Emerson™ Wireless 1410 A/B and 1410D Gateway with 781 Field Link

Quick Start Guide

Document Number: 00825-0200-4410, Rev EC

February 2019

NOTICE

This guide provides basic guidelines for the Emerson Wireless 1410 and 1410D Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless Gateway 1410 Reference Manual for more information and instructions. The manuals and this guide are available electronically on Emerson.com/Rosemount.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.

WARNING

Explosion hazard

Potential electrostatic charging hazard

Contents

1.0 Wireless planning

1.1 Power up sequence

The Gateway should be installed and functioning properly before power modules are installed in any wireless field devices. Wireless field devices should also be powered up in order of proximity from the Gateway beginning with the closest. This will result in a simpler and faster network installation.

1.2 Antenna position

The antenna should be positioned vertically and be approximately 6 ft. (2 m) from large structures or buildings to allow for clear communication to other devices.

1.3 Mounting height

For optimal wireless coverage, the remote antenna is ideally mounted 15–25 ft. (4.6–7.6 m) above ground or 6 ft. (2 m) above obstructions or major infrastructure.

2.0 PC requirements

2.1 Operating system (optional software only)

2.2 Applications

Configuration of the Gateway is done through a secure web interface. Recent versions of the following browsers are supported:

2.3 Hard disk space

3.0 Initial connection and configuration

To configure the Gateway, a local connection between a PC/Mac/laptop and the Gateway needs to be established. The Emerson 1410 and 1410D are operationally equivalent and the following instructions are applicable to both models.

3.1 Powering the Gateway

For both Emerson Wireless 1410A/B and the 1410D, bench top power will be needed to power the Gateway by wiring a 10.5–30 VDC (20–30 VDC if a 781 is connected with I.S. barriers to the Emerson 1410D) power source, with a capacity of at least 250 mA to the power terminals.

Figure 1. Emerson 1410A/B Gateway Housing

A. DIN Rail clip

B. SMA to N type connection

C. Power light. During normal operation the power indicator will be green.

D. Ethernet port 2. When this port is activated, the factory IP address is 192.168.2.10. See Table 1 on page 9.

E. Ethernet port 1. Use for standard communication to the webserver or other protocols enabled on the Gateway. The factory IP address is 192.168.1.10. See Table 1 on page 9.

F. Emerson 1410 power and serial connection. Black terminal included in the box.

Figure 2. Emerson 1410D Gateway Wiring

A. DIN Rail Clip

B. Power light. During normal operation the power indicator will be green.

C. Ethernet port 2. When this port is activated, the factory IP address is 192.168.2.10. See Table 1 on page 9.

D. Ethernet port 1. When this port is activated, the factory IP address is 192.168.1.10. See Table 1 on page 9.

E. Emerson 1410 Power and Serial connections. Black terminal included in the box.

F. Emerson Wireless 781 Field Link power and data connections. Black terminal included in box.

3.2 Establishing a connection

Connect the PC/laptop to the Ethernet 1 (Primary) receptacle on the Gateway using an Ethernet cable.

Windows 7

  1. Click the Internet Access icon on the bottom right of the screen.
  2. Select the Network and Sharing Center.
  3. Select Local Area Connection.
  4. Select Properties.
  5. Select Internet Protocol Version 4 (TCP/IPv4) then select Properties.

Note: If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured.

  1. Select the Use the following IP address button.
  2. In the IP address field, enter 192.168.1.12 (DeltaV Ready enter 10.5.255.12).
  3. In the Subnet mask field, enter 255.255.255.0.
  4. Select OK for both the Internet Protocol (TCP/IP) Properties window and the Local Area Connection Properties window.

Windows 10

  1. Select the network icon in the lower right corner.
  2. Select the Network settings link.
  3. Select Ethernet on the left hand side of the Network Settings dialog.
  4. Select Change adapter options.
  5. See steps 4-10 from Windows 7 instructions.

Note: Connecting to the Gateway's secondary Ethernet port will require different network settings.

Table 1. TCP/IP Network Settings

Interface Gateway PC/laptop/tablet Subnet
Ethernet 1 192.168.1.10 192.168.1.12 255.255.255.0
Ethernet 2 192.168.2.10 192.168.2.12 255.255.255.0

Disable proxies

  1. Open web browser.
  2. Navigate Tools > Internet Options > Connections > LAN Settings (may be a different process for other browsers).
  3. Under Proxy server, uncheck the Use a proxy server... box.

