Danfoss EKE 347 Level Controller User Guide

Brand: Danfoss

Product Type: Industrial Controller

Introduction

The EKE 347 controller is designed for liquid level control in various industrial applications, including pump tanks, separators, intercoolers, economizers, condensers, and receivers. It continuously monitors liquid levels and automatically adjusts valve operations to maintain the desired setpoint.

The EKE 347 receives measured values from a liquid level transmitter. By comparing these values to customer-defined setpoints, it operates valves to control inflow or outflow, thereby maintaining the desired liquid level.

Key Features

  • Liquid Level Control: Precise control of liquid levels.
  • Alarms: Generates alarms when setpoints are exceeded (high or low limits).
  • Relay Outputs: Three configurable relay outputs for high/low limit and alarm signals.
  • Setup Wizard: User-friendly initial setup wizard for easy configuration.
  • Control Modes: Supports PI control, low-side or high-side control.
  • Master/Slave Configuration: Enables master/slave systems to control up to three expansion valves (AKV/A).
  • Manual Control: Allows manual adjustment of output.
  • Angle Limitation: Configurable valve opening angle limits.
  • Hysteresis: Adjustable hysteresis for ON/OFF operations.
  • Access Levels: Three password-protected access levels for programming.
  • Connectivity: Can connect to other EKE 347 controllers and supports remote display units.
  • BUS Communication: Integrated support for CAN Bus (Danfoss internal) and MODBUS RTU RS485 for communication with PLCs and SCADA systems.

Applications

The EKE 347 is suitable for a range of applications:

  • Pump Tank: Regulates inflow to maintain a stable liquid level and suction pressure.
  • Evaporator (Full): Maintains consistent liquid levels even under fluctuating load conditions, utilizing the wide capacity range of the control valve.
  • Intercooler: Monitors liquid levels across the entire measurement range, enabling safety functions related to maximum permissible levels.
  • Receiver/Condenser: Ideal for high-pressure float systems with low refrigerant charge due to its fast response time.

System Components and Communication

Signal Transmitters

The controller can be used with microwave inductive level sensors like the AKS 4100/4100U, which offer precise measurement across a wide temperature range.

Expansion Valves

The EKE 347 supports two types of Danfoss expansion valves:

  • ICM: A direct-acting electric valve controlled by an ICAD unit.
  • AKV/A: A pulse-width modulated expansion valve.

An analog input is provided for feedback from the ICM's opening angle.

MODBUS Communication

Equipped with standard RS485 MODBUS-RTU communication, the EKE 347 can interface with PLCs and other third-party devices. This allows for parameter reading and writing, enabling remote operation, monitoring, and data collection via SCADA systems.

Remote Display Option

A panel-mountable remote display (MMIGRS2) can be connected. This display provides a comprehensive overview and access to all EKE 347 controllers connected via the internal Danfoss CAN bus.

Control Panel and Display

The control panel features four buttons: Enter (▶️), Up (⬆️), Down (⬇️), and Back (⬅️). The home screen displays a system overview. The display shows the controller name, measured liquid level, controller mode (On/Off), valve opening angle, and status of low/high level alarms. An audible alarm icon (bell ?) will flash when an alarm is active.

Navigation allows access to the Status Menu (short press of Enter) and the Setup & Service Menu (long press of Enter), which requires password authentication.

Menus

Status Menu (Open Menu)

This menu is accessible to all users and displays information such as:

  • Setpoint
  • Active Alarms
  • Detailed Status (Controller state, measured values, digital input status, etc.)
  • Controller Info (Type, product name, software/BIOS version, address, serial number, etc.)
  • QR Code

Setup & Service Menu

This menu requires a password for access and is divided into three levels:

  • Commissioning: Full access to all parameters, including re-running the setup wizard.
  • Service: Access for service technicians with restricted permissions.
  • Normal: Daily use level with limited modification capabilities.

Parameters and Configuration

The EKE 347 offers extensive configuration options accessible via the Setup & Service menu. These include:

  • Alarm Setup: Configuration of low/high level limits, delays, hysteresis, and common alarms.
  • Control: Settings for control method (On/Off, P, PI), proportional band, integral time, dead band, and valve control parameters.
  • Display: Language selection, output display mode (level/OD), login timeout, backlight settings, and password management.
  • IO Configuration: Setup for system configuration (e.g., ICAD, AKV/A), signal inputs (voltage/current), and valve position feedback.
  • Communication: Configuration for MODBUS (ID, speed, mode, mapping) and CAN Bus (ID, speed).

