EnerSys Ironclad Flooded Lead-Acid Batteries Owner's Manual

This manual provides essential information for the safe handling, operation, and maintenance of EnerSys Ironclad Flooded Lead-Acid Batteries, specifically the Superhog model, used in industrial trucks.

Introduction

The information contained in this document is critical for safe handling and proper use of the Superhog® battery for powering electrical industrial trucks. It contains a global system specification as well as related safety measures, codes of behavior, a guideline for commissioning and recommended maintenance. This document must be retained and available for users working with and responsible for the battery. All users are responsible for ensuring that all applications of the system are appropriate and safe, based on conditions anticipated or encountered during operation.

This owner's manual contains important safety instructions. Read and understand the sections on safety and operation of the battery before operating the battery and the equipment into which it is installed.

It is the owner's responsibility to ensure the use of the documentation and any activities related thereto, and to follow all legal requirements applicable to themselves and the applications in the respective countries.

This owner's manual is not intended to substitute for any training on handling and operating the industrial truck or Superhog® battery that may be required by local laws and/or industry standards. Proper instruction and training of all users must be ensured prior to any contact with the battery system.

For service, contact your sales representative or call: 1-800-ENERSYS (USA) 1-800-363-7797

Website: www.enersys.com

Your Safety and the Safety of others is Very Important

⚠️ WARNING: You can be killed or seriously injured if you don't follow these instructions.

Safety Precautions

To calculate the hydrogen produced, use the following formula and ventilate the area as required:

Formula: .00027 x (finish rate) x (number of cells) = cu. ft. of hydrogen produced per min.

Hydrogen must be ventilated to avoid an explosion. When calculating, assume all chargers are finish rate at the same time. The National Fire Protection Association (NFPA) allows up to 1% concentration. Make sure the ventilation system can remove the hydrogen before it reaches concentrations of 1% within the charging area.

The ventilation system must also be designed to remove fumes and excess heat from the area directly above the charging batteries. Inlet air ducts should be placed at shoulder height or lower to provide air movement across the charging room and batteries. Failure to properly ventilate charging areas may result in employee complaints of heat and "battery odor" and may affect charger components.

Safety Precautions (cont.)

Spills and Recycling

Spills of sulfuric acid should be handled with consideration for the following:

Handling and storage of new and used (spent) batteries

Recycling

Spent lead-acid batteries which are destined for recycling are not regulated under federal hazardous waste regulations or by most state regulations. Contact your state environment agency for additional information.

Fundamentals

Battery

A battery: a device for converting chemical energy into electrical energy. All batteries are made up of individual compartments called cells, connected in series. Size, internal design, and the materials are used to control the amount of energy available from each cell. A lead-acid battery is several cells filled with a mixture of sulfuric acid and water, called electrolyte. The electrolyte covers vertical plates made of two types of lead. Chemical action between the electrolyte and the lead creates electrical energy.

Volt (V)

The standard measure of electrical potential. A DC forklift's running speed and lifting speed are determined by a battery's voltage. AC forklifts typically draw a consistent level of power (Watts) from the battery, which means higher voltage batteries will require lower current draws to do the same work (Watts = Volts x Amperes). The advantage of higher battery voltages in AC lift trucks is lower ampere draws, leading to extended run times. Since each cell in a lead-acid battery has approximately 2 volts, multiply the number of cells by 2 to determine the terminal (overall) voltage. Forklifts are rated for a specific voltage battery.

Ampere (A)

The standard measure of the amount of electric current. The amount, or flow, can be large (amperes) or small (milliamperes). Flashlight batteries are measured in milliamperes. Lift truck battery current is measured in amperes. While it is important to match battery size with the maximum amperage requirements of a forklift truck, the most important factor to keep a truck running for an entire shift is the total capacity the battery has available, i.e. Ampere-hours.

Ampere-hour (Ah)

The amount of current the battery can supply, multiplied by the length of time the battery is discharged. The higher a battery's ampere-hour capacity, the longer a forklift will run. The amp-hour capacity varies with the length of the discharge. American forklift battery manufacturers rate their battery at the 6-hour rate. For example, a hypothetical battery has a rating of 680 ampere-hours (Ah) at the 6-hour rate. By dividing 680 Ah by 6 hours, a discharge rate of 113 amperes is determined. This means that if a forklift's motor and attachments draw 113 amperes continuously, the battery will be completely drained of usable power in 6 hours. To maximize the life of your battery, it should not be discharged below 80% depth of discharge.

