Quick Start Guide 00825-0100-4091, Rev CA
August 2017
RosemountTM 3051HT Hygienic Pressure Transmitter
with 4­20 mA HART® Revision 5 and 7 Protocol
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host systems. See page 3 for system readiness.

Quick Start Guide

August 2017

NOTICE
This guide provides basic guidelines for the Rosemount 3051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations.

Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate
local, national, and international standards, codes, and practices.  Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments
in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.  In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.  To avoid process leaks, only use the gasket designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.  Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries  Unless marked, the conduit/cable entries in the transmitter housing use a 1/2­14 NPT thread form. Only
use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.

Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . . . 3 Connect the wiring and power up . . . . . . . . . . . 7 Transmitter installation . . . . . . . . . . . . . . . . . . . . 4 Verify configuration . . . . . . . . . . . . . . . . . . . . . . . 9 Mount the transmitter. . . . . . . . . . . . . . . . . . . . . 4 Trim the transmitter. . . . . . . . . . . . . . . . . . . . . . 12 Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product Certifications . . . . . . . . . . . . . . . . . . . . 14
2

August 2017

Quick Start Guide

1.0 System readiness

1.1 Confirm HART Revision capability
 If using HART based control or asset management systems, confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7.
 For instructions on how to change the HART Revision of your transmitter, see page 11.
1.2 Confirm correct device driver
 Verify the latest device driver (DD/DTMTM) is loaded on your systems to ensure proper communications.
 Download the latest device driver at Emerson.com or hartcomm.org.
Rosemount 3051 device revisions and drivers
Table 1 provides the information necessary to ensure you have the correct device driver and documentation for your device.
Table 1. Rosemount 3051 Device Revisions and Files

Software release date
Dec-11

Identify device HART software
Revision
01

Find device driver

HART universal

Device

Revision

Revision(1)

7

10

5

9

Review functionality
Changes to software(2)
See Footnote 2 for list of changes.

1. Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
2. HART Revision 5 and 7 Selectable, Power Diagnostics, Safety Certified, Local Operator Interface, Process Alerts, Scaled Variable, Configurable Alarms, Expanded Engineering Units.

3

Quick Start Guide

August 2017

2.0 Transmitter installation

2.1 Mount the transmitter
Orient the transmitter to desired orientation before mounting. Transmitter must not be securely mounted or clamped in place when changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 3051HT, it is recommended installing so the conduit entry faces downward or parallel to the ground to maximize drainability when cleaning.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA® Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress Protection ratings are required.

Note
IP69K rating only available on units with a SST housing and option code V9 in the model string.

For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located on the neck of the transmitter via a protected gage vent (See Figure 1).
Keep the vent path free from obstructions including but not limited to paint, dust, and viscous fluids by mounting the transmitter so the process can drain away.

Figure 1. In-line Protected Gage Vent Low Side Pressure Port

Aluminum

Polished 316 SST

A
A. Low side pressure port (atmospheric reference)
4

August 2017

Quick Start Guide

Clamping When installing clamp, follow recommended torque values provided by gasket manufacturer(1).
2.2 Set the switches

Set alarm and security switch configuration before installation as shown in Figure 2.
 The alarm switch sets the analog output alarm to high or low. - Default alarm is high.
 The security switch allows (unlocked symbol) or prevents (locked symbol) any configuration of the transmitter. - Default security is off (unlocked symbol).
Use the following procedure to change the switch configuration: 1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small screwdriver.
4. Reattach the transmitter cover.  The covers must only be capable of being released or removed with the aid of a tool to comply with applicable ordinary locations requirements.  The cover must be fully engaged to comply with explosion-proof requirements.

1. To maintain transmitter performance, torquing a 1.5-in. Tri Clamp beyond 50 in-lb is not recommended on pressure ranges below 20 psi.
5

Quick Start Guide

August 2017

Figure 2. Transmitter Electronics Board
Without LCD display Aluminum

With LOI or LCD display

A. Alarm B. Security

A B
Polished 316 SST
A B

6

August 2017
2.3 Connect the wiring and power up
Figure 3. Transmitter Wiring Diagrams (4­20 mA)
Aluminum

Quick Start Guide

A
B C

Polished 316 SST
A
B C

A. 24 Vdc supply B. RL  250 C. Current meter (optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 ft. (1,500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
 Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051HT case is properly grounded.
 Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.  Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the
terminal block.
7

Quick Start Guide

August 2017

Use the following steps to wire the transmitter: 1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the "+" terminal (PWR/COMM) and the negative lead to the "­" terminal.
3. Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.

Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.

