Goodman GPG 16 SEER "M" SERIES Single Package Gas-Electric Heating & Cooling Units

INSTALLATION INSTRUCTIONS

Affix this manual and Users Information Manual adjacent to the unit.

WARNING

ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR (HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT. IMPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

ATTENTION INSTALLING PERSONNEL

Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use.

⚠️ RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.

General Installation Overview

These installation instructions cover the outdoor installation of self-contained package air conditioner and heating units. See the Specification Sheets applicable to your model for information regarding accessories.

*NOTE: Please contact your distributor or our website for the applicable Specifications Sheets referred to in this manual.

This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below: ANSI Z21.47•CSA-2.3 Central Furnaces

IMPORTANT - This product has been designed and manufactured to meet ENERGY STAR® criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer's refrigerant charging and air flow instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.

IOG-3012C 02/2018

Goodman Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com ©2015-2018 Goodman Company, L.P.

Safety Instructions

TO THE INSTALLER

Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.

TO THE OWNER

A warranty certificate is provided with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it when necessary. Keep this literature in a safe place for future reference.

⚠️ WARNING

IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.

  • DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
  • WHAT TO DO IF YOU SMELL GAS:
    • DO NOT TRY TO LIGHT ANY APPLIANCE.
    • DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING.
    • IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR'S PHONE. FOLLOW THE GAS SUPPLIER'S INSTRUCTIONS.
    • IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
  • INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.

⚠️ WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE UNIT BEFORE TURNING OFF THE ELECTRICAL SUPPLY.

⚠️ WARNING

HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE, ROUTINE, INSPECTION, MAINTENANCE AND SUPERVISION. IF THE BUILDING IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VACANT, CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUTINELY INSPECTED, MAINTAINED AND MONITORED. IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT, ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE BUILDING SHOULD BE PROPERLY WINTERIZED, AND THE WATER SOURCE CLOSED. IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT, ANY HYDRONIC COIL UNITS SHOULD BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED.

⚠️ WARNING

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE THIS UNIT IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE UNIT AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN UNDER WATER.

⚠️ WARNING

THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES.

⚠️ HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

⚠️ WARNING

DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.

⚠️ WARNING

TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.

⚠️ WARNING

THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.

DANGER - CARBON MONOXIDE POISONING HAZARD

Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas.

Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.

This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.

CO can cause serious illness including permanent brain damage or death.

(Note: This warning is also provided in Spanish and French.)

UNIT LOCATION

IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit.

ALL INSTALLATIONS:

  • For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be mounted level.
  • The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
  • To avoid possible corrosion of the heat exchanger, do not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds.
  • To avoid possible illness or death of the building occupants, do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
  • Allow minimum clearances from the enclosure for fire protection, proper operation, and service access (see appendix). These clearances must be permanently maintained.
  • The combustion air inlet and flue outlet hoods on the unit must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems.
  • When the unit is heating, the temperature of the return air entering the unit must be between 50° F and 100° F.
  • Units manufactured on or after May 1, 2017 are not permitted to be used in Canada for heating of buildings or structures under construction.

GROUND LEVEL INSTALLATIONS ONLY:

  • When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3" larger than the package unit footprint and a minimum of 3" thick.
  • The base should also be located where no runoff of water from higher ground can collect in the unit.

Diagram Description: An illustration shows a typical outdoor slab installation for the unit, indicating the unit placed on a concrete base.

ROOFTOP INSTALLATIONS ONLY:

NOTE: To ensure proper condensate drainage, unit must be installed in a level position.

  • To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
  • The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material.
  • To avoid possible personal injury, a safe, flat surface for service personnel should be provided.

Diagram Description: An illustration depicts the unit installed on a rooftop.

ROOF CURB INSTALLATIONS ONLY:

  • Sufficient structural support must be determined prior to locating and mounting the curb and package unit.
  • Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit.
  • Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor.

GENERAL INFORMATION

This unit is approved for outdoor installation ONLY. Rated performance is achieved after 72 hours of operation. Rated performance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.goodmanmfg.com for Goodman® brand products. Within the website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model's specification sheet.

To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.

The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J Load Calculations published by the Air Conditioning Contractors of America.

Obtain from:

American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036

TRANSPORTATION DAMAGE

Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately. Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should:

  1. Make notation on delivery receipt of any visible damage to shipment or container.
  2. Notify carrier promptly and request an inspection.
  3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
  4. File the claim with the following supporting documents:
    • Original Bill of Lading, certified copy, or indemnity bond.
    • Original paid freight bill or indemnity in lieu thereof.
    • Original invoice or certified copy thereof, showing trade and other discounts or reductions.
    • Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.

NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.

RIGGING DETAILS

IMPORTANT NOTE: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.

Diagram Description: An illustration shows a unit being rigged, highlighting the center of gravity and suggesting cable sling usage.

GAS PIPING

IMPORTANT NOTE: This unit is factory set to operate on natural gas at the altitudes shown on the rating plate.

⚠️ WARNING

TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL THE PROPER CONVERSION KIT(S). FAILURE TO DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. HIGH ALTITUDE KITS ARE FOR THE U.S. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA.

The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of a factory authorized conversion kit. Contact your distributor or refer to the specification sheet for your model for a listing of approved LP gas conversion kit(s). Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas.

The minimum supply pressure should not vary from that shown in the Inlet Gas Pressure table because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.

INLET GAS PRESSURE

Min. 5.0" W.C., Max. 10.0" W.C.
Natural
PropaneMin. 11.0" W.C., Max. 13.0" W.C.

Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.

HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)

IMPORTANT NOTE: The gas/electric units naturally derate with altitude. Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate. Contact your distributor or refer to the specification sheet for your model for listing of approved high altitude conversion kit(s). Refer to the Installation Manual provided with the high altitude kit for altitude adjustments.

NOTE: No changes are required up to 2,000 feet. Use the appropriate high altitude kit above 2,000 feet.

PIPING

IMPORTANT NOTE: To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not undersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously.

Natural Gas Capacity of Pipe in Cubic Feet of Gas Per Hour (CFH)
Length of Pipe in FeetNominal Black Pipe Size (inches)
1/23/411 1/41 1/2
1013227852010501600
20921903507301100
3073152285590980
4063130245500760
5056115215440670
6050105195400610
704696180370560
804390170350530
904084160320490
1003879150305460

CFH = Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based on 0.60 Specific Gravity Gas)
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)

Diagram Description: A diagram labeled "Proper Piping Practice" illustrates the general layout for gas piping to the unit, showing a drip leg, manual shut-off valve, and ground joint union.

CAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING:

  • THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGER FAILURE.
  • THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).
  • THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).

GAS PIPING CHECKS

There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.

⚠️ WARNING

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.

PROPANE GAS INSTALLATIONS

⚠️ WARNING

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE. SINCE RUST CAN REDUCE THE LEVEL OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK. CONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A GAS DETECTING WARNING DEVICE.

IMPORTANT NOTE: Propane gas conversion kits must be installed to convert units to propane gas. Contact the distributor or refer to the specification sheet for your model for the correct LP conversion kit(s).

TANKS AND PIPING

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).

For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

  1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers.
  2. Proper pressure regulation.
  3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.

Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers.

Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde's® or John Crane® are satisfactory.

See Typical Propane Gas Piping figure for typical piping arrangement.

Diagram Description: A diagram illustrates a typical propane gas piping setup, showing a first stage regulator, a second stage regulator, and the connection to the unit.

Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING LENGTH, FEETTUBING SIZE, O.D., TYPE LNOMINAL PIPE SIZE, SCHEDULE 40
3/8"1/2"5/8"3/4"7/8"1/2"3/4"1"
103097001,3032,2053,3941,8433,8547,200
202655991,1151,8872,9041,5773,2986,200
302355319881,6722,5741,3982,9235,500
402134818961,5152,3321,2672,6495,000
501964468241,3942,1461,1652,4374,600
601824127671,2971,9961,0842,2674,300
701713867191,2171,8731,0172,1274,000
801613656791,1491,7699612,0093,800
901302935469231,4217721,6132,900
1001112514677901,2166601,3812,500
150902224147001,0785851,2242,100
200892013786349765301,1091,900
250821853455848984881,0201,700
300761723215438364549491,500
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at 11" W.C. Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING LENGTH, FEETTUBING SIZE, O.D., TYPE LNOMINAL PIPE SIZE, SCHEDULE 40
3/8"1/2"5/8"3/4"7/8"1/2"3/4"1"1-1/4"1-1/2"
10491102063485392916081,1462,3533,525
2034761412393682004187881,6172,423
3027611141922961613366321,2991,946
402352971642531372845411,1111,665
502046861462241222554809851,476
601942781322031102314368921,337
80163667113174941983727641,144
100143259100154841753306771,014
1251228528913774155292600899
1501126488012467141265544815
2001022416910658120227465697
25091936619451107201412618
3008183355854697182374560
3507163051784389167344515
4007152847734083156320479

*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54

Diagram Description: A diagram illustrates typical propane gas piping, showing regulators and pipe sizing charts for different lengths and tubing/pipe sizes.

ELECTRICAL WIRING

THERMOSTAT LOCATION

Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation. Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions.

All units have two stages of heating and two stages of mechanical cooling. Units which will have economizers may use thermostats with two or three stages of cooling. All units can use single stage or multi-stage thermostats. Refer to figures later in this section for wiring.

The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. The low voltage wiring must be connected between the unit control panel and the room thermostat.

⚠️ WARNING

TO AVOID PERSONAL INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING.

Diagram Description: A wiring diagram shows a thermostat connected to an integrated control module for two-stage heating and two-stage cooling.

SINGLE STAGE THERMOSTAT

To use a single stage thermostat, move jumper located to the left of the terminal strip labeled "Stage Delay” from NONE to “5” or “10” minutes. This selection will cause the control to run on low stage for the selected time (5 or 10 minutes) then shift to HIGH STAGE. This option controls both cooling and heating modes. If the jumper is not moved, only low-stage cool and low-stage heat will operate.

Diagram Description: A wiring diagram illustrates how to connect a single-stage thermostat for timed delay heating and cooling, showing jumper positions for 5 or 10-minute delays.

Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof.

⚠️ WARNING

TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE POLARIZED AND GROUNDED.

CAUTION

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUCTORS.

⚠️ WARNING

TO PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. VERIFY PROPER OPERATION AFTER SERVICING.

For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.

Diagram Description: Two diagrams show typical electrical power entry points to the unit: directly to a junction box, and through the bottom of the unit.

UNIT VOLTAGE

The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram. The induced draft blower on some models is equipped with a low speed 230V lead (blue) and a low speed 208V lead (black). If equipped, connect the induced draft blower low speed 208V lead (black) in place of the low speed 230V lead (blue). Place the unused 230V lead on the "PARK" terminal located on ignition control.

HEAT ANTICIPATOR SETTING

The heat anticipator is to be set by measuring the load (amperage) at the “R” circuit. Follow the instructions provided with the thermostat for more details.