Watt (W)

The standard measure of electrical power. Multiplying volts by amperes determines watts. Every 1,000 watts is a kilowatt (kW). The total capacity available from a battery can be determined by multiplying wattage by the length of the discharge. For example, if your forklift needs 10 kW of continuous power for a 6-hour shift, you need a battery that provides 60 kilowatt hours (60 kWh) of energy.

Cycle

Every time a battery is charged and then discharged in use is one cycle. Battery life is usually measured in cycles. In a one-shift-per-day operation, a battery designed for 1,200 to 1,500 80% discharge cycles should last 5 or 6 years. However, battery maintenance and charging procedures will either prolong or shorten battery life depending on how well-recommended procedures are followed. EnerSys will provide training aids and materials whenever requested. Also, when a battery's average voltage measures less than 2.08 volts (open circuit after a full charge) times the total number of cells, the battery either needs repair or has reached the end of its life. To be sure the situation isn't the result of a maintenance problem, call your lift truck dealer or EnerSys representative.

Specific Gravity

As a battery is used, the sulfuric acid in the electrolyte changes into another chemical when it combines with the active material. As a result, there is less and less power-generating sulfuric acid as the battery is discharged. When the battery is recharged, the sulfuric acid returns.

Figure 1: The hydrometer detects the chemical change by measuring the ratio of sulfuric acid to water. In addition, temperature also affects a battery's specific gravity. Temperatures above and below 77°F require correction of the hydrometer reading. EnerSys can provide a thermometer that shows how much to correct for the temperature at your location.

Gassing

Gassing occurs when the battery does not accept some or all of the charge current. This normally occurs during the last 20% of a charging cycle. The water in the electrolyte inside the battery breaks down into hydrogen and oxygen. When this happens, electrolyte will bubble and expand, causing the battery to overflow if any cell was previously filled with too much water. Inexperienced maintenance personnel should never try to replace lost sulfuric acid. Under-watering is even worse than over-watering. The electrolyte level must be above the cell's separator protector during charging and use. Otherwise, part of the plates will be unused. The battery will then overheat and gas more violently. The exposed plates will eventually dry out and become permanently damaged. Scheduled maintenance must be performed if a battery is to work to its full rated capacity.

Construction & Inspection

Construction

Figure 2: Illustrates the construction of a typical motive power cell of the tubular design.

# Description
1 Positive Post
2 Negative Post
3 Positive Plate
4 Negative Plate
5 Negative Grid
6 Positive Spine
7 Separator
8 Vent Cap
9 Jar
10 Cover
11 Bridge
12 Vent Wall

Inspection of the Battery Upon Receipt

Moist-Charged Batteries

Moist-charged batteries are electrically live upon receipt, even before filling with electrolyte. Do NOT lay any metallic objects on the battery.

Moist-charged batteries or cells should be activated (unsealed, filled with electrolyte, and charged) only when ready to be placed in service. Until ready for use, they must be stored in a cool, dry, low-humidity location with the pressure relief valves/vent plugs tightly in place. Moist-charged cells must be activated within 24 hours of the loosening/breaking of the seal of the pressure relief valves/vent plugs.

Moist-Charged Batteries (cont.)

▲ CAUTION: IF THE EXISTING VENT PLUG HAS A LABEL MARKED “DO NOT REMOVE, STOP ALL ACTIVITY AND CALL YOUR LOCAL ENERSYS REPRESENTATIVE.

Installation of Batteries

TAPPING THE BATTERY SHORTENS ITS LIFE BY UP TO THREE YEARS.

Storage - refer to the Storage section.

Operation

Fast Charging and Opportunity Charging

If a single battery is being used in a lift truck for multiple shifts or is partially recharged during breaks, lunches, and other idle periods, it may be in a fast charge or opportunity charge mode of operation.

Opportunity charging can be used to keep the battery's state of charge above 30% depth of discharge during the daily discharge cycle, thereby reducing or even eliminating the need to change out spent batteries in a heavy single-shift or multi-shift operation. Opportunity chargers need to limit battery gassing to one hour per 24-hour period (except for the equalizing charge). The total accumulated discharged ampere-hours should not exceed 120% of the battery's designed capacity rating per day. Discharge of more than 120% of the battery's designed capacity rating in a 24-hour period will shorten battery life. Charge rates during opportunity charging should not exceed 25 amps per 100 amp-hours of a battery's nameplate capacity. Under the opportunity charging procedures outlined in this paragraph, special opportunity battery warranties apply.

