INVT BD Series Hybrid Inverter User Manual
Manufacturer: INVT Solar Technology (Shenzhen) Co., Ltd.
Address: 6th Floor, Block A, INVT Guangming Technology Building, Songbai Road, Matian, Guangming District, Shenzhen, China. Postcode: 518106
Web: www.invt-solar.com
E-mail: solar@invt.com.cn
1. Introduction
1.1 Important Safety Instructions
? Danger!
- Danger to life due to high voltages in the inverter!
- All work must be carried out by a qualified electrician.
- The appliance is not to be used by children or persons with reduced physical sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
- Children should be supervised to ensure that they do not play with the appliance.
⚠️ Caution!
- Danger of burn injuries due to hot enclosure parts!
- During operation, the upper lid of the enclosure and the enclosure body may become hot.
- Only touch the lower enclosure lid during operation.
⚠️ Caution!
- Possible damage to health as a result of the effects of radiation!
- Do not stay closer than 20 cm to the inverter for any length of time.
? Note!
- Grounding the PV generator.
- Comply with the local requirements for grounding the PV modules and the PV generator. It is recommended to connect the generator frame and other electrically conductive surfaces in a manner which ensures continuous conduction and ground these in order to have optimal protection of system and persons.
⚠️ Warning!
- Ensure input DC voltage is less than the maximum DC voltage. Over voltage may cause permanent damage to the inverter or other losses, which will not be included in warranty!
⚠️ Warning!
- Authorized service personnel must disconnect both AC and DC power from the inverter before attempting any maintenance or cleaning or working on any circuits connected to the inverter.
- Risk of electric shock!
- Accessories only together with the inverter shipment are recommended here. Otherwise, it may result in a risk of fire, electric shock, or injury to person.
- Make sure that existing wiring is in good condition and that the wire is not undersized.
- Do not disassemble any parts of the inverter which are not mentioned in the installation guide. It contains no user-serviceable parts. See Warranty for instructions on obtaining service. Attempting to service the inverter yourself may result in a risk of electric shock or fire and will void your warranty.
- Keep away from flammable, explosive materials to avoid fire disaster.
- The installation place should be away from humid or corrosive substances.
- Authorized service personnel must use insulated tools when installing or working with this equipment.
- PV modules shall have an IEC 61730 class A rating.
- Never touch either the positive or negative pole of the PV connecting device. Strictly prohibit touching both of them at the same time.
- The unit contains capacitors that remain charged to a potentially lethal voltage after the MAINS, battery, and PV supply has been disconnected.
- Hazardous voltage will be present for up to 5 minutes after disconnection from power supply.
- CAUTION - RISK of electric shock from energy stored in capacitor. Never operate on the inverter couplers, the MAINS cables, Battery cables, PV cables, or the PV generator when power is applied. After switching off the PV, battery, and Mains, always wait for 5 minutes to let the intermediate circuit capacitors discharge before unplugging DC, battery inplug, and MAINS couplers.
- When accessing the internal circuit of the inverter, it is very important to wait 5 minutes before operating the power circuit or demounting the electrolyte capacitors inside the device. Do not open the device beforehand, since the capacitors require time to discharge sufficiently!
1.2 Explanation of Symbol
This section gives an explanation of all the symbols shown on the inverter and on the type label.
Symbol | Explanation |
---|---|
[CE Mark] | The inverter complies with the requirements of the applicable CE guildlines. |
[TÜV Certified] | TÜV certified. |
[RCM remark] | RCM remark. |
[SAA certification] | SAA certification. |
⚠️ [Hot Surface] | Beware of hot surface. The inverter can become hot during operation. Avoid contact during operation. |
⚡ [High Voltage] | Danger of high voltages. Danger to life due to high voltages in the inverter! |
⚡ [Electric Shock] | Danger. Risk of electric shock! |
? [Observe Enclosed Documentation] | Observe enclosed documentation. |
♻️ [Do Not Dispose with Household Waste] | The inverter cannot be disposed of together with household waste. Disposal information can be found in the enclosed documentation. |
? [Do Not Operate] | Do not operate this inverter until it is isolated from battery, mains, and on-site PV generation suppliers. |
⚡ [Danger to life due to high voltage] | Danger to life due to high voltage. There is residual voltage existing in the inverter after powering off, which needs 5 min to discharge. Wait 5 min before you open the upper lid or the DC lid. |
1.3 Basic features
The BD series hybrid inverter is a high-quality inverter that can convert solar energy to AC energy and store energy into the battery.
The inverter can be used to optimize self-consumption, store energy in the battery for future use, or feed into the public grid. Work mode depends on PV energy and user's preference. It can provide power for emergency use during grid loss by using the energy from the battery and inverter (generated from PV). In addition, the parallel function is available (off-grid model).
System Diagram 1 (applies to most countries)
Description: This diagram illustrates the system connections. PV modules (PV1+, PV1-, PV2+, PV2-) are connected to the inverter. The inverter is connected to the Grid (via AC, Meter, Main switch, RCDs) and to the Battery. An EPS output is also shown, which powers the Loads. The diagram includes a DC disconnect switch and grounding points (PE).
System Diagram 2 (applies to wiring rules AS/NZS_3000:2012 for Australia and New Zealand)
Description: Similar to System Diagram 1, this diagram shows the connections for PV modules, Inverter, Grid, Battery, EPS, and Loads, adhering to specific Australian and New Zealand wiring standards.
? Note! The instrument and switch in the above figures are provided by users.
1.4 Work Modes
Hybrid Inverter provides multiple work modes based on different requirements.
Work modes: Self-use
1. When PV, Grid, Battery is available:
- A. Solar energy provides power to the loads as first priority. If solar energy is sufficient to power all connected loads, excess solar energy will charge the battery, and then redundant power will feed to the grid.
- B. Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
- C. Solar energy provides power to the loads as first priority. If solar energy and battery are not sufficient to power all connected loads, utility energy (Main Grid) will supply power to the loads along with solar energy at the same time.
2. When PV, Grid is available (without battery):
- A. Solar energy provides power to the loads as first priority. If solar energy is sufficient, the excess power will feed to the grid.