CIRCULATING AIR AND FILTERS

AIRFLOW CONVERSION

Units can easily be converted from horizontal to down-discharge airflow delivery. In down-discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow.

Horizontal Air Flow

Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman's Service Parts department.

Down Discharge Applications

Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.

NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis).

Diagram Description: An illustration shows the unit with panels removed to access the bottom for downflow duct applications. Arrows indicate supply and return air paths.

DUCTWORK

Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.

A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.

The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.

For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix.

For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual.

If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.

FILTERS

Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. All units may be externally filtered.

CAUTION

TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD-UP ON INTERNAL PARTS, NEVER OPERATE THE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.

Refer to the unit filter size chart in the appendix for filter size information. Filters installed external to the unit should be sized in accordance with their manufacturer recommendations. A throwaway filter must be sized for a maximum face velocity of 300 feet per minute.

Filter Installation

IMPORTANT NOTE: When installing a filter, the air flow arrows on the filter must point toward the circulator blower.

VENTING

NOTE: Venting is self-contained. Do not modify or block.

INSTALLATION - FLUE HOOD EXHAUST

  1. Locate the flue hood assembly box in the unit.
  2. Slide screen over flanges on the lower flue hood.
  3. Slide screen and lower flue hood into hood.
  4. Using the three screws provided, attach the hood (with the opening facing down) over the flue exhaust opening in the utility panel.

Diagram Description: An illustration shows the components of the flue hood exhaust assembly: HOOD, SCREEN, LOWER FLUE HOOD, and LIP.

INSTALLATION - COMBUSTION AIR INTAKE HOOD

  1. Locate the second hood.
  2. Using the three screws provided, attach the hood (with the opening facing down) to the heat exchanger access door.

CONDENSATE DRAIN

CONDENSATE DRAIN CONNECTION

A 3/4" NPT drain connection is supplied for condensate piping. An external trap must be installed for proper condensate drainage.

Diagram Description: A diagram illustrates the condensate drain connection, showing the unit's drain connection, a flexible tubing-hose or pipe, a 2" minimum vertical drop, a 3" minimum horizontal run, and a required positive liquid seal.

NORMAL SEQUENCES OF OPERATION

HEATING

This unit is equipped with an ignition control that automatically lights the main burner. DO NOT attempt to light the main burners by any other method.

  1. Thermostat calls for low or high stage heating.
  2. Induced draft blower energizes for 15-second pre-purge.
  3. The spark igniter and low and high stage gas valve are energized for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas.
  4. Main burners light and control detects presence of flame.
  5. If the call is for low stage heat, the induced draft blower switches to low speed and the high stage gas valve closes 5 seconds after the main burners light. If call is for high stage heat, induced draft blower remains at high speed and high stage gas valve remains open.
  6. NOTE: If a single stage thermostat is used, the control will step to low stage after the main burners light and remain at low stage for 5 or 10 minutes, depending on jumper position. If the call for HEAT remains after the transition delay time expires, the control will transition from low stage to high stage.
  7. The 30-second HEAT FAN ON delay time begins after the main burners light.
  8. The unit delivers heat to the conditioned space until the thermostat is satisfied.
  9. Gas valve(s) de-energizes. The induced draft blower continues operation for a 30-second post-purge.
  10. Induced draft blower remains at low speed (or switches from high to low if operating at high stage heat) for the 30-second post purge.
  11. Ignition control begins timing the HEAT FAN OFF delay. There is an adjustable HEAT FAN OFF delay of approximately 90/120/150/180 seconds (factory set at 150). If the unit is operating at high stage when the call for heat is removed, the blower will operate for 30 seconds at high heat speed then switch to low heat speed for the remainder of the selected HEAT FAN OFF delay.
  12. NOTE: After the HEAT FAN OFF delay time has elapsed, the blower will de-energize. This allows any additional heat in the heat exchanger to be transferred to the conditioned space.

COOLING

  1. Thermostat calls for low or high stage cooling.
  2. If the thermostat call is for low stage cooling, the compressor and outdoor fan are energized at low stage. If the thermostat call is for high stage cooling, the compressor and outdoor fan are energized at high stage.
  3. The indoor blower will energize approximately 6 seconds later.
  4. The unit delivers cooling to the conditioned space until the thermostat is satisfied.
  5. The compressor and outdoor fan will be de-energized when the thermostat opens.
  6. The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor blower is de-energized.
  7. NOTE: A 180-second anti-short cycle is integral to the control and prevents recycling of the compressor.

FAN ONLY

  1. Thermostat calls for FAN ONLY by energizing "G".
  2. The indoor blower is immediately energized at the low heat speed.
  3. The indoor blower is immediately de-energized once thermostat call for FAN is removed.

STARTUP, ADJUSTMENTS, AND CHECKS

HEATING STARTUP

This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower to exhaust combustion products.

On new installations, or if a major component has been replaced, the operation of the unit must be checked. Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and check for wiring errors, or obstructions in or near the blower motors. Duct covers must be removed before operating unit.

Heat Anticipator Setting

Set the heat anticipator on the room thermostat to 0.4 amps to obtain the proper number of heating cycles per hour and to prevent the room temperature from overshooting the room thermostat setting.

Rollout Protection Control

The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control must be determined and repaired prior to resetting this manual reset control.

⚠️ WARNING

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING THE ROLLOUT PROTECTION DEVICE.

Diagram Description: An illustration shows the location of the Rollout Protection device on the burner bracket.

Secondary Limit Control

The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting.

If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset.

Diagram Description: An illustration shows the location of the Secondary Limit Control on the blower scroll assembly, viewed from the back of the unit.