Fast charging is intended to extend a battery's run time during a shift or day. A typical fast charging system will provide charge rates from 26 to 50 amps per 100 amp-hours of a battery's nameplate capacity. Fast charging requires special chargers that can monitor and manage battery temperatures during charge, limit battery gassing to no more than one hour per 24-hour period (except for the equalizing charge), assure a battery is recharged to at least 90% state of charge daily, and automatically provide an equalizing charge at least once per week. Also, a fast charge battery should be designed to accept higher charge current and to manage heat that may be created by higher charging rates. A fast charge system, including the battery and charger, should be designed to utilize no more than 160% of the battery's 6-hour capacity rating in a shift day. Under the fast charging procedures outlined in this paragraph, special fast-charging warranties apply.

If engaging in opportunity charging or fast charging, the battery must be returned to nameplate-specific gravity at least once per week (equalizing charge). However, a daily recharge to nameplate-specific gravity is desirable.

Operation

Temperatures

Low Temperatures. The capacity of a storage battery is reduced at low temperatures due to the increased viscosity and resistance of the electrolyte. An approximation of this reduction in capacity for batteries of these types is shown below.

Internal Temperature of Cell (°F) Percent Capacity
77 100
60 95
40 87
20 73
Figure 3: Temperature vs. Battery Life Curve.

This, of course, refers to the actual temperature of the cell and not the ambient temperature. Thus, a battery may be operated in quite low ambient temperatures for short periods without the actual battery temperature falling to a point where the capacity is seriously curtailed. For example, batteries used in cold storage plants or similar locations will deliver close to normal capacity if they are moved into warmer areas for charging and whenever not in actual use.

Low temperatures also increase the battery voltage on the charge, resulting in lower charge currents and a longer recharge time. Undercharging could occur unless charger adjustments are made to compensate.

There is little danger of freezing the battery electrolyte in temperate climates unless the battery is completely discharged. At the temperatures shown in the following table, the electrolyte will not freeze unless the specific gravity is lower than indicated.

Battery Specific Gravity (Corrected to 77°F) Freezes @ or Below Degrees F
1.080 +20
1.130 +10
1.160 0
1.180 -10
1.200 -20
1.215 -30
1.225 -40

In sub-freezing temperatures, water should be added just before charging is completed to ensure prompt mixing with the electrolyte; otherwise, it may freeze on the surface before mixing. No permanent harm results from low-temperature operation as long as freezing is avoided.

High temperatures have an adverse effect and all practical means should be employed to keep the battery temperature at normal values:

The effect of temperature on battery life on any lead-acid truck battery is shown below.

EXAMPLE: If the average lifetime temperature of the battery is 100°F, it will result in a battery life of approximately 53% as compared to 100% at 77°F.

Discharge Characteristics

Cell Type Fully Charged 80% Discharge* 100% Discharge*
E-55L 1.315 1.170 1.130
E-75L 1.315 1.170 1.130
E-75 1.280 1.175 1.140
E-90 1.280 1.150 1.120
E-90D 1.280 1.155 1.125
E-100 1.315 1.150 1.110
E-100X 1.280 1.130 1.090
E-110 1.315 1.155 1.115
E-100D 1.280 1.155 1.125
E-125 1.280 1.150 1.120
E-125D 1.280 1.155 1.125
E-140 1.300 1.145 1.100
E-140X 1.280 1.140 1.105
E-155 1.315 1.155 1.115

*These values are for discharging at the 6 hr. rate, read immediately after the discharge, and corrected to 77°F.

Charging Equipment

Charging Characteristics

Higher temperatures tend to reduce the battery voltage on the charge, permitting higher current flow from the charger and further raising the cell temperatures. Battery temperature at the end of charge should not exceed 125°F.

Should excessive battery temperature occur with some frequency, call your local EnerSys representative for assistance.

When the battery reaches full charge, the charge should be stopped. No amount of overcharging can increase battery capacity.

