E3Point® Gas Monitor - Quick Start Guide
Introduction
The E3Point® gas detection system integrates a gas sensor (electrochemical or catalytic type), a control unit, a buzzer, a relay, and RS-485 into one reliable and robust product. The polycarbonate housing is resistant to rust, dents, and corrosion, making it suitable for commercial use in certain outdoor and indoor environments like parking garages and mechanical rooms.
Installation
Key installation considerations include height and detection objectives. For fastest leak detection, mount the sensor near potential leak sources. This may mean the indicated concentration isn't representative of personnel exposure, and calibration/maintenance access might be difficult. Assess local air currents, as they often influence gas concentration areas more than vapor density. Generally, place at least one sensor near likely emission points, ensuring it's accessible for calibration and maintenance.
For personnel protection, mount the unit in the “breathing zone” (3.5 to 5 ft. / 1 to 1.5m from the ground). Protect the sensor from water, wash-down, and excessive humidity. Keep sensor and wire runs away from mercury vapor lights, variable speed drives, and radio repeaters to prevent electrical interference. Protect the sensor from physical damage. Do not mount the sensor flat on a ceiling or on a vibrating surface.
Detected Gas Installation Heights
Detected Gas | Relative Density (air = 1) | Installation Height |
---|---|---|
CO Carbon monoxide | 0.968 | 1–1.5 m (3–5 ft.) from floor |
H₂S Hydrogen sulfide | 1.19 | 30 cm (1 ft) from floor |
NO₂* Nitrogen dioxide | 1.58 (cold) | 30 cm–1 m (1–3 ft) from ceiling |
O₂ Oxygen | 1.43 | 1–1.5 m (3–5 ft) from floor |
Combustibles | Most are heavier than air (exceptions: methane, hydrogen, ethylene, acetylene) | Heavier than air: approx. 30 cm (1 ft) from floor. Lighter than air: 30 cm (1 ft) from ceiling, near leak source. |
*May differ in certain applications. Hot NO₂ from exhaust systems is lighter than ambient air.
Duct Mounting
Use the custom housing provided with the duct mount version. Ensure airflow is between 500–4000 fpm for best results.
- Measure and mark holes for intake and exhaust tubes.
- Drill holes in the duct: 1 1/2 in. (38 mm) for air intake, 1/2 in. (13 mm) for air exhaust.
- Affix intake and exhaust tubes to the duct mount housing.
- Insert tubes into the duct holes.
- Orient air holes on the intake tube to face the airflow.
- Attach housing to duct with four 8 x 3/4” galvanized or zinc-plated sheet metal screws (not provided).
- Remove a knockout for cable entry and affix appropriate conduit.
- Run wiring through conduit and housing to the monitor.
- Connect wires (see Wiring section).
- Screw the cover onto the monitor and replace the housing cover.
Dimensions: 11.1 cm (4 3/8”) height, 8.3 cm (3.281”) width.
Wall Mounting
Mounting is typically on concrete walls or columns, but can be on any vertical surface or standard electrical junction box. The housing has rear spacers for moisture flow. Mounting holes are inside the housing.
- Open the unit and drill holes: 4 3/8” (11.1 cm) apart for wall mounting, or 3.281” (8.3 cm) height for electrical boxes. Do not remove the PC board when removing knockouts.
- Mount securely using appropriate screws and anchors (#6 screws recommended).
- Tighten screws to 8.7 in-lb (1 Nm) maximum.
- Close the unit cover and tighten cover screws to 29.7 in-lb (3 Nm).
Wiring
Power wiring must comply with all applicable codes. Minimum #20 AWG for general wiring; #14 or #12 AWG for 120 VAC. Signal wiring should use #20-24 AWG shielded twisted pair cable (e.g., Belden 9841). Network units should not exceed 2,000 ft (600 m) of #22 AWG wire; smaller gauges are limited by resistance.
Power wiring must be grounded at the screw and nut on the grounding plate inside the case.
Wiring Standalone Units
Ground the shield at the main control panel. Connect the shield wire to the “shield” terminal block. Tape all exposed shield wire at the sensor to insulate it from the enclosure.
- Electrical Power: 24 VDC/VAC nominal, 0.35 amp maximum. AC or DC can be connected.
- Output: 4-20 mA linear output from the sensor. Monitoring equipment may have a maximum impedance of 500 ohms.
- Circuit Board Connections: Power to J1, communication to J2, external devices (ventilators, strobes) to relay terminals J5 or J6.
- Relay Output: 2 DPDT relays, 5A @ 250VAC.
Wiring Diagrams:
- 3-Wire Current Sink Output (DC supply only)
- 4-Wire Current Sink Output
- 120 VAC Connection (transformer pre-wired under PCB)
Connecting a Remote to the Main Unit
Use #20-24 AWG shielded twisted pair cable (e.g., Belden 9841). Remote sensors should not exceed 200 ft (61 m) of #22 AWG wire. OUT1 and OUT2 connectors on the remote sensor are not used.
Wiring Network Units
Ensure minimum voltage requirements are respected.
User Interface
The E3Point® gas monitor features a 2-line, 8-character LCD screen for displaying readings and accessing programming/calibration functions.
- Enter key: Confirms selections and accesses programming menus.
- Escape key: Cancels modifications and exits menus.
- LCD screen: Shows real-time readings, including gas type, concentration (% or ppm), and sensor source (built-in or remote).
- Navigation controls: Increment/decrement values and scroll through menus.