Pre-Operation Checks

  1. Close the manual gas valve external to the unit.
  2. Turn off the electrical power supply to the unit.
  3. Set the room thermostat to its lowest possible setting.
  4. Remove the heat exchanger door on the side of the unit by removing screws.
  5. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method.
  6. Move the gas control valve switch to the OFF position. Do not force.
  7. Wait five minutes to clear out any gas.
  8. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 3 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position.
  9. Replace the heat exchanger door on the side of the unit.
  10. Open the manual gas valve external to the unit.

Gas Supply And Manifold Check

Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed.

With Power And Gas Off:

  1. Back inlet pressure test screw (inlet pressure boss) out one turn (counterclockwise, not more than one turn). Alternately, inlet gas pressure may be measured by removing the cap from the drip leg and installing a predrilled cap with a hose barb fitting.
  2. Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve (or hose barb fitting on predrilled cap).

With Power And Gas On:

  1. Put unit into heating cycle and turn on all other gas consuming appliances.
INLET GAS PRESSURE
Min. 5.0" W.C., Max. 10.0" W.C.
Natural
PropaneMin. 11.0" W.C., Max. 13.0" W.C.

NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown. If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/or consult with local utility.

  1. Turn off all electrical power and gas supply to the system.
  2. Remove manometer hose from the outlet pressure boss (or remove hose from hose barb).
  3. Turn inlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum). Alternately, remove predrilled cap from drip leg. Reinstall original cap, sealing with pipe thread compound.
  4. Turn on electrical power and gas supply to the system.
  5. Turn on system power and energize valve.
  6. Using a leak detection solution or soap suds, check for leaks at the pressure boss screw (or drip leg cap). Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.

Manifold Pressure Check

  1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
  2. Turn off all electrical power to the system.
  3. Back outlet pressure test screw (outlet pressure boss) out one turn (counterclockwise, not more than one turn).
  4. Attach a hose and manometer to the outlet pressure boss of the valve.
  5. Turn ON the gas supply.
  6. Turn on power and energize main (M) solenoid. Do not energize the HI solenoid.
  7. Measure gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table.
  8. Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure, or counterclockwise to decrease pressure.
  9. Energize main (M) solenoid as well as the HI terminal.
  10. Remove regulator cover screw from the HI outlet pressure regulator adjust tower and turn screw clockwise to increase pressure, or counterclockwise to decrease pressure.
  11. Turn off all electrical power and gas supply to the system.
  12. Remove manometer hose from outlet pressure boss.
  13. Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).
  14. Turn on electrical power and gas supply to the system.
  15. Turn on system power and energize valve.
  16. Using a leak detection solution or soap suds, check for leaks at pressure boss screw. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.
Manifold Gas Pressure
GasRangeNominal
Low Stage1.7 - 2.3" w.c.2.0" w.c.
NaturalHigh Stage3.2 - 3.8" w.c.3.5" w.c.
Low Stage5.7 - 6.3" w.c.6.0" w.c.
PropaneHigh Stage9.7 - 10.3" w.c.10.0" w.c.

Diagram Description: A diagram shows the setup for measuring inlet gas pressure using a manometer, including the gas line, shutoff valve, drip leg, and manometer hose connection to the gas valve. Another diagram shows a White-Rodgers Model 36G54 gas control valve connected to a manometer.

NOTE: For Natural gas to LP gas conversion, consult your dealer for appropriate conversion kit(s).

Gas Input (Natural Gas Only) Check

To measure the gas input use a gas meter and proceed as follows:

  1. Turn off gas supply to all other appliances except the unit.
  2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit.
  3. INPUT = GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
  4. Example: Natural gas with a heating value of 1000 BTU per cubic foot and 36 seconds per cubic foot as determined by Step 2, then: Input = 1000 x 3600 / 36 = 100,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.
  5. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating.

Main Burner Flame Check

Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off.

Temperature Rise Check

Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained.

  1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking readings.
  2. The temperature rise must be within the range specified on the rating plate.

NOTE: Air temperature rise is the temperature difference between supply and return air.

With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed. If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise.

NOTE: Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the rating plate.

⚠️ WARNING

TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE BLOWER MOTOR.

External Static Pressure Check

The total external static pressure must be checked on this unit to determine if the airflow is proper.

Blower Speed Adjustments

Blower speeds are changed at the indoor blower. The ignition control board has four blower speeds: LOW HEAT, HI HEAT, LOW COOL and HIGH COOL.

NOTE: FAN ONLY energizes at LOW HEAT speed. The GPG16 models are equipped with EEM motors. EEM motors are constant torque motors with very low power consumption. This motor is energized by 24VAC. Adjust the CFM for the unit by changing the 24 VAC leads to the speed terminal block on the motor.

HEATING
Speed TapDefinitionLead Color
T1Low Speed HeatWhite
T2High Speed HeatBrown
COOLING
Speed TapDefinitionLead Color
T3Low Speed CoolPurple
T4High Speed CoolYellow
T5High Speed Cool Hi-Static

Limit Check

Check limit control operation after 15 minutes of operation by blocking the return air grille(s).

  1. After several minutes the main burners must go OFF. Blower will continue to run.
  2. Remove air restrictions and main burners will relight after a cool down period of a few minutes.

Adjust the thermostat setting below room temperature.

  1. Main burners must go OFF.
  2. Circulating Air Blower will continue to run for 90, 120, 150 or 180 seconds, depending on the setting.

NOTE: If necessary, adjust fan OFF delay settings to obtain satisfactory comfort level.

Diagram Description: A diagram shows the top view of the Control Board, illustrating terminals for blower speed, stage control, and thermostat connections (ECON, R, C, W1/W2, G, Y1, Y2).

