Room sensor for relative humidity and temperature

HTS201 Manual

Download-Center


File Info : application/pdf, 22 Pages, 3.18MB

PDF preview unavailable. Download the PDF instead.

BA HTS201
User Manual HTS201
Humidity and Temperature Room Sensor

User Manual HTS201

Content

1 General Information...................................................................................................................................... 3 1.1 Explanation of Warning Notices and Symbols ....................................................................................... 3 1.2 Safety Instructions ................................................................................................................................ 4 1.2.1. General Safety Instructions ......................................................................................................................... 4 1.2.2. Intended Use ............................................................................................................................................... 4 1.2.3. Mounting, Start-up and Operation................................................................................................................ 4 1.3 Environmental Aspects.......................................................................................................................... 5 1.4 ESD Protection .................................................................................................................................... 5

2 Scope of Supply ........................................................................................................................................... 5

3 Product Description ..................................................................................................................................... 6 3.1 General................................................................................................................................................. 6 3.2 Dimensions ........................................................................................................................................... 7 3.3 Electrical Connection ............................................................................................................................ 7 3.4 Display.................................................................................................................................................. 8

4 Mounting and Installation ............................................................................................................................ 9

5 Setup and Configuration ............................................................................................................................ 10

5.1 PCS10 Product Configuration Software .............................................................................................. 10 5.2 RS485 Digital Interface ....................................................................................................................... 11
5.2.1. Hardware Bus Termination .........................................................................................................................11 5.2.2. Device Address ..........................................................................................................................................11

5.2.3. BACnet Protocol Settings .......................................................................................................................... 12 5.2.4. Modbus RTU Protocol Settings.................................................................................................................. 12

5.2.5. 5.2.6. 5.2.7. 5.2.8.

Modbus Register Map ............................................................................................................................... 13 Freely Configurable Custom Modbus Map................................................................................................. 14 Device Status Indication and Error Monitoring........................................................................................... 15 ModBus RTU Examples............................................................................................................................. 16

6 Maintenance and Service ........................................................................................................................... 18

6.2.1. 6.2.2. 6.2.3.

Basic Cleaning .......................................................................................................................................... 18 Error Messages in PCS10 ......................................................................................................................... 18 Repairs...................................................................................................................................................... 18

7 Accessories ................................................................................................................................................ 18

8 Technical Data ............................................................................................................................................ 19

9 Conformity .................................................................................................................................................. 21 9.1 Declarations of Conformity.................................................................................................................. 21 9.2 FCC Part 15 Compliance Statement ................................................................................................... 21 9.3 ICES-003 Compliance Statement........................................................................................................ 21

Humidity and Temperature Room Sensor | 2

User Manual HTS201
1 General Information
This user manual serves for ensuring proper handling and optimal functioning of the device. The user manual shall be read before commissioning the equipment and it shall be provided to all staff involved in transport, installation, operation, maintenance and repair. E+E Elektronik Ges.m.b.H. does not accept warranty and liability claims neither upon this publication nor in case of improper treatment of the described products. This document may contain technical inaccuracies and typographical errors. The content will be revised on a regular basis. These changes will be implemented in later versions. The described product(s) can be improved and changed at any time without prior notice. The user manual may not be used for the purposes of competition without the written consent of E+E Elektronik Ges.m.b.H. and may not be forwarded to third parties. Copies may be made for internal purposes. All information, technical data and diagrams included in these instructions are based on the information available at the time of writing.
PLEASE NOTE Find this document and further product information on our website at www.epluse.com/hts201.

1.1

Explanation of Warning Notices and Symbols
Safety precautions Precautionary statements warn of hazards in handling the device and provide information on their prevention. The safety instruction labeling is classified by hazard severity and is divided into the following groups:
DANGER Danger indicates hazards for persons. If the safety instruction marked in this way is not followed, the hazard will verly likely result in severe injury or death.

WARNING
Warning indicates hazards for persons. If the safety instruction marked in this way is not followed, there is a risk of injury or death.

CAUTION
Caution indicates hazards for persons. If the safety instruction marked in this way is not followed, minor or moderate injuries may occur.

NOTICE Notice signals danger to objects or data. If the notice is not observed, damage to property or data may occur.
Informational notes Informational notes provide important information which stands out due to its relevance.
INFO The information symbol indicates tips on handling the device or provides additional information on it. The information is useful for reaching optimal performance of the device. The title field can deviate from "INFO" depending on the context. For instance, it may also read "PLEASE NOTE".