- B. Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Grid energy will supply power to the loads at the same time.
3. When PV, Battery is available (Grid is disconnected):
- A. Solar energy provides power to the loads as first priority. If solar energy is sufficient to power all connected loads, solar energy will provide charging for the battery.
- B. Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy and solar energy will supply power to the loads at the same time.
Work modes: Peak shift
1. When PV, Grid, Battery is available:
- A. On charge time, solar energy will charge the battery as first priority. Excess energy will supply power to the loads. If solar energy is sufficient to supply loads and charge battery, and if there's still some extra energy, then the excess power will feed to the grid.
- B. On charge time, solar energy will charge the battery as first priority, then the excess solar energy will supply power to loads. If solar energy is not sufficient to charge battery and supply loads, the grid will supply all the connected loads with solar energy together.
- C. On discharge time, solar energy provides power to the loads as first priority. If solar energy is sufficient to supply loads, and if there's still some extra energy from solar energy, then the excess power and battery will deliver power to the grid at the same time.
- D. In the period of no charge or discharge, the solar power supplies loads at first priority, with excess energy to the grid.
2. When Grid, Battery is available (PV is disconnected):
- A. On charge time, the grid will charge the battery and supply power to the connected loads at the same time.
- B. On discharge time, if load power is less than battery power, the battery will supply power to loads as first priority, and the excess power will be fed to the grid.
- C. On discharge time, if load power is more than battery power, battery and grid will supply power to the loads at the same time.
Work modes: Bat priority
1. When PV, Grid, Battery is available:
- A. Solar energy will charge the battery as first priority. If solar energy is excess, the excess power will supply the load. If there's still some extra energy, then the excess power will feed the power to the grid.
- B. Solar energy will charge the battery as first priority. If solar energy is excess, the excess power will supply the load. If solar energy is not sufficient to charge the battery and supply loads, the grid will supply power to the loads.
2. When Grid, Battery is available (PV is disconnected):
The grid will supply power to the load and charge the battery at the same time.
? Note! If the anti-Reverse function is allowed, once on the work mode of Self-use, Peak shift, or Battery priority, the system will not feed power to the grid.
1.5 Dimension
Description: The inverter has dimensions of 550.0mm (Width) x 520.0mm (Height) x 200.0mm (Depth).
2. Interface definition and Technical Data
2.1 Interface definition
Description: The front panel of the inverter features various ports and indicators. A diagram shows the layout of these interfaces, labeled A through P.
Object | Description |
---|---|
A/B | Battery +/- |
C/D | PV1+/PV1- |
J/K | PV2+/PV2- |
E | DC switch |
F | WiFi port for external WiFi |
L | Reserved port |
G | DRM/BMS |
H | Grid current / DRY IO |
M | USB port for upgrading |
N | POWER CAN /LEAD-NTC |
I | Pressure valve |
O | EPS output |
P | Grid output |
? Note!
- The Update port is for on-premises upgrades.
- The BMS port is for BMS communication for lithium batteries.
- The CT port is for external grid-side CT to detect current size.
- The DRM port, CAN port, NTC port, and DRY IO port are reserved ports, temporarily unavailable.
2.2 Technical Data
The following table details the technical specifications for various INVT BD Series Hybrid Inverter models (BD3KTL-RL1 to BD6KTL-RL1).
Model | BD3KTL-RL1 | BD3K6TL-RL1 | BD4KTL-RL1 | BD4K6TL-RL1 | BD5KTL-RL1 | BD6KTL-RL1 |
---|---|---|---|---|---|---|
DC input | ||||||
Max. recommended DC power [W] | 4600 | 4600 | 6000 | 6000 | 7000 | 7000 |
Max. DC voltage [V] | 550 | 550 | 550 | 550 | 550 | 550 |
Norminal DC operating voltage [V] | 360 | 360 | 360 | 360 | 360 | 360 |
MPPT voltage range [V] | 125-500 | 125-500 | 125-500 | 125-500 | 125-500 | 125-500 |
MPPT voltage range@full load [V] | 150-500 | 150-500 | 170-500 | 170-500 | 220-500 | 220-500 |
Max. input current [A] | 14/14 | 14/14 | 14/14 | 14/14 | 14/14 | 14/14 |
Max. short circuit current [A] | 17.5/17.5 | 17.5/17.5 | 17.5/17.5 | 17.5/17.5 | 17.5/17.5 | 17.5/17.5 |
Start input voltage [V] | 125 | 125 | 125 | 125 | 125 | 125 |
No. of MPP trackers | 2 | 2 | 2 | 2 | 2 | 2 |
Strings per MPP tracker | 1 | 1 | 1 | 1 | 1 | 1 |
Max. inverter backfeed current to array | 0 | 0 | 0 | 0 | 0 | 0 |
DC disconnection switch | / | / | / | / | / | / |
AC output | ||||||
Norminal AC power [VA] | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
Max. apparent AC power [VA] | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
Rated grid voltage (range) [V] | 230 (176 to 270) | |||||
Rated grid frequency [Hz] | 50/60 | |||||
Norminal AC current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Max. AC current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Displacement power factor | 0.99 leading~0.99 lagging | |||||
Total harmonic distortion (THDI) | < 2% | |||||
Load control | optional | |||||
AC input | ||||||
Norminal AC power [VA] | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
Rated grid voltage (range) [V] | 230(176 to 270) | |||||
Rated grid frequency [Hz] | 50/60 | |||||
Norminal AC current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Max. AC current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Displacement power factor | 0.99 leading~0.99 lagging | |||||
AC inrush current | 35 | 35 | 35 | 35 | 35 | 35 |
EPS output | ||||||
EPS rated power [VA] | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
Max. EPS power [VA] | 3000 | 3680 | 4000 | 4600 | 5000 | 6000 |
EPS rated voltage, Frequency | 230VAC, 50/60Hz | |||||
EPS rated current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Max. EPS current [A] | 13 | 16 | 17.4 | 20 | 21.7 | 26 |
Switch time [s] | <20ms | |||||
Total harmonic distortion (THDv) | <2% | |||||
Parallel operation | Yes | |||||
Compatible with the generator | Yes (signal provided only) | |||||
Battery parameter | ||||||
Battery type | Lithium battery/Lead-ACID | |||||
Battery voltage range [V] | 40-58 | |||||
Recommended battery voltage [V] | 48 | |||||
Cut Off Voltage [V] | 40 | |||||
Max. charging Voltage [V] | 58 | |||||
Max. Protective Voltage [V] | 59 | |||||
Max. charge/discharge current [A] | 95/62.5 | 95/76.6 | 95/83.3 | 95/95.8 | 95/104.2 | 95/110 |
Peak charge/discharge current [A] | 95/62.5 | 95/76.6 | 95/83.3 | 95/95.8 | 95/104.2 | 95/110 |
Communication interfaces | CAN/RS485/WIFI/LAN/DRM | |||||
Reverse connect protection | Yes | |||||
Efficiency | ||||||
MPPT efficiency | 99.9% | |||||
Euro efficiency | 97% | |||||
Max. efficiency | 97.6% | |||||
Max. Battery charge efficiency | 95% | |||||
Max. Battery discharge efficiency | 95% |
? Note! If the South African national grid standard is selected, the grid power is only 4.6kW!