LED Indicators
LED | Description | Display Modes |
---|---|---|
1 (I/O Power) | Always on = Normal operation Always off = Microcontroller fault or no power Blinking (twice per second) = Self-test |
|
2 (Standalone: Built-in Sensor / Network: Built-in Sensor) | Standalone: Always on = Alarm A triggered; Slow blink (once per second) = Alarm B/C triggered; Fast blink (4 times per second) = Fault Network: Always on = Alarm A triggered; Slow blink (once per second) = Alarm B/C triggered; Fast blink (4 times per second) = Fault |
Standalone: Alarm A / Alarm B/C / Fault Network: Alarm A / Alarm B/C / Fault |
3 (Standalone: Remote Sensor / Network: Transmit) | Standalone: Always on = Alarm A triggered; Slow blink (once per second) = Alarm B/C triggered; Fast blink (4 times per second) = Fault Network: Always on when transmitting, blinks for communication; Always off = Normal operation |
Standalone: Alarm A / Alarm B/C / Fault Network: Transmitting / Communication / Normal |
Detection Ranges and Alarm Levels
Gas Detected | Range | Alarm A | Alarm B | Alarm C | Maximum Overload* |
---|---|---|---|---|---|
CO Carbon monoxide | 0-250 ppm | 25 ppm | 100 ppm | 225 ppm | 500 ppm |
H₂S Hydrogen sulfide | 0-50 ppm | 10 ppm | 15 ppm | 20 ppm | 150 ppm |
NO₂ Nitrogen dioxide | 0-10 ppm | 0.7 ppm | 2 ppm | 9 ppm | 1000 ppm |
O₂ Oxygen | 0-25%vol | 19.5%vol. | 22%vol. | 22.5%vol | 100%vol |
COMB Combustibles | 0-100%LEL | 25%LEL | 50%LEL | 90%LEL | 100 %LEL |
*Sensor exposure to gas concentration that may result in permanent damage to the sensor.
Limited Warranty
Honeywell Analytics, Inc. warrants its products to the original purchaser for one (1) year against defects in material or workmanship. Defective parts will be repaired or replaced free of charge if shipped prepaid to Honeywell Analytics. The product will be returned freight prepaid if the defect is due to faulty materials or workmanship. This warranty is Honeywell Analytics’ sole responsibility.
Re-Stocking Policy
A 15% re-stocking fee applies for returns within 1 month of shipping; 30% within 3 months. Full credit is issued for products in perfect working condition, less the re-stocking fee. Repair costs will be deducted if needed. No credit beyond three months.
Exclusions
Gas sensors have a twelve (12) month manufacturer's limited warranty. This warranty may be voided by excessive gas concentration exposure, misuse, negligence, or failure to operate according to instructions. Consumable items like batteries, lamps, fuses, valves, vanes, sensor elements, cartridges, or filter elements are not covered.
Warranty Limitation and Exclusion
Honeywell Analytics’ obligations are void if the product has been subject to abuse, misuse, negligence, or accident, or if the purchaser fails to follow instructions, or if the serial number is removed or altered.
Disclaimer of Unstated Warranties
The printed warranty is the only one applicable. All other warranties, express or implied (including merchantability or fitness for a particular purpose), are disclaimed.
Limitation of Liability
Honeywell Analytics’ liability shall not exceed the purchase price of the product. Honeywell Analytics is not liable for special, indirect, or consequential damages. No action may be brought more than one year after the cause of action has occurred.
Risk of electric shock
Part No. 1998-0767 Revision 4, March 2014
Models: E3SAH, E3point, Gas MonitorFile Info : application/pdf, 2 Pages, 867.01KB
DocumentDocumentRelated Documents
![]() |
Honeywell MultiRAE Portable Gas Detector - Technical Specifications and Features Detailed specifications and features of the Honeywell MultiRAE, a wireless, portable six-gas detector with advanced VOC detection capabilities. Covers applications, technical data, sensors, and safety certifications. |
![]() |
Honeywell Analytics 2015 Product Guide: Commercial Gas Detection Systems Comprehensive guide to Honeywell Analytics' 2015 commercial gas detection products, including E3Point, 301C, IAQPoint2, 301EM-20/301IRFS, SCBA, SQN8x, AirScan IR-F9, Sensepoint XCD series, ToxyPoint, and Midas gas detectors. Features product specifications, applications, and contact information. |
![]() |
Honeywell XNX Universal Transmitter Technical Manual This technical manual provides comprehensive information for the Honeywell XNX Universal Transmitter, a versatile gas detection system. It covers installation, operation, maintenance, and calibration procedures for detecting toxic, flammable, and oxygen depletion gas hazards using catalytic bead, electrochemical (EC), and infrared (IR) sensor technologies. The manual details communication options including HART, Modbus, and Foundation Fieldbus protocols. |
![]() |
Honeywell E3Point Network Gas Monitor User Manual Comprehensive user manual for the Honeywell E3Point Network Gas Monitor. Learn about installation, operation, specifications, troubleshooting, and maintenance for this advanced gas detection system. |
![]() |
Honeywell E³Point Toxic and Combustible Gas Monitor | Features & Applications Discover the Honeywell E³Point, an advanced toxic and combustible gas monitor designed for intelligent building operations. Learn about its flexible operation, cost-effectiveness, advanced sensing technology, and diverse applications for enhanced safety and productivity. |
![]() |
Honeywell BW RigRat Quick Start Guide Quick start guide for the Honeywell BW RigRat gas detector, covering user interface, charging, operation, bump testing, calibration, and app integration. |
![]() |
Honeywell MultiRAE Portable Gas Monitor: Advanced Six-Gas Detection Discover the Honeywell MultiRAE, an advanced portable gas detector with six-gas capability and advanced VOC detection. Learn about its features, applications in industrial hygiene, personal protection, and hazardous material response, and technical specifications. |
![]() |
Honeywell BW Ultra Gas Detector: Quick Reference Guide & Safety Get essential information on the Honeywell BW Ultra portable gas detector. This quick reference guide covers setup, safety precautions, operation, and alarms for reliable gas detection. |