Humidity and Temperature Room Sensor | 3

User Manual HTS201
1.2 Safety Instructions
1.2.1. General Safety Instructions NOTICE Improper handling of the device may result in its damage.
 The HTS201 enclosure and the electronics board inside shall not be exposed to unnecessary mechanical
stress.
 Do not apply the supply voltage to the RS485 data lines.  The HTS201 electronics is sensitive to electrostatic discharge (ESD), appropriate protective measures shall
be taken when touching it.
 Use the HTS201 only as intended and observe all technical specifications.
1.2.2. Intended Use WARNING
Non-compliance with the product documentation may cause safety risk for people and the entire measurement installation. The manufacturer cannot be held responsible for damages as a result of incorrect handling, installation, and maintenance of the device.
 Do not use HTS201 in explosive atmosphere or for measurement of aggressive gases.  This device is not appropriate for safety, emergency stop or other critical applications where device
malfunction or failure could cause injury to human beings.
 The device may not be manipulated with tools other than specifically described in this manual.
NOTICE Failing to follow the instructions in this user manual may lead to measurement inaccuracy and device failures.
 The HTS201 may only be operated under the conditions described in this user manual and within the
specification included in chapter 8 Technical Data.
 Unauthorized product modification leads to loss of all warranty claims. Modification may be accomplished
only with an explicit permission of E+E Elektronik Ges.m.b.H.!
1.2.3. Mounting, Start-up and Operation The HTS201 has been produced under state of the art manufacturing conditions, has been thoroughly tested and has left the factory after fulfilling all safety criteria. The manufacturer has taken all precautions to ensure safe operation of the device. The user must ensure that the device is set up and installed in a way that does not impair its safe use. The user is responsible for observing all applicable local and international safety guidelines for safe installation and operation of the device. This user manual contains information and warnings that must be observed by the user in order to ensure safe operation.
PLEASE NOTE The manufacturer or his authorized agent can only be held liable in case of willful or gross negligence. In any case, the scope of liability is limited to the corresponding amount of the order issued to the manufacturer. The manufacturer assumes no liability for damages incurred due to failure to comply with the applicable regulations, operating instructions or the specified operating conditions. Consequential damages are excluded from the liability.
Humidity and Temperature Room Sensor | 4

User Manual HTS201

WARNING
Non-compliance with the product documentation may cause accidents, personal injury or property damage.
 Mounting, installation, commissioning, start-up, operation and maintenance of the device may be
performed by qualified staff only. Such staff must be authorized by the operator of the facility to carry out
the mentioned activities.
 The qualified staff must have read and understood this user manual and must follow the instructions
contained within.
 All process and electrical connections shall be thoroughly checked by authorized staff before putting the
device into operation.
 Do not install or start-up a device supposed to be faulty. Make sure that such devices are not accidentally
used by marking them clearly as faulty.
 A faulty device shall be removed from the process.  Service operations other than described in this user manual may only be performed by the manufacturer.

1.3

Environmental Aspects
PLEASE NOTE Products from E+E Elektronik Ges.m.b.H. are developed and manufactured in compliance with all relevant environmental protection requirements. Please observe local regulations for the disposal of the device.

For disposal, the individual components of the device must be separated according to local recycling regulations. The electronics shall be disposed of correctly as electronics waste.

1.4

ESD Protection
The sensing elements and the electronics board are ESD (electrostatic discharge) sensitive components of the device and must be handled as such. The failure to do so may damage the device by electrostatic discharges when touching exposed sensitive components.

2 Scope of Supply
 HTS201Room Sensor for Humidity and Temperature according to ordering guide  Mounting set  Quick Guide for digital version

Humidity and Temperature Room Sensor | 5

User Manual HTS201

3 Product Description

3.1

General
The HTS201 is aRHandT room sensor for demand controlled ventilation and building automation. It is designed for indoor wall mounting in residential and commercial applications.
Depending on the target market, the sensor is available with an EU or US enclosure. For dimensions, please refer to chapter 3.2 Dimensions. The electronics of HTS201 is located in the front cover, which can be easily snapped on/off once the back cover is fixed onto the wall and wired. The back cover contains just the push-in terminals. No tools are needed for mounting or changing the active part.

Front cover

Back cover
RHandT can also be read on the optional display. Please refer to chapter 3.4 Display. The measured data is available on two types of output: The analogue versions deliver the measurands according to the ordering code. Model, measurement units (metric or non-metric) and output scaling can not be changed by the customer. The versions with digital interface supply all available quantities. For further information, please refer to chapter 5.2.5. Modbus Register Map and chapter 8 Technical Data. By means of a jumper, the RS485 termination resistor can be set on or off. For BACnet, please see the PICS (Product Implementation Conformance Statement), which is available at www.epluse.com/hts201. For a setup deviating from default, the digital HTS201 can be configured manually with the free PCS10 Product Configuration Software and an optional configuration adapter. Refer to chapter 5 Setup and Configuration for details.