2.3 Basic Data
Model | BD3KTL-RL1 | BD4KTL-RL1 | BD5KTL-RL1 | BD3K6TL-RL1 | BD4K6TL-RL1 | BD6KTL-RL1 |
---|---|---|---|---|---|---|
Dimension [W/H/D](mm) | 550*520*200 | |||||
Dimension of packing [W/H/D](mm) | 665*635*330 | |||||
Net weight [kg] | 25 | 25 | 31 | 31 | 31 | 31 |
Gross weight [kg] | 31 | 31 | 31 | 31 | 31 | 31 |
Installation | modularization | |||||
Operating temperature range [°C] | -25~+60 (derating at 45) | |||||
Storage temperature [°C] | -25~+60 | |||||
Storage/Operation relative humidity | 4%~100% (Condensing) | |||||
Altitude [m] | <2000 | |||||
Ingress Protection | IP65 (for outdoor use) | |||||
Protective Class | III (MAINS), II (PV, Battery) | |||||
Night-time consumption | <3W | |||||
Over Voltage Category | III | |||||
Pollution Degree | 2 | |||||
cooling | Natural | |||||
Noise level | <40dB | |||||
Inverter Topology | non-isolated | |||||
Active anti-islanding method | Power variation | |||||
Communication interface | CAN/RS485/WIFI/LAN/DRM |
2.4 Safety and Protection
Safety & Protection | |
---|---|
Over/under voltage protection | YES |
DC isolation protection | YES |
Monitoring ground fault protection | YES |
Grid protection | YES |
DC injection monitoring | YES |
Back feed current monitoring | YES |
Residual current detection | YES |
Anti-islanding protection | YES |
Over load protection | YES |
Over heat protection | YES |
Max. output fault current | 55A |
Max. output over current | 28.7A |
3. Installation
3.1 Check for Physical Damage
Make sure the inverter is intact during transportation. If there is any visible damage, such as cracks, please contact your dealer immediately.
3.2 Packing List
Open the package and take out the product, please check the accessories first. The packing list is shown below.
Object | Description |
---|---|
A | Inverter |
B | Bracket |
C | Expansion screws and pan-head screws |
D | PV connectors (2*positive, 2*negative) |
E | AC terminals |
F | PV pin connectors (2*positive, 2*negative) |
G | WiFi module (optional) |
H | GPRS module (optional) |
I | User manual |
3.3 Tools required for installation.
Installation tools: crimping pliers for binding post and RJ 45, screwdriver, manual wrench, etc.
3.4 Mounting
Space Requirement
Description: The inverter requires specific clearance around it for proper ventilation and access. The diagram shows a 300mm clearance required on the left, right, top, bottom, and front.
Position | Min. size |
---|---|
Left | 300mm |
Right | 300mm |
Top | 300mm |
Bottom | 300mm |
Front | 300mm |
Mounting Steps:
Step 1: Screw the wall bracket on the wall
1.1 Place the bracket on the wall and mark down the position of the 4 holes.
1.2 Drill holes with a driller, make sure the holes are deep enough (at least 60mm) to support the inverter.
1.3 Install the expansion tubes in the holes, and tighten them. Then install the wall bracket with the expansion screws.
Step 2: Place the inverter on the wall-mounted bracket by holding the handle on the side.
Step 3: Tighten the fixing screws on both sides of the inverter.
Step 4: If necessary, the customer can install an anti-theft lock on the left-bottom of the inverter.
4. Electrical Connection
Electrical connection diagram
Description: This diagram illustrates the electrical connections for the hybrid inverter. It shows connections for Battery (BAT), PV inputs (PV1, PV2), Communication (COM), Grid (GRID), and EPS output (EPS). Various breakers (BAT Breaker, PV Breaker, EPS Breaker, Main Breaker, AC Breaker) and components like Meter, CT, and Loads are depicted in the system.
4.1 Grid connection and EPS connection
Hybrid inverters are designed for single-phase grids. Voltage is 220/230/240V, frequency is 50/60Hz. Other technical requests should comply with the requirements of the local public grid.
Model | BD3KTL-RL1 | BD3K6TL-RL1 | BD4KTL-RL1 BD4K6TL-RL1 | BD5KTL-RL1 BD6KTL-RL1 |
---|---|---|---|---|
Cable | 4-5 mm² | 5-6mm² | ||
Micro-breaker | 20A | 32A |
Micro-breakers should be installed between the inverter and the grid. Any load should not be connected directly to the inverter.
Step-by-step connection instructions:
Step 1: Check the grid voltage.
1.1 Check the grid voltage and compare with the permissive voltage range (Please refer to technical data).
1.2 Disconnect the circuit board from all phases and secure against re-connection.
Step 2: Remove the waterproof lid from the grid port on the inverter.
Step 3: Make AC and EPS wires.
3.1 Choose the appropriate wire (Cable size: refer to Table 1).
3.2 Reserve about 60mm of conductor material sectional area and remove 10mm of insulation from the end of the wire.
3.3 Separate the docking screw cap of the AC terminal from the housing portion and insert stripped wires into the AC terminal, then tighten the screws with a hexagonal wrench.