4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important the instrument cable shield be:  Trimmed close and insulated from touching the transmitter housing  Connected to the next shield if cable is routed through a junction box  Connected to a good earth ground at the power supply end
6. If transient protection is needed, refer to section "Grounding for transient terminal block" for grounding instructions.
7. Plug and seal unused conduit connections.
8. Reattach the transmitter covers.  The covers must only be capable of being released or removed with the aid of a tool to comply with applicable ordinary locations requirements.  The cover must be fully engaged to comply with explosion-proof requirements.

Figure 4. Wiring
Aluminum
A C
B

Polished 316 SST
A C
B

DP

E

D

DP
ED

A. Minimize distance B. Trim shield and insulate C. Protective grounding terminal

D. Insulate shield E. Connect shield back to the power supply
ground

8

August 2017

Quick Start Guide

Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow Connect the wiring and power up, step 1 through 8. When the transmitter is properly wired, refer to Figure 4 for internal and external transient grounding locations.

Note
The Rosemount 3051HT polished 316 SST housing only provides ground termination inside the terminal compartment.
2.4 Verify configuration
Verify the configuration using any HART capable configuration tool or Local Operator Interface (LOI) - option code M4. Configuration instructions for a Field Communicator and LOI are included in this step.
Verifying configuration with a Field Communicator
A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 2 on page 9. For Fast Key sequences using legacy DD's, contact your local EmersonTM representative.

Note
Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com/Field-Communicator for information on updating the DD Library.

1. Verify device configuration using the Fast Key sequences in Table 2.  A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of configuration and startup.
Table 2. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence

Function
 Alarm and Saturation Levels  Damping  Range Values  Tag  Transfer Function  Units

Fast Key sequence

HART 7

HART 5

2, 2, 2, 5, 7

2, 2, 2, 5, 7

2, 2, 1, 1, 5

2, 2, 1, 1, 5

2, 2, 2

2, 2, 2

2, 2, 7, 1, 1

2, 2, 7, 1, 1

2, 2, 1, 1, 6

2, 2, 1, 1, 6

2, 2, 1, 1, 4

2, 2, 1, 1, 4

9

Quick Start Guide

August 2017

Table 2. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence

Function
Burst Mode Custom Display Configuration Date Descriptor Digital to Analog Trim (4­20 mA Output) Disable Configuration Buttons Rerange with Keypad Loop Test Lower Sensor Trim Message Scaled D/A Trim (4­20 mA Output) Sensor Temperature/Trend (3051S) Upper Sensor Trim Digital Zero Trim Password Scaled Variable HART Revision 5 to HART Revision 7 switch Long Tag(1) Find Device(1) Simulate Digital Signal(1)

Fast Key sequence

HART 7

HART 5

2, 2, 5, 3 2, 2, 4
2, 2, 7, 1, 4 2, 2, 7, 1, 5
3, 4, 2 2, 2, 6, 3 2, 2, 2, 1
3, 5, 1 3, 4, 1, 2 2, 2, 7, 1, 6
3, 4, 2 3, 3, 3 3, 4, 1, 1 3, 4, 1, 3 2, 2, 6, 5

2, 2, 5, 3 2, 2, 4
2, 2, 7, 1, 3 2, 2, 7, 1, 4
3, 4, 2 2, 2, 6, 3 2, 2, 2, 1
3, 5, 1 3, 4, 1, 2 2, 2, 7, 1, 5
3, 4, 2 3, 3, 3 3, 4, 1, 1 3, 4, 1, 3 2, 2, 6, 4

3, 2, 2 2, 2, 5, 2, 3

3, 2, 2 2, 2, 5, 2, 3

2, 2, 7, 1, 2

N/A

3, 4, 5

N/A

3, 4, 5

N/A

1. Only available in HART Revision 7 mode.
Verifying configuration with LOI
The optional LOI can be used for commissioning the device. The LOI is a two-button design with internal and external/rear buttons. On a polished stainless steel housing, buttons are located internally both on the display and terminal side of the transmitter. On an aluminum housing, buttons are located on the display and externally underneath the top metal tag. To activate the LOI, push any button. LOI button functionality is shown on the bottom corners of the display. See Table 3 and Figure 5 for button operation and menu information.

10

August 2017
Table 3. LOI Button Operation

Button

Left

No

Right

Yes

Figure 5. LOI Menu

Quick Start Guide
SCROLL ENTER

Assign PV
HART Revision
Switch HART Revision mode If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 3051 will load a generic menu with limited capability. The following procedures will switch the HART Revision mode from the generic menu: 1. Manual Setup > Device Information > Identification > Message
a. To change to HART Revision 5, Enter: HART5 in the Message field. b. To change to HART Revision 7, Enter: HART7 in the Message field. Note
See Table 2 on page 9 to change HART Revision when the correct device driver is loaded.
11

Quick Start Guide

August 2017

2.5 Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage transmitter to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.