3.3 Configure the Gateway

To complete initial configuration for the Gateway:

  1. Access the default web page for the Gateway at https://192.168.1.10
    • Log on as Username: admin
    • Type in password: default
  2. Navigate to System Settings > Gateway > Ethernet Communication to enter the Network Settings.
    • Configure a static IP Address or set for DHCP and enter a Hostname.
    • Restart application at System Settings > Gateway > Backup and Restore > Restart Apps.

    Note: Resetting applications will temporarily disable communications with field devices.

  3. Disconnect the power and Ethernet cable from the Gateway.

4.0 Physical installation

4.1 Emerson 1410A/B and 1410D mounting

The unit can be snapped onto a DIN TS35/7.5 or TS35/15 rail system. To clip the unit onto the DIN rail, see Figure 7.

  1. Tilt the unit at a slight angle allowing the lower lip of the chassis to catch the bottom of the DIN rail.
  2. Apply pressure forward to snap the back of the unit securely onto the DIN rail.

Figure 7. Installing

To remove the unit, see Figure 8.

  1. Place a flat or rounded object (such as a screw driver) into the DIN clip and apply a slight pressure downwards on the object.
  2. Once the unit is released from the DIN rail, pull backwards and down to successfully disengage.

Figure 8. Removing

NOTICE

When mounting the unit in an electrical enclosure or other location, comply with the appropriate local and national installation codes. Verify that the installer, associated hardware, and installation equipment used have the proper certifications for the specific type of installation being performed. Before installation, verify if local codes require a permit and/or an inspection before energizing. When planning the installation, account for routing the antenna cable within the enclosure.

Note:

4.2 Connecting the Emerson 1410D with 781

There are two main connection configurations for the Emerson 1410D and 781: with and without barriers. The location and hazardous approval option of the Emerson 781 determines whether it needs to be installed with barriers.

Installation without barriers

A shielded twisted pair cable is needed for connecting the Emerson 1410D and 781 (refer to Figure 9). The Emerson 781 can be located up to 656 ft. (200m) from the Emerson 1410D.

Figure 9. Emerson 1410D and 781 without Barriers Installation

A. Emerson Wireless 1410D Gateway

B. Attach shield pair cable (Belden 3084A or equivalent)

C. Tape back shield wire and foils

D. Short these terminals to enable 250 Ω terminating resistor

E. Emerson Wireless 781 Field Link

Installation with barriers

When installing the Emerson 781 in a hazardous area there are two I.S. barriers that need to be installed: a power barrier and a signal barrier. The signal and the power are two separate I.S. circuits so they must comply with proper I.S. segregation distance. When using the Emerson recommended barriers the input power of the Gateway should be 20–30 VDC, with current capacity of at least 330 mA.

The signal barrier needs additional power. You can wire it to the Emerson 1410D terminals or to a separate power supply. Make sure power supply is rated to handle power drawn for the barrier. Figure 10 and Figure 11 show the two variations of powering the signal barrier.

Figure 10. Emerson 1410D and 781 with Gateway Powered Barrier Installation

A. Emerson Wireless 1410D Gateway

B. Attach shield pair cable (Belden 3084A)

C. Tape back shield wire and foils

D. Short these terminals for 250 Ω

E. Emerson Wireless 781 Field Link

F. I.S. segregation

G. Shield

Figure 11. Emerson 1410D and 781 with Additional Power Supplied Barrier Installation

A. Emerson Wireless 1410D Gateway

B. Attach shield pair cable (Belden 3084A)

C. Tape back shield wire and foils

D. Short these terminals for 250 Ω

E. Emerson Wireless 781 Field Link

F. I.S. segregation

G. Shield

Recommendation

4.3 Connecting the Emerson 1410A/B with the remote antenna

WARNING

When installing remote mount antennas for the Gateway, always use established safety procedures to avoid falling or contact with high-power electrical lines.

Install remote antenna components for the Gateway in compliance with local and national electrical codes and use best practices for lightning protection.

Before installing, consult with the local area electrical inspector, electrical officer, and work area supervisor.

The Gateway remote antenna option is specifically engineered to provide installation flexibility while optimizing wireless performance and local spectrum approvals. To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type.