3.4 Tighten the docking screw cap and housing portion of the AC terminal.
Step 4: Connect the AC connector to the GRID port of the inverter and tighten the screw cap. Connect the LOAD connector to the EPS port of the inverter and tighten the screw cap.
? Note: Connect the AC connector to the GRID interface.
4.2 PV connection
Hybrid Inverters can be connected in series with 2-string PV modules for 3KW, 3.6KW, 4KW, 4.6KW, 5KW, and 6KW models. Select PV modules with excellent function and reliable quality. Open-circuit voltage of module arrays connected in series should be less than the Max. DC input voltage; operating voltage should conform to the MPPT voltage range.
Max. DC Voltage Limitation:
Model | BD3KTL-RL1 BD3K6TL-RL1 BD4KTL-RL1 BD4K6TL-RL1 BD5KTL-RL1 BD6KTL-RL1 |
---|---|
Max. DC Voltage (V) | 550 |
MPPT Voltage Range (V) | 125-500 |
⚠️ Warning! PV module voltage is very high, which already achieves dangerous voltage range. Please comply with electric safety rules when connecting. Please do not make PV positive or negative ground!
Connection Steps:
Step 1: Checking PV module to ensure PV is in open circuit state and ensure the PV+ and PV- ports of the PV string are correct.
Step 2: Separating the DC connector.
Description: This step involves separating the plug, pin contact, and cable nut components of the DC connector.
Step 3: Wiring
3.1 Choose the 12 AWG wire to connect with the cold-pressed terminal.
3.2 Remove 10mm of insulation from the end of the wire.
3.3 Insert the insulation into the pin contact and use crimping pliers to clamp it.
Step 4: Insert pin contact through the cable nut to assemble into the back of the male or female plug. When you feel or hear a “click” sound, the pin contact assembly is seated correctly.
Step 5: Plug the PV connector into the corresponding PV connector on the inverter.
4.3 Battery Connection
Notes:
- Before choosing a battery, please note the maximum voltage of the battery cannot exceed 59V and the rated voltage of the battery cannot exceed 48V. The battery communication should be compatible with the Hybrid inverter.
- Before connecting to the battery, please install a nonpolarized DC (125A) breaker to ensure the inverter can be securely disconnected during maintenance.
- The connecting cable between the battery and the inverter shall be at least 4AWG.
- The battery communication can only work when the battery BMS is compatible with the inverter.
- To replace the battery, you need to turn off all switches and unplug the system communication line.
- All the above wiring and operations must be carried out after the whole machine is powered down, and all of them need professional personnel to complete.
Power Connection Steps:
Step 1: Choose the 4AWG wire and strip the cable to 15mm.
Step 2: Select two O-terminals with an aperture of M6.
Step 3: Insert the stripping line into the O-terminal and clamp it with a crimping clamp.
Step 4: Remove the waterproof cover plate.
Step 5: Disassemble the waterproof connector and pass the cable through the waterproof connector.
Step 6: Connect the cable to the terminal of the inverter.
Step 7: Assemble waterproof connectors and waterproof covers plate.
? Note! Positive and negative lines are not allowed to reverse. The positive pole is on the left and the negative pole is on the right.
4.4 Communication interface definition
BMS PIN Definition
Communication interface between inverter and battery is RS485 or CAN with an RJ45 connector. The wiring sequence of the crystal head conforms to the 568B standard: orange white, orange, green white, blue, blue white, green, brown white, and brown.
PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|
CAN Definition | X | X | X | BMS_CANH | BMS_CANL | X | X | X |
Rs485 Definition | X | X | X | X | X | GND | BMS_485A | BMS_485B |
DRY_IO (RJ45 PIN) Definition
Reserved dry contact interface of the inverter.
PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|
COM1 | NO 1 | NC 1 | DI 1 | DI 2 | COM2 | NO 2 | NC 2 |
DRM Connection
DRM is provided to support several demand response modes by emitting control signals as below. ? Note: Only PIN6(DRM0) is available now, and other PIN functions are being developed.
4.5 WiFi And GPRS Connection (optional)
The inverter provides a WiFi port which can collect data from the inverter and transmit it to a monitoring website by WiFi.
Steps:
Step 1: Plug WiFi into “COM” port at the bottom of the inverter.
Step 2: Build the connection between the inverter and router.
Step 3: Create a user account online. (Please check the WiFi user manual for more details).
Diagram:
Description: Illustrates connecting a WiFi module to the inverter's COM port, which then connects to a router and the cloud for monitoring.
GPRS Connection:
GPRS connection interface is consistent with WIFI interface. Please refer to the GPRS user manual for detailed connection steps.
Diagram:
Description: Illustrates connecting a GPRS module to the inverter, which then connects to a router and the cloud for monitoring, similar to the WiFi connection.
5. LCD Interface and Setting
5.1 Control Panel
Description: The control panel features an LCD screen (A) and indicator LEDs (B, C, D, E) for status indication, along with function buttons (F, G, H, I) for navigation and selection.
Object | Name | Description |
---|---|---|
A | LCD Screen | Display the information of the inverter. |
B | Indicator LED | Lit in green: The inverter is in grid mode. Off: The inverter is not in grid mode. |
C | Indicator LED | Lit in green: The inverter is in off-grid mode. Off: The inverter is not in off-grid mode. |
D | Indicator LED | Lit in Yellow: The inverter is in Warning. Off: The inverter has no Inverter Warning. |
E | Indicator LED | Lit in red: The inverter is in fault status. Off: The inverter has no errors. |
F | Function Button | Esc: Return from current interface or function. |
G | Function Button | Up: Move cursor to upside or increase value. |
H | Function Button | Down: Move cursor to downside or decrease value. |
I | Function Button | Enter: Confirm the selection. |
5.2 Instructions for LED Indicator
Status | Grid (Green) | EPS (Green) | Alarm (Yellow) | Fault (Red) |
---|---|---|---|---|
Initialization | off | off | off | off |
Stand-by | off | off | off | off |
Grid mode | on | off | off | off |
Off-Grid | off | on | off | off |
Bypass of mains | off | on | on | off |
Fault | off | off | off | on |
5.3 Instructions for the use of three modes
Description: This section outlines the hierarchical menu structure for configuring the inverter's settings, including System Settings, Battery Settings, Baud Rate, Language, and more.
