869 Style D Initiation Module Installation Guide

Description

The 869 Style D Initiating Module provides two supervised, power limited Style D, 4-wire initiating zones for connecting waterflow switches and non-powered fire and burglary devices to XR150/XR550 Series panels.

The module supervises both zones for opens, shorts, or ground fault conditions and requires 8.0 VDC to 25.0 VDC auxiliary power, a common ground, and one or two alarm zone inputs from the panel. Program the two alarm zone inputs according to the types of devices being used on the 869 module.

Compatibility

What is Included?

Mount the Module

The module can be mounted in a DMP enclosure using the standard 3-hole mounting pattern. Refer to Figure 2 as needed during installation.

  1. Hold the plastic standoffs against the inside of the enclosure side wall.
  2. Insert the included Phillips head screws from the outside of the enclosure into the standoffs. Tighten the screws.
  3. Carefully snap the module onto the standoffs.
Figure 2: Standoff and Module Installation

[Diagram illustrating the module mounting process. It shows plastic standoffs secured to an enclosure wall with Phillips head screws from the exterior, followed by the module being attached to the standoffs.]

Wire the Module

Caution: Disconnect all power from the panel before wiring the module. Failure to do so may result in equipment damage or personal injury.

For power connections, use 22 AWG or larger wire. Refer to Figure 3 when wiring the module.

  1. Connect module Terminals A1 and A2 to zone A devices.
  2. Connect module Terminal LOOP A to a panel zone 1-8.
  3. Connect module Terminal GND to panel ground or battery negative.
  4. Connect module Terminal AUX to auxiliary power (8.0 VDC-25.0 VDC).
  5. Connect module Terminal LOOP B to a panel zone 1-8.
  6. Connect module Terminals B1 and B2 to zone B devices.
Figure 3: Wiring Diagram

[Wiring diagram for the 869 Style D Initiation Module. It depicts Zone A and Zone B, each configured with two 'Manual Pull' devices and one 'Heat Detector' in series, noting 'No EOL Resistor Required' for these connections. Terminal connections are shown: A1/A2 for Zone A devices, B1/B2 for Zone B devices, LOOP A/LOOP B to panel zones (1-8), GND to panel ground or battery negative, and AUX to auxiliary power (8.0 VDC-25.0 VDC). It also includes 'GND FAULT' indicators for both zones and notes maximum line impedance and ground fault resistance values.]

Additional Information

Wiring Specifications

DMP recommends using 18 or 22 AWG for all LX-Bus and Keypad Bus connections. The maximum wire distance between any module and the DMP Keypad Bus or LX-Bus circuit is 1,000 feet. To increase the wiring distance, install an auxiliary power supply, such as a DMP Model 505-12. Maximum voltage drop between a panel or auxiliary power supply and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit.

To maintain auxiliary power integrity when using 22-gauge wire on Keypad Bus circuits, do not exceed 500 feet. When using 18-gauge wire, do not exceed 1,000 feet. Maximum distance for any bus circuit is 2,500 feet regardless of wire gauge. Each 2,500 foot bus circuit supports a maximum of 40 LX-Bus devices.

For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031) and the 710 Bus Splitter/Repeater Module Installation Guide (LT-0310).

Operation

The Class A, Style D circuit consists of a 2-wire zone out to the protective devices and a 2-wire return from the last device to the module. In the event of an open condition on the circuit, devices on either side of the fault could still initiate an alarm. During an alarm (shorted) condition on either Style D zone, the module shorts the panel alarm zone to ground. During a trouble (open) or ground fault condition on either zone, the module opens the panel alarm zone. In addition, ground fault conditions on either Zone A or Zone B light the corresponding red LED.

Specifications

SpecificationValue
Operating Voltage8.0 VDC to 25.0 VDC
Operating Current25 mA Standby, 75 mA Maximum (both zones shorted to ground)
Zone TypesTwo Style D, 4-wire initiating circuits
Zone Voltage5 VDC, 1.5 mA max

Ordering Information

869 Style D Initiation Module

Certifications

Models: STYLE D, XR150, XR550

File Info : application/pdf, 2 Pages, 327.86KB

PDF preview unavailable. Download the PDF instead.

LT-0186

References

Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)

Related Documents

Preview DMP 866 Style W Notification Module Installation Guide
Installation guide for the DMP 866 Style W Notification Module, detailing mounting, wiring, programming, specifications, and compatibility with DMP alarm panels. Includes detailed instructions and textual descriptions of diagrams.
Preview DMP 866 Style W Notification Module Installation Guide
Installation guide for the DMP 866 Style W Notification Module, detailing its description, compatibility, mounting, wiring, and specifications for fire alarm systems.
Preview DMP 711S Zone Expansion Module Installation Guide
Comprehensive installation guide for the DMP 711S Zone Expansion Module, detailing setup, wiring, programming, and compliance for DMP XT30/XT50 and XR150/XR550 series alarm panels.
Preview 1135 Series Wireless Siren Installation Guide
Comprehensive installation guide for the DMP 1135 Series Wireless Siren, covering programming, mounting, battery replacement, specifications, and regulatory compliance for security system installers.
Preview DMP 716 Output Expansion Module Installation Guide
Installation guide for the DMP 716 Output Expansion Module, detailing its features, mounting, wiring, addressing, and programming for XR150/XR550 series alarm panels. Includes specifications and compliance information.
Preview DMP 714/715 Zone Expansion Module Installation Guide
Comprehensive installation guide for DMP 714 and 715 Zone Expansion Modules. Learn about wiring, compatibility with DMP XT30/XT50 and XR150/XR550 panels, and setup for burglary and fire alarm systems.
Preview DualCom Series Universal Alarm Communicator Compliance Listing Guide
Compliance information, programming requirements, and installation details for the DMP DualCom Series Universal Alarm Communicator, including models DualComNF and DualComN, for commercial fire and burglary alarm systems.
Preview DMP XTLtouch Wireless Security System: Features and Benefits
Explore the DMP XTLtouch, an all-in-one wireless security system offering enhanced features like multiple keypads, sirens, Z-Wave device control, and remote access via the Virtual Keypad app. Learn about its flexible installation options and advanced entry check-in protection.