Note
When performing a zero trim, ensure the equalization valve is open and all wet legs are filled to the correct level.

It is not recommended to zero an absolute transmitter, Rosemount 3051HTA model.

1. Choose your trim procedure. a. Analog zero trim ­ Sets the analog output to 4 mA.  Also referred to as a "rerange" it sets the lower range value (LRV) equal to the measured pressure.  The display and digital HART output remains unchanged. b. Digital zero trim ­ Recalibrates the sensor zero.  The LRV is unaffected. The pressure value will be zero (on display and HART output). 4 mA point may not be at zero.  This requires the factory calibrated zero pressure is within a range of 3% of the URL [0 ± 3%  URL].
Example URV = 250 inH2O Applied Zero Pressure = ± 0.03 250 inH2O = ± 7.5 inH2O (compared to factory settings) values outside this range will be rejected by the transmitter
Trimming with a Field Communicator
1. Connect the Field Communicator, see "Connect the wiring and power up" on page 7 for instructions.
2. Follow the HART menu to perform the desired zero trim.
Table 4. Zero Trim Fast Keys

Fast Key sequence

Analog zero (set 4 mA) 3, 4, 2

Digital zero 3, 4, 1, 3

Trimming with configuration buttons
A zero trim is to be performed using one of the three possible sets of configuration buttons located above the terminal block or under the top tag.
To access the configuration buttons on a polished stainless steel housing, remove the terminal side housing cover.
To access the configuration buttons on an aluminum housing, loosen the screw on the top tag and slide the tag on the top of the transmitter.

12

August 2017

Quick Start Guide

Figure 6. External or Rear/Terminal-Side Configuration Buttons

LOI

Analog zero and span

Digital zero

Aluminum

A

Polished 316 SST
A
N/A(1)
A. Configuration buttons
1. LOI buttons (option M4) only offer front facing buttons on SST housing (option 1). Options D4 and DZ can still be purchased for rear/terminal-side facing buttons.
Use the following procedures to perform a zero trim: Perform trim with LOI (option M4) 1. Set the transmitter pressure. 2. See Figure 5 on page 11 for the operating menu.
a. Perform an analog zero trim by selecting Rerange. b. Perform a digital zero trim by selecting Zero Trim. Perform trim with analog zero and span (option D4) 1. Set the transmitter pressure. 2. Press and hold the Zero button for two seconds to perform an analog zero trim. Perform trim with digital zero (option DZ) 1. Set the transmitter pressure. 2. Press and hold the Zero button for two seconds to perform a digital zero trim.
13

Quick Start Guide

August 2017

3.0 Product Certifications

3.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.
3.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

Altitude 5000 m max

Pollution degree
4 (metallic enclosure) 2 (non-metallic enclosure)

3.3 Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

3.4 USA

I5 Intrinsic Safety; Nonincendive Certificate: 1053834 Standards: FM Class 3600 ­ 2011, FM Class 3610 ­ 2010, FM Class 3611 ­ 2004, FM Class 3810 ­ 2005 Markings: IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-1024, CL I ZONE 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D T5; T4(­20 °C  Ta  +70 °C) [HART]; T4(­20 °C  Ta  +60 °C) [Fieldbus]; Type 4x
3.5 Canada

I6 Intrinsic Safety Certificate: 1053834 Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987 Markings: Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T4; Suitable for Class I, Zone 0; Type 4X; Factory Sealed; Single Seal (See drawing 03031-1053)
3.6 Europe

I1 ATEX Intrinsic Safety Certificate: BAS97ATEX1089X Standards: EN 60079-0:2012 + A11:2013, EN 60079-11:2012

14

August 2017

Quick Start Guide

Markings: HART: II 1 G Ex ia IIC T5/T4 Ga, T5(­20 °C  Ta  +40 °C), T4(­20 °C  Ta  +70 °C) Fieldbus: II 1 G Ex ia IIC Ga T4(­20 °C  Ta  +60 °C)

Table 5. Input Parameters

Parameter

HART

Fieldbus/PROFIBUS

Voltage Ui Current Ii Power Pi Capacitance Ci Inductance Li

30 V 200 mA 0.9 W 0.012 F
0 mH

30 V 300 mA 1.3 W
0 F 0 mH

Special Conditions for Safe Use (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by
clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus. 2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.