Example: Before selecting a mode, configuration can be done according to the local power grid, PV input mode, and battery type.
Power grid:
Flow: Circular display interface -> User -> Enter password -> Choose according to local power grid -> Press Enter button -> 3:GRID STD.
Password: Default is 00000. Use UP/DOWN buttons to adjust, Enter to move cursor, Esc to go back.
PV input mode:
Flow: Setting -> 1:SYS SETTING -> 6 PV INPUT -> Select PV input mode, Press Enter to confirm.
Battery parameters:
Flow: Setting -> 1:BAT TYPE -> Enter password -> Set corresponding battery type, Press Enter to confirm.
5.4 LCD Interface
5.4.1 Error information
Interface | Description |
---|---|
ERROR NO. 02:BatDisconnect 27:BMS Comm.fail | Numbers represent error codes and text is error information. Refer to Chapter 9 for specific contents. ? NOTE: When there is a lock mark in the upper right corner of the screen, you cannot turn the page; you need to press Enter to unlock it first. |
5.4.2 System setting
Interface | Description |
---|---|
SYSTEM 1 STATE: SELF CSM GRID : US-CA PV I/P: PARALL | State: Setting of the whole machine working mode. Including: SELF CONSUME, PEAK SHIFT and BAT PRIORITY. Refer to Chapter 3.3 for specific contents. Grid standard: Displays the grid standard actually set. PV input mode: The display value is the setting value of PV input type. Including: INDEPENDANT, PARALLEL, CV. |
5.4.3 System setting 2
Interface | Description |
---|---|
SYSTEM 2 BMS Com: CAN Anti Reve : DISA DOD: 80% | BMS Com: Battery Management System communication mode. Including: CAN, RS485. Anti Reve: Displays whether the inverter is allowed to generate electricity to the Grid. Including: DISABLE, ENABLE. DOD: Depth of battery discharge. |
5.4.4 System setting 3
Interface | Description |
---|---|
SYSTEM 3 EPS ENABLE: ENAB | EPS ENABLE: When the Grid and PV are powered off, enable the battery to supply power to the load; default option is enable. See Chapter 8.2.4.2 for setting details. |
5.4.5 PV1 Input display interface
Interface | Description |
---|---|
PV1 INPUT VOLT: 300V CURR: 10.00A POWER: 3000W | PV1 input real-time voltage, current, and power. |
5.4.6 PV2 Input display interface
Interface | Description |
---|---|
PV2 INPUT VOLT: 300V CURR: 10.00A POWER: 3000W | PV2 input real-time voltage, current, and power. |
5.4.7 DC Voltage interface
Interface | Description |
---|---|
DC VOLTAGE BUS: 384V LeakCurr: 0mA | BUS: Real-time voltage of bus capacitor of the machine. LeakCurr: Real-time leak current of the machine. |
5.4.8 Battery interface
Interface | Description |
---|---|
BATTERY VOLT: 300V CURR: 10.00A STA: C D F | Battery real-time voltage, current. STA: Battery status. C: Charge. D: Discharge. F: Full charge. Battery status depends on BMS instructions. |
5.4.9 Battery current interface
Interface | Description |
---|---|
BATTERY INFO TYPE: Lithum TEMP: 26°C SOC: 30% | TYPE: Battery type (lead acid, lithium battery). TEMP: Battery temperature. SOC: Percentage of battery surplus capacity. |
5.4.10 Battery current interface
Interface | Description |
---|---|
BMS PRMETER CHAR VOL: 0.0V CHARGE: 50A DISCHA: 50A | CHAR VOL: Battery charging voltage. CHARGE: Battery charging current. DISCHA: Battery discharging current. |
5.4.11 Grid-connected
Interface | Description |
---|---|
GRID VOLT: 0.0V CURR: 0.00A FREQ: 0.00Hz | VOLT: Grid real-time voltage. CURR: CT real-time current. FREQ: Grid real-time frequency. |
5.4.12 INV
Interface | Description |
---|---|
INV VOLT: 0.0V CURR: 0.00A FREQ: 0.00Hz | VOLT: INV real-time voltage. CURR: INV real-time current. FREQ: INV real-time frequency. |
5.4.13 LOAD
Interface | Description |
---|---|
LOAD VOLT: 0.0V CURR: 0.00A PERCENT: 0% | VOLT: LOAD real-time voltage. CURR: LOAD real-time current. PERCENT: LOAD real-time percentage. |
5.4.14 POWER
Interface | Description |
---|---|
POWER INV: 0.0W GRID: 0.0W | INV: INV power. GRID: Grid power. |
5.4.15 POWER
Interface | Description |
---|---|
POWER PV I/P: 0W LOAD: 0W BAT: 0W | PV I/P: PV power. LOAD: LOAD power. BAT: BAT power. |
5.4.16 Temperature
Interface | Description |
---|---|
TEMPERATURE INVER: 0°C DCDC: 0°C INSIDE: 0°C | INVER: INV Temperature. DCDC: DCDC Temperature. INSIDE: Internal ambient temperature of the machine. |
5.4.17 State
Interface | Description |
---|---|
STATE SYS: STANDBY INV: STANDBY DCDC: STANDBY | System information: Display complete machine status information, Including: Initialization, Standby, PV grid connection, Grid connection of battery, Hybrid power supply, etc. INV: Displays the inverter status information. DCDC: Displays charging and discharging status information. |
5.5 Settings
5.5.1 State
Interface | Description |
---|---|
USER 1:SETUP 2:INQUIRE 3:STATISTIC | SETUP: Press Enter to user settings interface. INQUIRE: Query machine model, serial number, software version. STATISTIC: View machine run statistics. |
5.5.2 SET Password
Interface | Description |
---|---|
PASSWORD INPUT: XXXXX | Enter the password required for setting. The default password is "00000". Press the Up or Down keys to adjust the number, press the Enter key to move the cursor forward, and press the Esc key to move the cursor backward. |
5.5.3 Setup
Interface | Description |
---|---|