Unit Shutdown

  1. Set the thermostat to lowest setting.
  2. Turn off the electrical power supply to the unit.
  3. Remove the heat exchanger door on the side of the unit by removing screws.
  4. Move the gas control valve switch to the OFF position. Do not force.
  5. Close manual gas shutoff valve external to the unit.
  6. Replace the heat exchanger door on the unit.
  7. If cooling and/or air circulation will be desired, turn ON the electrical power.

COOLING STARTUP

NOTE: Check all manual reset limit controls in heating circuit if cooling mode does not operate.

Compressor Protection Devices

The compressor includes components which are designed to protect the compressor against abnormal operating conditions.

⚠️ WARNING

THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES.

⚠️ WARNING

TO PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL POWER BEFORE INSPECTING OR SERVICING THE UNIT. NOTE: ALL COMPRESSOR PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR AND OUTDOOR FAN.

Cooling Refrigerant Charging (Models with TXV)

Check unit charge before putting the cooling section into full operation. The unit has a thermostatic expansion valve metering device. To ensure the unit is properly charged for the intended application, check the unit refrigerant sub-cooling at the condenser. The refrigerant sub-cooling is a function of outdoor ambient temperature and return air temperature of the conditioned space. It is the installing contractor's responsibility to ensure the proper refrigerant sub-cooling at the condenser is adjusted for each application. As the outdoor ambient temperature rises the sub-cooling decreases and as the outdoor ambient temperature lowers, the sub-cooling increases. NOTE: Proper sub-cooling adjustment optimizes cooling performance. Models equipped with thermostatic expansion valve, charge the system to sub-cooling, range shown on chart, when necessary, adjust expansion valve stem for superheat setting.

NOTE: The expansion valve will not need adjustment for most applications. Ensure system superheat is set within range listed on chart.

Design superheat & subcooling @ 95 °F outdoor ambient temperature
Models #Superheat °FSubcooling °F
GPG1624060M419 - 139 - 13
GPG1630080M418 - 1210 - 14
GPG1636080M4110 - 148 - 12
GPG1642100M4110 - 146 - 10
GPG1648100M418 - 128 - 12

Superheat Adjustment

To adjust superheat, remove the control box cover and locate the expansion valve on the liquid line of the evaporator. Unscrew the cover from the expansion valve, locate the adjustment screw, and turn it clockwise (in) to increase superheat or counterclockwise (out) to decrease superheat. Replace adjustment cap. Wait a minimum of 10 minutes between adjustments to allow time for the TXV and pressures to stabilize.

Cooling Operation

NOTE: Mechanical cooling cannot be reliably provided at ambient temperatures below 50° F.

  1. Turn on the electrical power supply to the unit.
  2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired).
  3. Set the room thermostat to the desired temperature.

TROUBLESHOOTING

IGNITION CONTROL ERROR CODES

The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.

Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.

FAULT RECALL

The ignition control is equipped with a momentary push-button switch that can be used to display on the diagnostic LED the last five faults detected by the control. The control must be in Standby Mode (no thermostat inputs) to use the feature. Depress the push-button switch for approximately 2 seconds. NOTE: Do not hold for longer than 4 seconds. Holding the button for 4 seconds or higher will erase the memory! Release the switch when the LED is turned off. The diagnostic LED will then display the flash codes associated with the last five detected faults. The order of display is the most recent fault to the least recent fault.

ABNORMAL OPERATION - HEATING

INTERNAL CONTROL FAILURE

If the integrated ignition control in this unit encounters an internal fault, it will go into a "hard" lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control.

EXTERNAL LOCKOUT

An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is de-energized, 30 second inter-purge cycle is completed, and ignition is re-attempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state.

If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle the ignition sequence.

The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic red LED indicates an external lockout, perform the following checks:

  • Check the supply and manifold pressures
  • Check the gas orifices for debris
  • Check gas valve for proper operation
  • Check flame sensor

A drop in flame signal can be caused by nearly invisible coating on the sensor. Remove the sensor and carefully clean with steel wool.

  • Auxiliary/Secondary Limit A dirty filter, excessive duct static, insufficient air flow, a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly.
  • Rollout Limit If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit.
  • Check wiring Check wiring for opens/shorts and miswiring.

IMPORTANT NOTE: If you have to frequently reset your gas/electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information.

PRESSURE SWITCH STUCK OPEN

A pressure switch stuck open can be caused by a faulty pressure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, a blocked pressure tap or a faulty induced draft blower.

If the control senses an open pressure switch during the pre-purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is de-energized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic LED (red) code is two (2) flashes.

PRESSURE SWITCH STUCK CLOSED

A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower remains off. The diagnostic red LED code for this fault is three (3) flashes.

PRIMARY LIMIT

A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.

If a limit switch opens, the gas valve is immediately de-energized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch re-closes. The diagnostic LED (red) code for an open limit is four (4) flashes.

NOTE: If the primary limit opens five (5) times within the same call for heat, the ignition control will lock out for one (1) hour with the air circulating blower energized at high heat speed. The diagnostic LED (red) code for this condition is seven (7) flashes.

FLAME DETECTED WITH GAS VALVE CLOSED

If flame is detected with the gas valve de-energized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes (red LED) for this condition. The flame diagnostic LED (amber) will flash (2) times to indicate this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault.

LOW FLAME SIGNAL

Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame signal. If the flame signal drops below a predetermined value, the ignition control will display an error code of (1) flash on the amber diagnostic LED. The unit will continue to operate until the control can no longer detect flame.