When charging batteries while they are in the vehicle, ensure proper ventilation. Open the battery cover, if so equipped, as well as the battery compartment cover of the vehicle. Disregarding these recommendations can cause pockets of hydrogen to remain in the vehicle or battery, increasing the risk of explosions when the vehicle is put into use.

The extra effort to ensure proper charging is well spent because it will result in trouble-free battery performance, reduced maintenance, and long battery life.

Maintenance

Lead-Acid Battery Charging Specifications

Battery Type (Charge Type) Flooded (8 HR Charge) Flooded (Opportunity Charge) Flooded (Fast Charge)
Start Charge Rate* 15-20% 15-25% 26-50%
Finish Charge Rate* 4.0-5.0% 4.5-5.0% 5.0%
Charge Interval Daily Opportunity Opportunity
Equalizing Charge Rate* 4.5-5.0% 4.5-5.0% 2.0-3.0%
Equalize Time on Charge 3 Hours 3-7 Hours 10-12 Hours
Equalize Interval Weekly Weekly (minimum) Weekly (minimum)

*Percentage of the battery's 6-hour nameplate ampere-hour capacity rating (ampere output)

Troubleshooting

The following conditions are usually indications of approaching trouble.

Condition Cause Solution
Unequal or low specific gravities* Electrolyte spillage during watering Avoid overwatering, neutralize and clean.
Insufficient charge Water cells during end of charge. Extend charging time.
Internal short Replace cell.
Excessive water requirement Overcharging Select a properly sized charger. Check charging time and average battery temperature.
Jar leakage Replace or repair cell.
Excessive cell temperatures Overcharging Check charger size and charging time.
Battery overworked Reduce to one cycle/day or 300/year maximum.
Battery being charged more than once per day Reduce charging to once per day.
Battery temperature too high at start of charge Allow battery to cool down before starting charge.
Shorted cell(s) Replace defective cell(s).
Poor truck performance Battery undersized Install higher capacity battery.
Undercharged battery Extend charging time.
Discharge indicator malfunction Reset discharge indicator for 80%.
Defective charging connector Replace or repair cable and/or connector.
Excessive loss of electrolyte Check for leakage.*

*For specific gravity adjustments, contact your local EnerSys representative.

Determination of Capacity

Watering

Use only approved water that is 1) distilled water; 2) demineralized water; or 3) local water that has been approved for use in batteries. Never add acid, commercial additives, or other foreign material to the battery. The addition of acid, commercial additives, or foreign material may void your warranty.

If there is some doubt as to whether the water being used is suitable for use in lead-acid storage batteries, obtain an analysis from a qualified laboratory; otherwise, distilled or deionized water should be used. Deionized water is available by using the PRO SERIES® water deionizer.

The Water Impurity Chart shows the maximum allowable impurities.

Requirements Maximum Allowable Limits in Parts Per Million (ppm)
Total Solids 350
Fixed Solids 200
Organic and Volatile 150
Iron 4
Chloride 25
Ammonium (NH₄) 5
Nitrates (NO₂) 10
Nitrates (NO₃) 10
Manganese 0.07
Calcium and Magnesium 40

An EnerSys-approved watering gun is a convenient and accurate tool to aid in watering as it fills to a pre-selected height and automatically shuts off; however, care must be taken to adjust the watering gun so it will water cells to levels following Figure 4, on the next page.

Another convenient way to ensure proper fill levels is the use of a single-point watering (SPW) system. The PRO SERIES® single-point watering systems are efficient methods of watering a battery. These reliable quality systems allow the operator to fill to the proper level each time.

Watering & Cleaning

Watering (cont.)

Water should only be added to the battery when it is near the end of charge and gassing. As the electrolyte is at its maximum level during this time, it is a certainty that the level established by the addition of water will not be exceeded at any other time, and overflow of the electrolyte (flooding) will never occur. When watering near or at the end of the charge, sufficient water should be added to bring the level of the electrolyte between its upper limits. See Figure 4 for details.

It is often inconvenient or impossible to be present at the end of the charge to perform watering. In this case, it is recommended that the battery be watered as soon as possible after the termination of charging, as in this way levels will still be near the maximum and the danger of over- or under-watering is minimized. Fill to the lower limit in this case.