SETUP 1:SYS SETTING 2:BAT SETTING 3:GRID STD 4:RUN SETTING 5:485 ADDRESS 6:BAUD RATE 7:LANGUAGE 8:BACKLIGHT 9:DATE/TIME 10:CLEAR REC 11:PASSWORD 12:MAINTENANCE 13:FCTRY RESET | This interface is used for various information inquiry options. Press the Up/Down button to make the corresponding selection. Press Enter button to enter the selected menu. Press ESC button to return to the user interface. There are 13 options in total. |
5.5.4 System setting
5.5.4.1 System setting
Interface | Description |
---|---|
SYS SETTING 1: WORK MODE 2: EPS ENABLE 3: BAT WAKE-UP 4: REMOTE CTRL 5: START DELAY 6: PV INPUT 7: Anti Reverse | This interface is used to access system information. Press Up/Down button to move corresponding options. Press Enter to enter the selected menu. Press ESC button to return to the setting interface. There are 7 options in total. |
5.5.4.1.1 Work mode
Interface | Description |
---|---|
WORK MODE 1:SELFCONSUME 2:PEAK SHIFT 3:BAT PRIORITY | This interface is used to select the working mode. Press ESC button return to setting interface. (Refer to 3.3) |
5.5.4.1.2 Peak shift work time
Interface | Description |
---|---|
WORK MODE 1:SELFCONSUME 2:PEAK SHIFT 3:BAT PRIORITY | This interface is used to select the working mode. Press ESC button return to setting interface. (Refer to 3.3). Select the peak clipping and valley filling mode; you also need to set the charge and discharge time. |
WORKTIME 1:TIME 1 2:TIME 2 3:TIME 3 | It's allowed to set three charging and discharging periods. When setting the time, ensure that the time of the inverter is the local time. Press Enter to enter the next menu. |
CHAG START1 00:00 CHARGE END1 00:02 DISC START1 00:03 DISCHA END1 23:59 | This interface is used to adjust the time of peak load shifting. Press Up/Down button to move the corresponding options. Press Enter to enter the selected menu. Press Esc button to return to the working mode interface. |
5.5.4.2 EPS enable
Interface | Description |
---|---|
EPS ENABLE 1:DISABLE 2:ENABLE | When the Grid and PV are powered off, enable the battery to supply power to the load; default option is enable. |
5.5.4.3 Battery wake-up
Interface | Description |
---|---|
WAKE-UP EN 1:DISABLE 2:ENABLE | When the battery is low and the battery relay has been disconnected, the inverter will send instructions to the battery forcibly sucking relay by BMS, and the inverter will charge. The default option is disabled. (Partial battery support) |
5.5.4.4 REMOTE CTRL
Interface | Description |
---|---|
REMOTE CTRL 1:DISABLE 2:ENABLE | Remote control the inverter on or off. (Subsequent support...) The default option is disabled. |
5.5.4.5 START DELAY
Interface | Description |
---|---|
START-UP DELAY INPUT: 60 UNIT: SEC | The input value ranges from 20 to 300, which varies with different standards. |
5.5.4.6 PV INPUT MODE
Interface | Description |
---|---|
INPUT MODE 1.INDEPENDENT 2.PARALLEL 3.CV | Setup of PV Input mode. The factory setting by default is Independent. When parallel input is set to be stand-alone mode, PV power will be imbalanced. |
5.5.4.7 Anti Reverse
Interface | Description |
---|---|
Anti Reverse 1.DISABLE 2.ENABLE | Anti Reverse: Whether the inverter is allowed to generate electricity to the Grid. The default option is disabled, meaning the inverter is allowed to generate electricity to the Grid. |
5.5.5 BAT SETTING
5.5.5.1 BAT SETTING
Interface | Description |
---|---|
BAT SETTING 1.BAT TYPE 2.DISC-DEPTH 3.CHARG-CURR 4.BAT-COMM | This interface is used to select battery parameters. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu; Press ESC button to return to setting interface. |
5.5.5.1.1 BAT TYPE
Interface | Description |
---|---|
BAT TYPE 1.DC-SOURCE 2.LEAD-ACID 3.Lithum | This interface is used to select battery type. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. Select LEAD-ACID to enter the LEAD-ACID interface. |
5.5.5.1.1.1 Lead-acid battery parameter
Interface | Description |
---|---|
LEAD-ACID 1.CHARG-VOLT 2.BAT END VOLT 3:BAT OVP 4:BAT CAP | This interface is used to select LEAD-ACID battery parameters. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. |
CHARGE VOLT INPUT: 135.0 UNIT: V | This interface is used to set the lead acid battery charging voltage. |
Interface | Description |
---|---|
BAT END VOLT INPUT: 108.0 UNIT: V | This interface is used to set the lead acid battery discharging voltage. |
BAT OVP INPUT: 141.0 UNIT: V | This interface is used to set the lead acid battery Charge protection voltage. |
BAT CAP INPUT: 0450 UNIT: AH | This interface is used to set the lead acid Battery capacity. |
5.5.5.2 BAT-COMM
Interface | Description |
---|---|
BAT-COMM 1.RS485 2.CAN | This interface is used to select battery communication. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. The default option is CAN. |
5.5.6 Grid standard
5.5.6.1 Grid std
Interface | Description |
---|---|
GRID STD 1.AU 2.AU-W 3.NZ 4.UK 5.VDE 6.KR 7.PHI 8.CN 9.US-CA 10.JP 11.CUSTOM | This interface is used to select Grid standard. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. 1:AU--(Australia) 2:AU-W--(Western Australia) 3:NZ--New Zealand 4:UK--United Kingdom 5:VDE--Germany 6:KR--Korea 7:PHI--Philippines 8:CN--China 9:US-CA--America 10:JP--Japan 11:CUSTOM--User defined |
5.5.7 RUN SETTING
5.5.7.1 RUN SETTING
Interface | Description |
---|---|