3.7 International

I7 IECEX Intrinsic Safety
Certificate: IECEx BAS 09.0076X
Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: HART: Ex ia IIC T5/T4 Ga, T5(­20 °C  Ta  +40 °C), T4(­20 °C  Ta  +70 °C)
Fieldbus: Ex ia IIC T4 Ga(­20 °C  Ta  +60 °C)

Table 6. Input Parameters

Parameter

HART

Fieldbus/PROFIBUS

Voltage Ui Current Ii Power Pi Capacitance Ci Inductance Li

30 V 200 mA 0.9 W 0.012 F
0 mH

30 V 300 mA 1.3 W
0 F 0 mH

Special Conditions for Safe Use (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by
clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus. 2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.

15

Quick Start Guide

August 2017

3.8 Additional Certifications
3-A® All Rosemount 3051HT transmitters with the following connections are 3-A approved and labeled: T32: 11/2-in. Tri Clamp T42: 2-in. Tri Clamp If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of 3-A certifications. A 3-A certificate of compliance is available by selecting option code QA.
EHEDG All Rosemount 3051HT transmitters with the following connections are EHEDG approved and labeled: T32: 11/2-in. Tri Clamp T42: 2-in. Tri Clamp If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of EHEDG certifications. An EHEDG certificate of compliance is available by selecting option code QE. Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements.
ASME-BPE All Rosemount 3051HT Transmitters with option F2 and the following connections are designed to ASME-BPE SF4 standards(1): T32: 11/2-in. Tri Clamp T42: 2-in. Tri Clam A self-certified certificate of compliance to ASME-BPE is also available (option QB)

1. Per Clause SD-2.4.4.2 (m), suitability of painted aluminum housings to be determined by end user.
16

August 2017
Figure 7. Rosemount 3051HT Declaration of Conformity

Quick Start Guide

EU Declaration of Conformity
No: RMD 1106 Rev. D
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
RosemountTM 3051HT Pressure Transmitter
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.

(signature)
Chris LaPoint
(name)

Page 1 of 3

Vice President of Global Quality
(function)
19-July-2017
(date of issue)

17

Quick Start Guide

August 2017

EU Declaration of Conformity
No: RMD 1106 Rev. D
EMC Directive (2014/30/EU)
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
RoHS Directive (2011/65/EU) ­ Effective from 22 July 2017
This product conforms to Directive 2011/65/EU of the European Parliament and of the Council on the restriction of the use of certain hazardous substances in electrical and electronic equipment.
ATEX Directive (2014/34/EU)
BAS97ATEX1089X - Intrinsic Safety Equipment Group II Category 1 G Ex ia IIC T5/T4 Ga Harmonized Standards Used: EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3105X - Type n and Certificate Equipment Group II Category 3 G Ex nA IIC T5 Gc Harmonized Standards Used: EN60079-0:2012 + A11:2013, EN60079-15:2010
Baseefa11ATEX0275X - Dust Certificate Equipment Group II Category 1 D Ex ta IIIC T95°C T500105°C Da Harmonized Standards Used: EN60079-0:2012 + A11:2013, EN60079-31:2014
Page 2 of 3

18

August 2017

Quick Start Guide

EU Declaration of Conformity
No: RMD 1106 Rev. D
ATEX Notified Body
SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom
ATEX Notified Body for Quality Assurance
SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom

Page 3 of 3
19

Quick Start Guide

August 2017

China RoHSRosemount 3051HT
List of Rosemount 3051HT Parts with China RoHS Concentration above MCVs
/ Hazardous Substances 

 Part Name

 Lead

(Pb)

 Mercury
(Hg)

 Cadmium
(Cd)

 Hexavalent Chromium
(Cr +6)

 Polybrominated
biphenyls (PBB)

 Polybrominated diphenyl ethers
(PBDE)



Electronics

X

O

O

O

O

O

Assembly



Housing

O

O

O

O

O

O

Assembly



Sensor

X

O

O

O

O

O

Assembly

SJ/T11364 This table is proposed in accordance with the provision of SJ/T11364.

O: GB/T 26572 O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.

X: GB/T 26572 X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.

20

August 2017

Quick Start Guide

21

Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office Emerson Automation Solutions Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com

*00825-0100-4091*
Quick Start Guide 00825-0100-4091, Rev CA
August 2017
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. National Electrical Code is a registered trademark of National Fire Protection Association, Inc. DTM is a trademark of the FDT Group. HART is a registered trademark of the FieldComm Group. 3-A is a registered trademark of 3-A Sanitary Standards, Inc. All other marks are the property of their respective owners. © 2017 Emerson Process Management. All rights reserved.