Detailed parameter tables are available in the documentation, listing each parameter, its range, default value, and Modbus PNU.

Wiring and Connections

The controller features screw terminals for various connections:

  • Supply Voltage: 24V AC/DC.
  • Level Transmitter Input: For sensors like AKS 4100/4100U.
  • Expansion Valve Control: Outputs for controlling ICM or AKV/A valves.
  • Relay Outputs: Configurable for common alarm, high/low level limits.
  • Digital Inputs: For external signals like start/stop or alarms.
  • Communication Ports: RJ45 for CAN bus and screw terminals for MODBUS RTU.

Detailed wiring diagrams are provided for different configurations, including high-level alarms, low-level alarms, and ON/OFF operation. These diagrams illustrate the physical connections between the EKE 347, sensors (e.g., AKS 4100/4100U, AKS 41), expansion valves (ICM, AKV/A), and other system components.

Dimensions: The controller has dimensions of approximately 70mm (width) x 110mm (height) x 63mm (depth), with a 5mm projection for mounting.

Master/Slave and Multi-Valve Systems

The EKE 347 supports master/slave configurations to control multiple expansion valves (up to three) simultaneously. This is configured through the "Multi-valve system setup" and "System connection pattern" (parallel or serial) options in the IO configuration menu.

In a multi-valve system, the master controller displays system status and total opening angle, while slave controllers show their individual status.

Remote Display and Communication Examples

Various examples illustrate the connection of the EKE 347 with sensors, expansion valves, and remote displays via CAN bus and MODBUS.

Error Code ERR31: Indicates a communication failure with the external display (MMIGRS2). Troubleshooting involves checking terminations, display software version, and specific menu settings (MCX selection, COM selection, Start up mode, CAN baudrate/Node ID).

Technical Specifications

Parameter Range Default Value Unit Modbus PNU
Main Switch0-103001
Liquid Level Setpoint0-100%50%3002
Operating Mode0-203003
Low Level Limit0-100%15%3004
High Level Limit0-100%85%3005
Liquid Level Alarm Mode0-103006
Low Level Alarm Delay0-99910sec3007
High Level Alarm Delay0-99950sec3008
Low Level Hysteresis0-20%3%3009
High Level Hysteresis0-20%5%3010
Common Alarm Function0-303011
Vibration Detection Band0-100%100%3012
Vibration Detection Timeout2-3020min3013
Stop Mode Pump OFF0-103117
IO Low Level Limit0-100%5%3101
IO High Level Limit0-100%95%3102
IO Low Level Hysteresis0-20%3%3103
IO High Level Hysteresis0-20%3%3104
IO Low Level Alarm Delay0-99910sec3105
IO High Level Alarm Delay0-99950sec3106
IO Level Limit0-100%50%3107
IO Level Alarm Delay0-99910sec3108
IO Level Hysteresis0-20%3%3109
IO Level Change0-103110
Control Method0-223014
Control Type0-103015
Proportional Band5-200%30.0%3016
Integral Time Tn60-600400sec3017
Dead Band0-25%2.0%3018
Difference0.5-25%2%3019
AKV/AKVA Period Time3-156sec3020
Min OD0-99%0%3021
Max OD1-100%100%3022
Language0-003023
Output Display0-103024
Login Timeout1-12010min3025
Backlight Timeout0-1202min3026
Normal Password0-9991003027
Service Password0-9992003028
Commissioning Password0-9993003029
Contrast0-100%40%3030
Brightness0-100%80%3031
System Configuration0-403032
Liquid Signal Setup0-303033
Low Level Voltage0-100V3034
High Level Voltage0-1010V3035
Low Level Current0-200mA3036
High Level Current0-2020mA3037
Valve Position Setup0-203038
Valve Close Voltage0-100V3039
Valve Open Voltage0-1010V3040
Valve Close Current0-200mA3041
Valve Open Current0-2020mA3042
Common Alarm Setup0-313043
Multi-Valve System Setup0-403044

Ordering Information

Type Description Code No.
EKE 347Level Controller080G5000
MMIGRS2Remote Display, Panel, S080G0294
-Display Unit Cable, 1.5m, 1 pc.080G0075
-Display Unit Cable, 3m, 1 pc.080G0076
-Panel Mount Accessory for EKE / EKC027F0309