RUN SETTING 1.REACT MODE 2.GRID POWER 3.DISC POWER 4.PV POWER 5.VAC-MIN 6.VAC-MAX 7.FAC-MIN 8.FAC-MAX 9.ACTIVE REP. | This interface is used to select run setting. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. |
5.5.7.2 REACT MODE
Interface | Description |
---|---|
RUN SETTING 1.REACT MODE 2.GRID POWER 3.DISC POWER | This interface is used to select react mode. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. |
REACT MODE 1.POWER FACTOR 2.REACT POWER 3.QU WAVE 4.QP WAVE | |
POWER FACTOR INPUT: C1.00 | The input value should range between L0.80 and L0.99 or C0.8 and C1.00. |
REACT POWER INPUT: +00% | The input value should range between -60% and +60%, which varies with the standard. |
5.5.7.3 GRID POWER
Interface | Description |
---|---|
GRID PERCENT INPUT: 100% | The input value is power percent of grid. |
5.5.7.4 DISCHARGE POWER
Interface | Description |
---|---|
DISC PERCENT INPUT: 100% | The input value is power percent of battery discharge. |
5.5.7.5 PV POWER
Interface | Description |
---|---|
PV PERCENT INPUT: 100% | The input value is power percent of PV. |
5.5.7.6 VAC-MIN
Interface | Description |
---|---|
GRID VOLT LOW INPUT: 150 UNIT: V | The input value of Grid low voltage. It affects when grid mode chooses custom. |
5.5.7.7 VAC-MAX
Interface | Description |
---|---|
GRID VOLT HIGH INPUT: 280 UNIT: V | The input value of Grid high voltage. It affects when grid mode chooses custom. |
5.5.7.8 FAC-MIN
Interface | Description |
---|---|
GRID FREQ LOW INPUT: 57.0 UNIT: Hz | The input value of Grid low frequency. It affects when grid mode chooses custom. |
5.5.7.9 FAC-MAX
Interface | Description |
---|---|
GRID FREQ HIGH INPUT: 63.0 UNIT: Hz | The input value of Grid high frequency. It affects when grid mode chooses custom. |
5.5.8.10 ACTIVE REF.
Interface | Description |
---|---|
ACTIVE Type 1.PWR-VOLT RES 2.PWR-FREQ RES 3.PFC-VOLT RES 4.PFC-FREQ RES 5.Reserved1 6.Reserved2 7.Reserved3 8.Reserved4 | This interface is used to select active reference. Press Up/Down button to move corresponding options; Press Enter button to enter the selected menu. Each menu has enable or disable; set it when you need. All defaults are enable. |
5.5.8 485 Address
5.5.8.1 485 Address
Interface | Description |
---|---|
485 ADDRESS INPUT: 1 | This interface is used to select 485 address. |
5.5.9 485 BAUD RATE
5.5.9.1 BAUD RATE
Interface | Description |
---|---|
SELECT 1.2400 bps 2.4800 bps 3.9600 bps | This interface is used to select 485 baud rate. |
5.5.10 LANGUAGE
5.5.10.1 LANGUAGE
Interface | Description |
---|---|
LANGUAGE 1.Chinese 2.English | This interface is used to select language. |
5.5.11 BACKLIGHT
5.5.11.1 BACKLIGHT
Interface | Description |
---|---|
LIGHT TIME INPUT: 20 UNIT: SEC | This interface is used to set light time. |
5.5.12 DATE/TIME
5.5.12.1 DATE/TIME
Interface | Description |
---|---|
DATE/TIME DATE: 2021-12-25 TIME: 22:30:00 WEEK: Saturday | This interface is used to set date and time. |
5.5.13 CLEAR REC
5.5.13.1 Clear history
Interface | Description |
---|---|
DEL REC 1.CANCEL 2.CONFIRM | This interface is used to clear operation history. |
5.5.14 PASSWORD
5.5.14.1 PASSWORD
Interface | Description |
---|---|
PASSWORD OLD: XXXXX NEW: XXXXX CONFIRM: XXXXX | This interface is used to set password. |
5.5.15 MAINTENANCE
5.5.15.1 MAINTENANCE
Interface | Description |
---|---|
PASSWORD INPUT: XXXXX | This interface is used to enter maintenance. |
5.5.16 FCTRY RESET
5.5.16.1 FACTORY RESET
Interface | Description |
---|---|
FACTORY RESET 1.CANCEL 2.CONFIRM | This interface is used to reset the inverter. |
5.6 INQUIRE
5.6.1 INQUIRE
Interface | Description |
---|---|
INQUIRE 1.INV MODULE 2.MODULE SN 3.FIRMWARE 4.RECORD 5.DIAGNOSE | Press Up/Down button to move corresponding options; Press Enter button to jump to the selected menu. Press ESC button to return to other interface. |
5.6.1.1 INV MODULE
Interface | Description |
---|---|
MODEL 12K | This interface shows the inverter model. |
5.6.2 MODULE SN
Interface | Description |
---|---|
S / N GUID: XXXXXXXX XXXXXXXXXXXXXX SN:FXXXXXXXXXXX | This interface shows the module SN. |
5.6.3 FIRMWARE
Interface | Description |
---|---|
FIRMWARE ARM: V1.XX.XX DSP: V1.XX.XX | This interface shows the software version. |
5.6.4 RUNNING RECORDS
Interface | Description |
---|---|
REC(01) 02:Batdisconnect UP: 12-25 23:00 DOWN: | This interface shows running records. |
5.6.5 DIAGNOSE
Interface | Description |
---|---|
DIAGNOSE 000000 000000 000000 000000 000000 000000 | Factory internal use. |
5.7 STATISTIC
5.7.1 STATISTIC
Interface | Description |
---|---|
STAT. 1.TIME STAT. 2.CONNE.TIMES 3.PEAK POWER 4.E-TODAY 5.E-MONTH 6.E-YEAR 7.E-TOTAL | This interface shows inverter operation statistics. 1. Inverter operation and Grid-connection time statistic. 2. Inverter Grid-connection times statistic. 3. Displays power peak in history and for the day. 4. Displays statistic for the day (KWH). 5. Displays statistic for the month (KWH). 6. Displays statistic for the year (KWH). 7. Displays statistic of the inverter (KWH). |
? Note: 1. E-TODAY/MONTH/YEAR/TOTAL → INPUT → PV/GRID(Consume)/BATD(Battery discharge) → OUTPUT → BATC(Battery charge)/GRID(Generation)/ CNSUM(Load consume)
2. If the inverter shuts down before 24:00 on that day, the day statistic will not be stored.
5.8 Autotest Fast
Procedure: Press the Enter button and default password 00000, then press the Enter button to start the autotest.
