46 0.063 0.065
Input Voltage 110/230 VAC
Full Load Amps (A) 0.25

Note: "-2" in the Product Number indicates BACnet/IP functionality. For configuration of DZK systems with BACnet/IP functionality, only Product Numbers ending with "-2" or "-2-W" can be used. For configuration of DZK systems without BACnet, either products with, or without, the BACnet functionality can be used, even "mix and match".

DC-Ducted Ceiling Unit

Powerful, Concealed, Flexible

When combined with the DZK, the ceiling-mounted DC-Ducted unit is ideal for small to large spaces requiring a concealed air-conditioning system. It is extremely powerful, and its compact design allows it to be completely concealed, making it perfect for retail, classrooms, offices, banks, restaurants, shops, and hotels common areas.

Features and Benefits

Auto Adjust External Static Pressure

After installation, if the actual duct resistance is lower than expected at the time of design, the airflow may be too high. The automatic air-flow adjustment function allows the unit to adapt its fan speed to a lower curve, reducing the airflow. The airflow will always remain within 10% of the rated airflow due to the availability of multiple fan curves (more than 8 fan curves available per model).

Key features include: Condensate Pump [?] as Standard, Outside Air Integration Possible [?️].

Available controller options include BRC1E73 (option), BRC2A71 (option), and BRC4C82 (option).

Additional information regarding estimated annual energy consumption, yearly operating cost, or energy efficiency rating is available from your retailer.

FXMQ-PBVJU Specifications

Model Name 0.6 TON 0.75 TON 1.0 TON 1.25 TON 1.5 TON 2.0 TON 2.5 TON 3.0 TON 4.0 TON 4.5 TON
FXMQ-PBVJU FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJU
Power Supply (V/ph/Hz) 208-230/1/60
Rated Cooling Capacity (BTU/h) 7,500 9,500 12,000 15,000 18,000 24,000 30,000 36,000 48,000 54,000
Rated Heating Capacity (BTU/h) 8,500 10,500 13,500 17,000 20,000 27,000 34,000 40,000 54,000 60,000
Airflow Rate (H/M/L) (CFM) 317/264/229 450/410/388 560/530/500 635/582/529 688/618/565 1,094/953/812 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130 -
Height ("") 11-3/16
Width ("") 21-5/8 27-9/16 39-3/8 55-1/8 18-3/8
Depth ("") 27-9/16 18-3/8
Condensate Pump Lift ("")
Sound Pressure (H/M/L) (dB(A)) 33/31/29 39/37/35 40/38/37 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
Condensate Pipe Connection ("") O.D. 1-1/4
Pipe Connections Gas ("") 1/2 (Flare) 1/4 (Flare) 5/8 (Flare) 3/8 (Flare)
Pipe Connections Liquid ("")
Refrigerant R-410A
Refrigerant Control Electronic Expansion Valve
Maximum Overcurrent Protective Device (A) 15
Minimum Circuit Amps (A) 0.6 1.4 1.5 1.6 1.8 2.8 2.9 3.4
Protection Devices Fuse and Fan Driver Overload Protector
External Finish Galvanized Steel Plate
External Static Pressure (H/L) ("") W.G. 0.40/0.12 0.80/0.20 0.56/0.20

MERV 13 Filter Kit Option

Enthalpy Economizer (Field Applied Accessory)

FXMQ-PBVJU Accessories

*Optional face plates available to provide a more intuitive user interface and disable specific functions.

FXMQ-PBVJU Installation Space

Diagram illustrating required installation clearances for the FXMQ-PBVJU unit, showing air outlet and air inlet positions relative to the ceiling and floor surface. Specific dimensions for clearances are provided, including requirements for inspection hatches.

PDF preview unavailable. Download the PDF instead.

PF-DZKFXMQ-9-15 Adobe PDF Library 15.0 Adobe InDesign CC 2015 (Macintosh)

Related Documents

Preview Daikin FXMQ-PBVJU Ceiling Mounted Duct Type Engineering Data
This document provides comprehensive engineering data for Daikin's FXMQ-PBVJU series of ceiling-mounted duct type air conditioning units. It details specifications, dimensions, performance charts, and installation information for efficient HVAC system design.
Preview Daikin VRV System Inverter Air Conditioner Operation Manual - Ceiling-mounted Duct Type
Comprehensive operation manual for Daikin VRV System Inverter Air Conditioners, ceiling-mounted duct type. Covers safety, parts identification, maintenance, and cleaning instructions for indoor units.
Preview Daikin HVAC Solutions Catalog: Mini-Split, VRV, SkyAir, Light Commercial
Explore Daikin's comprehensive range of HVAC solutions, including Ductless Mini-Split, VRV, SkyAir, and Light Commercial systems. Discover energy-efficient heating and cooling technologies for residential and commercial applications.
Preview Daikin VRV HVAC System Remote Controllers Guide Specification v2.0
Comprehensive guide specification for Daikin VRV HVAC system remote controllers, detailing physical and electrical characteristics, product specifications for Navigation, Simple, and Wireless remote controllers, and their programmability features.
Preview Daikin Indoor Unit Field Settings Guide
Comprehensive guide to Daikin indoor unit field settings, covering various models and configurations for optimal performance and customization by Daikin technical services.
Preview Daikin VRV 6A Series: Next Generation VRV System
Discover the Daikin VRV 6A Series, a next-generation VRV system offering exceptional performance, improved reliability, and compact design. This brochure details its advanced features, energy-saving technologies, and flexible installation options for various applications.
Preview Daikin VRV Installation Guide: Participant Overview
Comprehensive participant guide for Daikin VRV system installation, covering product features, installation procedures, controls, and technical specifications for optimal HVAC performance.
Preview Daikin One+ for P1-P2 Installation & Commissioning Technical Training Module
Comprehensive guide for HVAC-R professionals on installing and commissioning the Daikin One+ smart thermostat with P1-P2 indoor units, covering system configurations, setup, and navigation.