In motive power service, the real need to add water may vary from weekly to quarterly depending on application, battery temperature, and battery design. To extend this interval to the maximum period possible, follow these steps:

  1. Adjust the watering gun to fill to the maximum possible height.
  2. Water while the battery is on charge and gassing.
  3. Do not add water until an actual visual inspection shows the top of separators is visible.
  4. A battery water monitor is an excellent way to indicate when water is needed.
  5. Once a repetitive routine is established, water your battery at that interval.
Figure 4: Sketch showing permissible high and low limits of electrolyte level. High-level marker indicates proper level immediately after charging. Low-level marker indicates immediately after charging watering is required. The high-level line is 1/4" below the bottom of the vent well.

Should the battery start to use excessive water, look for any of the following problems: charger not shutting off automatically, charging rate exceeds rate on battery nameplate, one cell shorted or weakened.

▲ CAUTION: Avoid overfilling as it will cause overflow (flooding) of electrolyte, resulting in loss of electrolyte, tray corrosion, ground paths, and loss of capacity.

Cleaning

⚠️ WARNING: Do NOT use any type of oil, organic solvent, alcohol, detergent, strong acids, strong alkalis, petroleum-based solvent or ammonia solution to clean the jars or covers. These materials may cause permanent damage to the battery jar and cover and will void the warranty.

Cleaning & Storage

Cleaning (cont.)

This spray-on premixed cleaning solution changes color as it neutralizes electrolyte or acids. Use this cleaner or sodium bicarbonate and water (1.0 lb./1.0 gal.) any time you see electrolyte on top of the battery. If any corrosion exists on metal parts of the tray or compartment, repaint with acid-resistant paint after cleaning.

Storage of Batteries

Accessories

Certain accessories and tools are desirable for routine work in the charging room. The following items are recommended for every charging room:

OTHER OPTIONAL ACCESSORIES

EnerSys also offers the following items that are useful in the operation of batteries:

Models: IRONCLAD Flooded Lead Acid Batteries, Flooded Lead Acid Batteries, Lead Acid Batteries, Acid Batteries

File Info : application/pdf, 20 Pages, 8.07MB

PDF preview unavailable. Download the PDF instead.

amer-en-om-iron-sh-0625

References

Adobe PDF Library 17.0

Related Documents

Preview Ironclad Flooded Lead-Acid Batteries Owner's Manual
Comprehensive owner's manual for EnerSys Ironclad Flooded Lead-Acid Batteries, covering safe handling, installation, operation, maintenance, and troubleshooting.
Preview EnerSys IRONCLAD Flooded Lead-Acid Batteries Owner's Manual
Comprehensive owner's manual for EnerSys IRONCLAD Flooded Lead-Acid Batteries, covering safe handling, operation, maintenance, troubleshooting, and specifications for industrial applications.
Preview EnerSys IMPAQ Battery Charger Owner's Manual
Comprehensive owner's manual for the EnerSys IMPAQ Battery Charger, detailing features, technical specifications, safety precautions, installation, operation, fault codes, and maintenance.
Preview IRONCLAD Flooded Lead Acid Battery Owner's Manual
Comprehensive owner's manual for IRONCLAD Flooded Lead Acid batteries, covering safe handling, operation, charging, maintenance, and the Wi-iQ® Battery Monitoring Device. Essential guide for industrial truck applications.
Preview Manual del Propietario: Baterías NexSys® TPPL con Certificación ATEX
Manual del propietario para las baterías NexSys® TPPL con certificación ATEX de EnerSys. Cubre seguridad, instalación, operación, mantenimiento y almacenamiento para entornos peligrosos.
Preview Powerbloc Battery User Manual - EnerSys
Comprehensive user manual for EnerSys Powerbloc batteries, covering operation, safety, charging, maintenance, and storage. Learn how to safely use and maintain your Powerbloc batteries for optimal performance and longevity.
Preview EnerSys Service & Support: Operations, Battery Recycling, and Pre-Owned Solutions
Discover EnerSys's comprehensive service and support solutions, including 24/7 technician coverage, cloud-based reporting, battery recycling programs for lead-acid and lithium-ion, and PROSeries pre-owned batteries and chargers.
Preview EnerSys NexSys TPPL Battery User's Manual: Operation, Maintenance, and Safety
Comprehensive user's manual for EnerSys NexSys TPPL batteries, covering nominal values, safety measures, commissioning, usage, charging, maintenance, storage, troubleshooting, and disposal. Includes technical specifications and terms.