ABNORMAL OPERATION - COOLING

SHORT CYCLE COMPRESSOR DELAY

The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored or thermostat call for cooling is restored. (Compressor is off a total of three minutes). The diagnostic red LED will flash six (6) times to indicate the compressor contactor output is being delayed.

NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time.

HIGH PRESSURE SWITCH/LOSS OF CHARGE SWITCH

Some models include a high pressure cutout switch and/or a loss of charge cutout switch. The high pressure cutout switch protects the refrigeration system from excessive operating pressures. The loss of charge cutout switch protects the refrigeration system from very low operating pressures due to a loss of refrigerant. Compressor operation will be disabled if either of these devices opens. If either devices opens, the diagnostic red LED will flash (9) times to indicate that a refrigeration system pressure switch is open.

MAINTENANCE

Have the gas heating section of the unit checked at least once a year before the heating season begins, to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a properly operating vent system.

FILTER REPLACEMENT OR CLEANING

A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), or return air filter grille(s). Consult with your installing dealer for the actual location of the return air filter(s) for your unit.

Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage.

Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent filters should last several years. However, should one become torn or uncleanable, it should be replaced.

CABINET FINISH MAINTENANCE

Use a fine grade automotive wax on the cabinet finish to maintain the finish's original high luster. This is especially important in installations with extended periods of direct sunlight.

CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)

The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris.

CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS

Bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated. No additional oiling is required.

FLAME SENSOR (QUALIFIED SERVICER ONLY)

A drop in the flame current can be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool.

NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC.

Diagram Description: An illustration shows the Flame Sensor and its location.

FLUE PASSAGES (QUALIFIED SERVICER ONLY)

At the start of each heating season, inspect and, if necessary, clean the unit flue passage.

CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)

  1. Shut off electric power and gas supply to the unit.
  2. Remove burner assembly by disconnecting the gas line and removing the manifold bracket from the partition panel.
  3. Remove the flue from the induced draft blower and the collector box cover from the partition panel.
  4. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube.
  5. When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed.
  6. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in "Startup, Adjustments, and Checks".

MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)

Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off.

At least once a year, prior to or during the heating season, make a visual check of the burner flames.

NOTE: This will involve removing and reinstalling the heat exchanger door on the unit, which is held by two screws. If you are uncertain about your ability to do this, contact a qualified servicer. If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not possible.

CLEANING BURNERS

  1. Shut off electric power and gas supply to the unit.
  2. Remove the screws securing the manifold to the burner retention bracket. Remove the manifold and rotate each burner counterclockwise to remove.
  3. Remove the burners.
  4. Use a bottle brush to clean burner insert and inside of the burners.
  5. Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots.
  6. Reconnect electrical power and gas supply.

For further information on the yearly inspection, consult the User Manual. It is recommended that a qualified servicer inspect and service the unit at least once each year.

Turn the unit on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.

Diagram Description: An illustration shows a "Burner Flame" with indicators for good adjustment, stable/soft/blue flame, and not curling/floating/lifting off. It also shows a "Manifold Assembly" with the burner and burner bracket.

ACCESSORIES AND FUNCTIONAL PARTS

SHEET METAL ACCESSORIES

Additional accessories can be purchased to fit specific application needs. Parts and instructions are available from your distributor.

FUNCTIONAL PARTS

FUNCTIONAL PARTSFUNCTIONAL PARTS
Auxiliary Limit SwitchFlame Sensor
Blower HousingGas Orifice
Blower WheelGas Valve
BurnerHeat Exchanger
Circulator Blower MotorHigh Limit Switch
CapacitorHigh Pressure Switch
CompressorIgniter
Condenser CoilIgnition Control
Condenser Fan BladeInduced Draft Blower
Condenser Fan MotorPressure Switch
ContactorPressure Switch Hose
Gas ManifoldThermostatic Expansion Valve
Evaporator CoilTransformer
Flame Rollout Switch

Functional Parts List

GENERAL INFORMATION

  1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the unit model and serial numbers with the order.
  2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description.
  3. Parts are available from your distributor.

APPENDIX

IGNITION CONTROL DIAGNOSTIC INDICATOR CHART

Red Light SignalRefer to Abnormal Heating or Cooling Operation Sections of this Manual
OffInternal Control Failure
1 FlashExternal Lockout
2 FlashesPressure Switch Stuck Open
3 FlashesPressure Switch Stuck Closed
4 FlashesThermal Protection Device Open
5 FlashesFlame Detected with Gas Valve Closed
6 FlashesShort Cycle Compressor Delay (Cooling Only)
7 FlashesLimit Opened Five (5) Times Within The Same Call For Heat
8 FlashesIndoor/Outdoor Thermostat Open (Cooling Only; Devices Not present On All Models)
9 FlashesHigh Pressure/Loss of Charge Switch Open (Cooling Only; Devices Not Present On All Models)
Amber Light SignalRefer to Abnormal Heating or Cooling Operation Sections of this Manual
OffNo Flame Present
OnNormal Flame
1 FlashLow Flame Current
2 FlashesFlame Detected with Gas Valve De-energized.

HEATING TIMING CHART

Diagram Description: A timing chart illustrates the sequence of operation for heating, showing the timing of the Circulator Blower, Gas Valve, Igniter, Induced Draft Blower, and Thermostat over seconds (0 to 180).

COOLING TIMING CHART

Diagram Description: A timing chart illustrates the sequence of operation for cooling, showing the timing of the Circulator Blower, Compressor, Outdoor Fan, and Thermostat over seconds (0 to 60).