Data Specifications

Parameter Specification
Supply Voltage24V AC +/-20% 50/60 Hz or 24V DC +/-20% (Galvanically isolated from input/output signals)
Power ConsumptionController: 15 VA / 10W; AKV or AKVA coil: 55 VA
Input SignalLiquid Level: 4-20 mA or 0-10V; ICM Valve Feedback: ICAD 0/4-20 mA
Relay Output3-pole changeover (Low Level Alarm, High Level Alarm, Common Alarm/NC Solenoid Valve). Rated for 3 A GP, 250V AC. Max 240V AC or 24V AC/DC.
Current Output0-20 mA or 4-20 mA, max load 500 Ω.
Valve ConnectionICM - Current output; AKV/A - 24 VAC pulse-width modulated output.
Data CommunicationMODBUS RTU: For system controller communication. RS485 with galvanic isolation (500V DC). CAN: For communication with other EKE controllers.
Modbus CommandsRead Holding Registers (0x03), Read Input Registers (0x04), Write Single Register (0x06), Diagnostics (0x08), Write Multiple Registers (0x10), Read Device ID (0x43).
Operating Environment-20 to 55°C (operating), -30 to 80°C (storage). 90% relative humidity (non-condensing). Not affected by shock/vibration.
EnclosureIP 20 / IP 40 (front panel mounting).
Weight193 g.
MountingDIN rail.
DisplayLCD display.
TerminalsFor 1.5 or 2.5 mm² multi-core cables.
CertificationsCE, EAC, cULus. Complies with EU Low Voltage Directive (EN 60730-1, EN 60730-2-9) and EMC requirements (EN61000-6-3, EN61000-6-2). UL File E31024.

Disclaimer

While every effort has been made to ensure accuracy, Danfoss is not liable for any errors or omissions in this publication. Danfoss reserves the right to make changes to products without prior notice. Trademarks mentioned are the property of their respective owners.

PDF preview unavailable. Download the PDF instead.

AI190286434038ja-000401 Danfoss A/S Adobe PDF library 8.00

Related Documents

Preview Danfoss EKE 347 Liquid Level Controller Installation Guide
Comprehensive installation guide for the Danfoss EKE 347 liquid level controller, covering system configurations, electrical connections, setup wizard, operation modes, parameter settings, and alarm/error codes.
Preview Техническое описание: Контроллер уровня жидкости Danfoss EKE 347
Подробное техническое описание контроллера уровня жидкости Danfoss EKE 347, включая его применение, преимущества, технические характеристики, схемы подключения и параметры настройки для промышленной автоматизации.
Preview Danfoss AKS 41 Level Transmitter: Operation and Calibration Guide
This guide provides detailed instructions for setting up, calibrating, and operating the Danfoss AKS 41 level transmitter. It covers refrigerant selection, signal damping, min/max calibration, and factory reset procedures for industrial applications.
Preview Danfoss EKC 347 Liquid Level Controller: Manual and Technical Specifications
Comprehensive manual and technical specifications for the Danfoss EKC 347 Liquid Level Controller, detailing its features, operation, parameter settings, and application examples in refrigeration and air conditioning systems.
Preview Danfoss ADAP-KOOL AK-CC55 Case Controller for Efficient Case Cooling
Learn about the Danfoss ADAP-KOOL AK-CC55 case controller and its accessories, designed for efficient and reliable refrigeration case control in food retail. Discover how this integrated solution optimizes performance, enhances energy efficiency, and ensures long-term reliability.
Preview Danfoss EKE 100 Installation Guide: Superheat Controller
Comprehensive installation guide for the Danfoss EKE 100 superheat controller, detailing its features, technical specifications, connection overview, mounting, sensor installation, and safety warnings for use in air conditioning, heat pumps, commercial refrigeration, food retailing, and industrial applications.
Preview Danfoss Industrial Refrigeration Field Service Guide: Installation and Operation
Comprehensive installation and operation guide for Danfoss industrial refrigeration components, including valves, regulators, controls, and sensors. Features product details, service procedures, and technical specifications.
Preview Danfoss AK-XM 205B Instructions and Technical Specifications
Official instructions and technical details for the Danfoss AK-XM 205B controller, covering specifications, wiring, inputs, outputs, and safety guidelines.