The test progresses through various stages (e.g., Testing 59.S1..., Test59.S1 OK!). The system waits at each stage. After the test, use the up/down buttons to page through the test results.
Test Results Description:
Object | Description |
---|---|
27.S1 | Under voltage protection |
27.S2 | Under voltage protection |
59.S1 | Over voltage protection |
59.S2 | Over voltage protection |
81<S1 | Under frequency protection |
81<S2 | Under frequency protection |
81>S1 | Over frequency protection |
81>S2 | Over frequency protection |
6. Fault diagnosis and solutions
The inverter is easy to maintain. When you encounter the following problems, please refer to the Solutions below, and contact the local distributor if the problem remains unsolved. The following table lists some of the basic problems that may occur during actual operation as well as their corresponding basic solutions.
Fault diagnosis table
Content | Codes | Solutions |
---|---|---|
DischgOverCur | 00 | Battery discharge over current. (1) Nothing need to do, wait one minute for the inverter to restart. (2) Check whether the load is in compliance with the specification. (3) Cut off all the power and shut down all the machines; disconnect the load and plug in to restart machines, then check. |
Over Load | 01 | The load power is greater than other power (PV, BAT). (1) Check whether the load is in compliance with the maximum power of the machine. (2) Cut off all the power and shut down all the machines; disconnect the load and plug in to restart machines, then check whether the load is short-circuited if the fault has been eliminated. (3) Contact customer service if error warning continues. |
BatDisconnect | 02 | Battery Disconnect. (Battery voltage not identified) (1) Check whether the battery is connected. (2) Check if battery wiring port is open-circuited. (3) Contact customer service if error warning continues. |
Bat Under Vol | 03 | Battery voltage low that normal range. (1) Checking System Settings. If so, power off and restart. (2) Check if the grid power is down. If so, wait for the grid power up; the inverter will automatically charge. (3) Contact customer service if error warning continues. |
Bat Low capacity | 04 | Battery low that setting capacity (SOC<100%-DOD). |
Bat Over Vol | 05 | The battery voltage is greater than the Inverter maximum voltage. (1) Checking System Settings. If so, power off and restart. (2) Contact customer service if error warning continues. |
Grid low vol | 06 | Grid voltage is abnormal. (1) Check if the grid is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
Grid over vol | 07 | Grid voltage is abnormal. (1) Check if the grid is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
Grid low freq | 08 | Grid Frequency is abnormal. (1) Check if the grid is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
Grid overFreq | 09 | Grid Frequency is abnormal. (1) Check if the grid is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
gfci over | 10 | Inverter GFCI exceeds standard. (1) Check PV string for direct or indirect grounding phenomenon. (2) Check peripherals of machine for current leakage. (3) Contact the local inverter customer service if fault remains unremoved. |
bus under vol | 13 | BUS voltage is lower than normal. (1) Check the input mode setting is correct. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
bus over vol | 14 | BUS voltage is over maximum value. (1) Check the input mode setting is correct. (2) Restart the inverter and wait until it functions normally. |
Inv over cur | 15 | The inverter current exceeds the normal value. (1) Restart the inverter and wait until it functions normally. |
Chg over cur | 16 | Battery charge current over than the Inverter maximum voltage. (1) Restart the inverter and wait until it functions normally. |
Bus vol osc | 17 | Bus voltage instability. (1) Check the input and output mode setting is correct. (2) Restart the inverter and wait until it functions normally. |
Inv under vol | 18 | INV voltage is abnormal. (1) Check if the INV voltage is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
Inv over vol | 19 | INV voltage is abnormal. (1) Check if the INV voltage is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
InvFreqAbnor | 20 | INV frequency is abnormal. (1) Check if the INV frequency is abnormal. (2) Restart the inverter and wait until it functions normally. (3) Contact customer service if error warning continues. |
igbt temp high | 21 | The inverter temperature is higher than the allowed value. (1) Cut off all the power of the machine and wait one hour, then turn on the power of the machine. |
bat over temp | 23 | Battery temperature is higher than the allowed value. (1) Disconnect the battery and reconnect it after an hour. |
bat UnderTemp | 24 | Battery temperature is low than the allowed value. (1) Check the ambient temperature near the battery to see if it meets the specifications. |
BMS comm.fail | 27 | Communication between lithium battery and inverter is abnormal. (1) Check the cable, crystal, Line sequence. (2) Checking the Battery switch. |
Fan fail | 28 | Fan fail. (1) Check whether the Inverter temperature is abnormal. (2) Check whether the fans run properly. (If you can see it) |
Grid Phase err | 30 | The grid fault phase. (1) Check power grid wiring. |
Arc Fault | 31 | PV Arc Fault. (1) Check Photovoltaic panels, PV wire. (2) Contact customer service if error warning continues. |
bus soft fail | 32 | (1) Restart the inverter and wait until it functions normally. (2) Contact customer service if error warning continues. |
inv soft fail | 33 | |
bus short | 34 | |
inv short | 35 | |
fan fault | 36 | Fan fault. (1) Check whether the Inverter temperature is abnormal. (2) Check whether the fans run properly. (If you can see it) |
PV iso low | 37 | (1) Check if the PE line is connected to the inverter and is connected to the ground. (2) Contact customer service if error warning continues. |
Bus Relay Fault | 38 | (1) Restart the inverter and wait until it functions normally. (2) Contact customer service if error warning continues. |
Grid Relay Fault | 39 | |
EPS rly fault | 40 | |
Gfci fault | 41 | |
Selftest fail | 44 | |
System fault | 45 | |
Current DCover | 46 | |
Voltage DCover | 47 |
? Note: If an error occurs that is not listed in the table, Please Contact customer service.