UNIT DIMENSIONS

Diagram Description: A detailed 3D diagram shows the unit's dimensions, including overall length, width, and height, as well as specific measurements for ports, entrances, and access panels. A table provides dimensions (A, B, C) for Medium and Large unit sizes.

DIMENSION (INCHES)
MEDIUMLARGE
A3240
B1618
C9 1/214

WIRING DIAGRAM

Diagram Description: A comprehensive wiring diagram for the GPG16*****M41A** model, showing high voltage and low voltage connections to various components like the compressor, motors, gas valve, and ignition control. It includes a component legend, wire code, notes for wiring, and a diagnostic LED status chart for red and amber lights, detailing error codes and their probable causes.

MINIMUM CLEARANCES

Diagram Description: A diagram illustrates the minimum required clearances around the unit for installation and service, showing distances such as 48" MIN, 12" MIN, 3" MIN, and 36" MIN for service. A note indicates roof overhang should be no more than 36".

RECOMMENDED FILTER SIZES

UNIT2 Ton2 1/2 Ton3 Ton3 1/2 Ton4 Ton
Min. Filter Size(1) 20 x 25 x1(1) 25 x 25 x 1(1) 25 x 25 x 1(2) 20 x 20 x 1(2) 20 x 20 x 1

BLOWER PERFORMANCE DATA

Diagram Description: A series of tables provide Blower Performance Data for different models (GPG1624060M41, GPG1630080M41, GPG1636080M41, GPG1642100M41, GPG1648100M41). Each table shows performance metrics like CFM, Watts, and Rise for various External Static Pressure (E.S.P.) values across different speed taps (T1-T5) for heating and cooling stages. A note indicates that shaded areas represent ranges exceeding the maximum allowable external static pressure for heating, and that satisfactory operation requires external static pressure not to exceed 0.8" w.c.

HOMEOWNER'S ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin.

REPLACE OR CLEAN FILTER

IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire.

A return air filter is not supplied with this unit; however, there must be a means of filtering the return air. An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort system clean. A dirty coil could cause poor operation and/or severe equipment damage.

The installer of your unit can tell you where your filter(s) are and how to clean or replace them. Check your return filter(s) at least once every two months. When they are dirty, replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned.

NOTE: Reusable type filters should be washed with warm water, dried completely and sprayed with an adhesive according to the manufacturer's recommendations.

You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic types. These filters can do a better job of catching small airborne particles.

Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as required. When replacing a filter, it must be replaced with a filter of the same type and size and always make certain the air flow arrows on the filter point in the proper direction.

CONDENSER, EVAPORATOR AND INDUCED DRAFT MOTORS

The bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated and require no further lubrication.

COMPRESSOR

The compressor motor is hermetically sealed and does not require additional oiling.

ALUMINUM INDOOR COIL CLEANING (QUALIFIED SERVICER ONLY)

This unit is equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils. An alternate cleaning method is to use one of the products listed in the technical publication TP-109 (shipped in the literature bag with the unit) to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is available on the web site in Partner Link > Service Toolkit.

NOTE: Ensure coils are rinsed well after use of any chemical cleaners.

ANNUAL INSPECTION (QUALIFIED SERVICER ONLY)

Your package unit should be inspected by a qualified installer, or service agency at least twice every year. This check should be performed before the heating and cooling seasons begin. This will ensure that adequate combustion air is being drawn and the vent system is working properly. Particular attention should be paid to the following items. Repair as necessary.

  • Check physical support of the unit. Ensure it is sound without any sagging, cracks, or gaps, around the base.
  • Check for obvious signs of deterioration of the unit.
  • Flue Hood and Combustion Air Inlet. Check for blockage (wasp nest, etc.) and corrosion.

FLUE HOOD (QUALIFIED SERVICER ONLY)

  • Return Air Connection. Check for physical soundness and ensure that the connection is firmly sealed to the package unit casing.
  • Heat exchanger. Check for corrosion and/or obstructions within the heat exchanger passageways.
  • Burners. Check for proper ignition, burner flame, and flame sense.
  • Wiring. Check wires for damage. Check electrical connections for tightness and/or corrosion.
  • Filters. Check that filters are clean and in the proper placement in the unit or duct system.
  • Louvers. Inspect air inlet louvers inside the heat exchanger compartments. Ensure the area is clean and free of dirt and debris.

CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)

The outdoor coil should be inspected annually. It is important to keep the outdoor coil clean. Dirt, leaves, or debris could restrict the airflow. If cleaning of the outdoor coil becomes necessary, hire a qualified servicer. Inexperienced people could easily puncture the tubing in the coil.

BEFORE CALLING YOUR SERVICER

  • Check the thermostat to confirm that it is properly set.
  • Check the disconnect switch near the unit to confirm that it is closed.
  • Check the electrical panel for tripped circuit breakers or failed fuses. Reset the circuit breakers or replace fuses as necessary.
  • Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture).
  • Check for obstructions on the unit. Confirm that it has not been covered on the sides or the top. Remove any obstruction that can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
  • Check the filter. If it is dirty, clean or replace it.