If the supplied remote mount antenna kit is not installed per these instructions, Emerson is not responsible for wireless performance or non-compliance with spectrum regulations.

Use only Emerson provided remote antenna, coaxial RF cable, and lightning arrestor. The remote antenna lightning arrestor must be installed and grounded in accordance with Figure 13.

Locate the remote antenna to achieve optimal wireless performance. Ideally this will be 15–25 ft. (4.6–7.6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure. To install the remote antenna, use one of the following procedures:

Installation of WL2/WN2 option

  1. Mount the antenna on a 11/2- to 2-in. pipe mast using the supplied mounting equipment.
  2. Connect the lightning arrestor either to the electrical cabinet or directly outside the wall or right outside the wall (depending on where the Gateway is located).
  3. Install the grounding lug, lock washer, and nut on top of the lightning arrestor.
  4. Bond the grounding terminal of the lightning arrestor to a common earth point using individual high integrity, low resistance means as shown in Figure 13.
  5. The DIN rail cabinet must be grounded as well. A #6 AWG (or 4.11 mm European) copper wire bonding conductor with the shortest length possible, no sharp bends, and no coiling is recommended.
  6. All the outdoor connections should be made hand tight plus an 1/8th turn with a wrench and wrapped with the coaxial seal (shown in Figure 14).
  7. Ensure the mounting mast, lightning arrestor, and Gateway are grounded according to local/national electrical code.

Any spare lengths of coaxial cable should be placed in 1 ft. (0.3 m) coils.

Figure 13. Installation of WL2/WN2 Option

Note: Weather proofing is required

The remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor, antenna, and Gateway. The coaxial sealant must be applied to guarantee performance of the wireless field network. See Figure 14 for details on how to apply weather proofing.

Figure 14. Applying Coaxial Sealant to Cable Connections

Table 2. Remote Antenna Kit Options

Kit option Antenna Cable 1 Cable 2 Lightning arrestor
WL2 1/2 Wavelength Dipole Omni-Directional +6 dB Gain 50 ft. (15,2 m) LMR-400 N/A Head mount, jack to plug Gas discharge tube 0.5 dB insertion loss
WN2 1/2 Wavelength Dipole Omni-Directional +8 dB Gain 25 ft. (7,6 m) LMR-400 N/A Head mount, jack to plug Gas discharge tube 0.5 dB insertion loss

4.4 Connect to the host system

  1. Wire the Gateway's Ethernet 1 (Primary) or Serial Output connection to the Host System Network or Serial I/O (see Figure 1 and Figure 2 for hardware drawings).
  2. For serial connections, make sure all terminations are clean and secure to avoid wiring connection problems.

4.5 Best practice

Twisted shielded pair cable is generally used to wire the serial connection, and it is standard practice to ground the shield on the serial host side leaving the shield floating on the Gateway side. Insulate the shield to avoid grounding issues.

In accordance with Emerson WirelessHART® security guidelines (Emerson Wireless Security Whitepaper), the Gateway should be connected to the Host System via a LAN (Local Area Network) and not a WAN (Wide Area Network).

5.0 Software installation (optional)

The 2-disk software pack contains the Security Setup Utility (only required for secure host connections or OPC communications) and AMS Wireless Configurator. The Security Setup Utility is located on Disk 1. To install the software:

  1. Exit/close all Windows programs, including any running in the background, such as virus scan software.
  2. Insert Disk 1 into the CD/DVD drive of the PC.
  3. If the setup program does not appear, go into the disc's file and run autorun.exe.
  4. Follow the prompts.

AMS Wireless Configurator is located on Disk 2. To install the software:

  1. Exit/close all Windows programs, including any running in the background, such as virus scan software.
  2. Insert Disk 2 into the CD/DVD drive of the PC.
  3. Select Install from the menu when the AMS Wireless Configurator setup begins.
  4. Follow the prompts.
  5. Allow AMS Wireless Configurator to reboot PC.
  6. Do not remove the disk from the CD/DVD drive.
  7. Installation will resume automatically after login.
  8. Follow the prompts.

Note: If the autorun function is disabled on the PC, or installation does not begin automatically, double click D:\SETUP.EXE (where D is the CD/DVD drive on the PC) and select OK.

For more information about the Security Setup Utility and AMS Wireless Configurator, see the Emerson Wireless Gateway 1410 Reference Manual.