Start-up Checklist

Pre Start-Up (Check each item as completed)

  • Verify all packaging material has been removed.
  • Remove all shipping brackets per installation instructions.
  • Verify the job site voltage agrees with the unit serial plate.
  • Verify condensate connection is installed per installation instructions.
  • Verify proper clearance around the unit for safety, service, maintenance and proper unit operation.
  • Verify proper weatherproofing of all ductwork, roof curbs and electrical connections.
  • Check that the flue screen is in place.
  • Check gas piping for leaks.
  • Verify gas pressure to the unit is within the range specified on the serial plate.
  • Check to ensure that all fans, pulleys and wheels are secure.
  • Check for proper belt tension and alignment per installation instructions.
  • Check refrigerant piping for rubbing and leaks. Repair if necessary.
  • Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges.
  • Check all electrical connections and terminals. Tighten as needed.
  • Verify that the crankcase heaters have been energized for 24 hours.
  • Verify the scroll compressor(s) are rotating in the right direction.
  • Verify all accessories are installed and operating correctly.
  • Check filters and replace if necessary.
  • Verify the installation of the thermostat.

Start-Up (Insert the values as each item is completed.)

ELECTRICAL
L1 - L2L2 - L3L3 - L1
Supply Voltage
Circuit 1 Compressor Amps
Circuit 2 Compressor Amps
Blower Amps
Condenser Fan AmpsFan 1Fan 2Fan 3
BLOWER EXTERNAL STATIC PRESSURE
Return Air Static PressureIN. W.C.
Supply Air Static PressureIN. W.C.
Total External Static PressureIN. W.C.
Blower Wheel RPMRPM
TEMPERATURES
DBWB
Outdoor Air Temperature
Return Air Temperature
Cooling Supply Air Temperature
Heating Supply Air Temperature
PRESSURES
IN. W.C.IN. W.C. (High Fire)
Gas Inlet Pressure
Gas Manifold PressureIN. W.C. (Low Fire)
Suction Circuit 1PSIG°F
Superheat (Orifice System)°F
Suction Circuit 2PSIG°F
Superheat (Orifice System)°F
Discharge Circuit 1PSIG°F
Subcooling (TXV System)°F
Discharge Circuit 2PSIG°F
Subcooling (TXV System)°F
(HEAT PUMP ONLY)
PSIG°F
Suction Circuit 1
Suction Circuit 2
Discharge Circuit 1
Discharge Circuit 2

CUSTOMER FEEDBACK

We are very interested in all product comments. Please fill out the feedback form on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page.

PRODUCT REGISTRATION

Thank you for your recent purchase. Though not required to get the protection of the standard warranty, registering your product is a relatively short process, and entitles you to additional warranty protection, except that failure by California and Quebec residents to register their product does not diminish their warranty rights.

For Product Registration, please register as follows: Goodman® Brand products: (https://www.goodmanmfg.com/product-registration). You can also scan the QR code on the right for the product brand you purchased to be directed to the Product Registration page.

NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE

Quality Makes the Difference!

All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have designed these units to significantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit is run tested before it leaves the factory.

That's why we know... There's No Better Quality.

Goodman Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
©2015-2018 Goodman Company, L.P.

PDF preview unavailable. Download the PDF instead.

IOG-3012C Acrobat Distiller 18.0 (Windows)

Related Documents

Preview Goodman GPG 16 SEER "M" Series Installation Instructions
Comprehensive installation manual for Goodman GPG 16 SEER "M" Series Single Package Gas-Electric Heating & Cooling Units. Covers safety precautions, unit location requirements, installation procedures for various settings (ground level, rooftop, roof curb), gas piping, electrical wiring, airflow, venting, condensate drain, normal operation sequences, startup, adjustments, troubleshooting, and maintenance. It also includes appendices with diagnostic charts, timing charts, unit dimensions, clearances, filter sizes, and blower performance data.
Preview Goodman GPG 16 SEER "M" Series Installation Manual for Single Package Gas-Electric Heating & Cooling Units
Comprehensive installation, operation, maintenance, and troubleshooting guide for Goodman GPG 16 SEER "M" Series single package gas-electric heating and cooling units. Includes safety instructions, wiring diagrams, and performance data.
Preview Goodman GPG 15 SEER "M" Series Installation Instructions
Detailed installation manual for Goodman GPG 15 SEER "M" Series single package gas-electric heating and cooling units. Covers safety, setup, operation, troubleshooting, and maintenance.
Preview Goodman GPG 16 SEER M Series Installation Manual
Comprehensive installation manual for Goodman GPG 16 SEER 'M' Series 2-4 Ton Single Package Gas-Electric Heating & Cooling Units. Covers safety, installation, operation, and maintenance.
Preview Goodman GPG 15 SEER M Series Gas-Electric HVAC Installation Guide
Official installation manual for Goodman GPG 15 SEER M Series Gas-Electric Heating & Cooling Units. Covers unit setup, safety, operation, troubleshooting, and maintenance. Includes model numbers PG15240701A, PG153009041A, and more.
Preview Goodman A/GPG 13.4 SEER2 "M" Series Gas-Electric Heating & Cooling Unit Installation Guide
Comprehensive installation and operating instructions for the Goodman A/GPG 13.4 SEER2 "M" Series Single Package Gas-Electric Heating & Cooling Unit. Covers safety precautions, unit location, installation procedures, gas piping, electrical wiring, startup, and maintenance.
Preview Goodman A/GPUM3 Series Ultra-Low NOx Heating & Cooling Unit Installation Manual
Comprehensive installation, operation, and maintenance manual for the Goodman A/GPUM3 Series Single Package Gas-Electric Ultra-Low NOx Heating & Cooling Unit. Covers safety precautions, installation procedures, startup, adjustments, troubleshooting, and homeowner maintenance recommendations.
Preview Goodman APG/GPG 14 SEER Gas Electric Package Units Service Instructions
Comprehensive service instructions for Goodman and Amana APG/GPG 14 SEER Gas Electric Package Units with R-410A refrigerant. Includes product identification, system operation, accessories, troubleshooting, and maintenance procedures for qualified HVAC technicians.