6.0 Verify operations

Operation is verified through the web interface by opening a web browser from any PC on the host system network and entering the Gateway IP address or DHCP host name in the address bar. If the Gateway has been connected and configured properly, the security alert will be displayed followed by the log in screen.

Figure 15. Gateway Log In Screen

The Gateway is now ready to be integrated into the host system. If wireless field devices were ordered with the Gateway, they were preconfigured with the same Network ID and Join Key information. Once the field devices are powered, they will appear on the wireless network and communications can be verified under the Explore tab using the web interface. The time needed for the network to form will depend on the number of devices.

For more detailed installation instructions, see the Emerson Wireless Gateway 1410 Reference Manual.

7.0 Product Certification

7.1 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at Emerson.com/Rosemount.

7.2 Telecommunication Compliance

All wireless devices require certification to ensure they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.

7.3 FCC and IC

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.

7.4 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

North America

N5 U.S.A. Division 2

Certificate: 2646342 (CSA)

Standards: CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 213-M1987 (2013), CSA C22.2 No. 61010-1-2012, ANSI/ISA-12.12.01 - 2012, UL61010-1, 3rd Edition

Markings: Suitable for CL I, DIV 2, GP A, B, C, D;

Temperature Code: T4 (-40 °C ≤ T』 ≤ 70 °C)

Note:

Canada

N6 Canada Division 2

Certificate: 2646342 (CSA)

Standards: CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 213-M1987 (R2013), CSA C22.2 No. 61010-1 - 2012, ANSI/ISA-12.12.01 - 2012, UL61010-1, 3rd Edition

Markings: Suitable for CL I, DIV 2, GP A, B, C, D

Temperature code: T4 (-40 °C ≤ T』 ≤ 70 °C)

Note:

Europe

N1 ATEX Type n

Certificate: Baseefa14ATEX0125X

Standards: EN 60079-0: 2012, EN 60079-15: 2010

Markings: II 3 G Ex nA IIC T4 Gc, T4(−40 °C ≤ T』 ≤ +75 °C), VMAX = 30 Vdc

Special Conditions for Safe Use (X):

  1. The equipment must be installed in an area of not more than Pollution Degree 2 as defined in IEC 60664-1, and in an enclosure that provides a degree of protection of at least IP54 and meets the relevant requirements of EN 60079-0 and EN 60079-15.
  2. External connections to the equipment must not be inserted or removed unless either the area in which the equipment is installed is known to be non-hazardous, or the circuits connected have been de-energized.
  3. The equipment is not capable of withstanding the 500 V electrical strength test as defined in clause 6.5.1 of EN 60079-15: 2010. This must be taken into account during installation.
  4. When fitted, the surface resistivity of the remote antenna is greater than 1 GΩ. To avoid electrostatic charge build up, it must not be rubbed with a dry cloth or cleaned with solvents.

Note: Currently not available for Emerson 1410D option.

International

N7 IECEx Type n

Certificate: IECEx BAS 14.0067X

Standards: IEC 60079-0: 2011, IEC 60079-15: 2010

Markings: Ex nA IIC T4 Gc, T4(−40 °C ≤ Tą ≤ +75°C), VMAX = 30 Vdc

Special Conditions for Safe Use (X):

  1. See certificate for special conditions.

Note: Currently not available for Emerson 1410D option.

EAC - Belarus, Kazakhstan, Russia

NM Technical Regulation Customs Union (EAC) Type n

Certificate: TC RU C-US.Gb05.B.01111

Markings: 2Ex nA IIC T4 Gc X, T4(−40 °C ≤ Tą ≤ +75 °C), VMAX = 30 Vdc

Special Condition for Safe Use (X):

  1. See certificate for special conditions.

Note: Currently not available for Emerson 1410D option.

Figure 16. Emerson 1410 Wireless Gateway Declaration of Conformity

EMERSON. EU Declaration of Conformity

No: RMD 1093 Rev. G

We, Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA declare under our sole responsibility that the product, Rosemount 1410 Wireless Gateway manufactured by, Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.

Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.

(signature) Chris LaPoint (name) Vice President of Global Quality (function) 1-Feb-19 (date of issue)

EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1:2013

Radio Equipment Directive (RED) (2014/53/EU) Harmonized Standards: EN 300 328 V2.1.1 EN 301 489-17: V3.2.0 EN 60950-1:2006+A11+A12+A1+A2 EN 50371: 2002

ATEX Directive (2014/34/EU) Baseefa14ATEX0125X – Type n Certificate Equipment Group II, Category 3 G Ex nA IIC T4 Gc Harmonized Standards: EN 60079-0: 2012 + A11:2013 EN 60079-15: 2010

ATEX Notified Body SGS FIMKO ΟΥ [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland

ATEX Notified Body for Quality Assurance SGS FIMKO ΟΥ [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland

List of Rosemount 1410 Parts with China RoHS Concentration above MCVs

Part Name Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium (Cr +6) Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE)
Electronics Assembly X O O O O O

This table is proposed in accordance with the provision of SJ/T11364.

O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.

X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.

Shield grounding

The shield of the twisted pair cable needs to be grounded using the grounding terminal on the Emerson 1410D, and it should be taped back on the Emerson 781 side.

Emerson 1410D Grounding

The Emerson 1410D DIN rail cabinet must be grounded as well. A #6 AWG (4.11 mm European) copper wire bonding connector with the shortest length possible, no sharp bends, and no coiling is recommended.

Figure 12. Emerson 1410D Grounding

A. #6 AWG copper wire

B. Protective ground

C. Reference ground (when present)

D. Earth

Emerson 781 grounding

Grounding of the electronics enclosure should be done in accordance with local and national installation codes. Grounding is accomplished through the external case grounding terminal.

A. Grounding lug

Terminating resistances

For best performance, the terminating resistances should be matched across the Emerson 1410D, 781, and the signal barrier. The Emerson 1410D has an integral 250 Ω terminating resistor. Short the Emerson 781 terminator terminals to engage a 250 Ω resistor (note D of Figure 10 and Figure 11). The recommended barriers can also be switched to 250 Ω.

PDF preview unavailable. Download the PDF instead.

quick-start-guide-emerson-smart-wireless-gateway-1410-en-77568 Acrobat Distiller 11.0 (Windows)

Related Documents

Preview Emerson Rosemount 1410 Wireless Gateway Technical Drawings
Technical drawings and specifications for the Emerson Rosemount 1410 Wireless Gateway and related components, including the 781 Wireless Field Link.
Preview Emerson Wireless Field Link: Quick Start Guide for Industrial Wireless Communication
Get started with the Emerson Wireless Field Link. This quick start guide provides essential installation, setup, and operational information for the Rosemount 781 Wireless Field Link, focusing on industrial wireless communication and safety.
Preview Emerson Wireless 1410S Gateway: Quick Start Guide for Industrial Wireless Connectivity
This Quick Start Guide provides essential information for the Emerson Wireless 1410S Gateway, covering installation, configuration, and safety procedures for reliable industrial wireless communication. Learn how to set up your gateway efficiently.
Preview Smart Wireless Gateway Reference Manual
Comprehensive reference manual for the Emerson Smart Wireless Gateway, detailing installation, configuration, operation, and troubleshooting for industrial wireless communication networks.
Preview Emerson Wireless 1410S Gateway: Next Generation Wireless Infrastructure
Discover the Emerson Wireless 1410S Gateway, a versatile wireless networking solution for industrial facilities. Learn about its features, specifications, and how it enhances wireless infrastructure for improved productivity and safety.
Preview Emerson Synchros WirelessHART Platform Quick Start Guide
This guide provides basic guidelines for the Emerson Synchros WirelessHART Platform for commissioning and provisioning sensor modules. It covers device preparation, provisioning, commissioning, battery information, and product certifications.
Preview Emerson AMS Device Manager v14.5 FP3 Product Data Sheet
Product data sheet for Emerson's AMS Device Manager v14.5 FP3, detailing its capabilities in predictive diagnostics, device configuration, calibration, asset management, security, and integration for industrial automation.
Preview Rosemount 3051HT Hygienic Pressure Transmitter Quick Start Guide | Emerson
This Quick Start Guide provides essential information for installing, configuring, and trimming the Rosemount 3051HT Hygienic Pressure Transmitter. It covers system readiness, mounting, wiring, switch settings, HART Revision capabilities (5 and 7), and product certifications (3-A, EHEDG, ASME-BPE, ATEX, IECEx). Includes detailed diagrams and procedures for optimal operation.