Humidity and Temperature Room Sensor | 6

3.2 Dimensions
Values in mm (inch) Enclosure EU format
85 (3.35) 40 (1.57)

User Manual HTS201

Enclosure US format

23 (0.91)

85 (3.35) 40 (1.57)

23 (0.91)

85 (3.35) 30 (1.18) 115 (4.53) 30 (1.18)

Optional display

Optional display

3.3

Electrical Connection
For connecting the power supply and the outputs, the HTS201 features push-in spring terminals for max. 1.5 mm2 (AWG 16). The cables are fed into the enclosure via the rear side.
WARNING Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property.
For correct cabling of the device, always observe the presented wiring diagram for the product version used.
The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.

HTS201 voltage output

Connection scheme

15 - 35 V DC 24 V AC ±20 %

Humidity and Temperature Room Sensor | 7

HTS201 current output

User Manual HTS201 Connection scheme
15 - 35 V DC

HTS201 digital interface

Connection scheme Connection on the electronics board

15 - 35 V DC 24 V AC ±20 %
Connection assignment appropriate for daisy-chain wiring

3.4

Display
The optional display shows the measured values (according to ordering code) and the measurement unit. The temperature unit is selected via order code. Tab. 1 shows the way measurands are displayed.

Line
1 2

Measurand
Humidity Temperature

Tab. 1 Order of displayed measurands

Humidity and Temperature Room Sensor | 8

User Manual HTS201
4 Mounting and Installation
As the room sensor is generally mounted onto a conduit box, for accurate measurement results it is important to tighten the conduit box for avoiding false air ingress (along the electrical tubes inside the wall) into the room sensor enclosure.
PLEASE NOTE In order to protect the front cover and the electronics from typical construction site pollution (such as painting of the walls) the front cover should be snapped on only after the construction works are completed. Please mind the following rules of thumb for sensor positioning:
 Mount the Sensor 2 m (6.6 ft) away from outlets and intakes  Mount the Sensor at a height of 1.5 m (5 ft) (half of room height)  Avoid direct sunlight from window  Avoid restricted airflow  Avoid close proximity to heat sources  Avoid heat accumulation  Avoid draught
1.5 m / 5 ft

The electronics is located in the front cover, which can be easily snapped on/off once the back cover is fixed onto the wall and wired.

Opening the enclosure

B

Press to release the latch A till the enclosure can be

opened.

Closing the enclosure Set the front cover into flutes B, rotate it like C and press it onto the back cover till the latch A snaps in.

C A

Humidity and Temperature Room Sensor | 9

Mounting Dimensions, values in mm (inch) EU format

81 (3.2) 4 (0.2)

4 (0.2) 30 (1.2)

5 (0.2)

7 (0.3)
40.5 (1.6)

81 (3.2) 15 (0.6)

Ø 60 (2.4)

55.5 (2.2)

15 (0.6)

1 (0.04)

User Manual HTS201

US format

81 (3.2) 4 (0.2)

Ø 60 (2.4)

4 (0.2)

30 (1.2)

5 (0.2)

41.65 (1.6) 83.3 (3.3) 111 (4.4)

5 Setup and Configuration
The HTS201 is ready to use and does not require any configuration by the user. The factory setup of HTS201 corresponds to the type number ordered. Please refer to the datasheet at www.epluse.com/hts201. While the room sensors with analogue output do not provide a configuration interface, the digital versions offer some options for customization. If needed, the user can change the factory setup with the help of the free PCS10 Product Configuration Software and the optional USB configuration adapter (HA011066).
The following settings can be made with the help of the PCS10:
 Change interface communication parameters  Setup and edit the custom Modbus map  Set individual device name
The PCS10 makes visible the
 Basic device data, e.g. serial number, firmware version  Device status register in the form of a device error list  Measurand(s) as a live graph
Furthermore, the device configuration can be exported and imported. It is possible to reset the device to factory settings and to update the firmware.

5.1

PCS10 Product Configuration Software
To use the software for changes in settings, please proceed as follows:
1. Download the PCS10 Product Configuration Software from www.epluse.com/pcs10 and install it on the PC. 2. Connect the HTS201 to the PC using the USB configuration adapter. 3. Start the PCS10 software. 4. Follow the instructions on the PCS10 opening page for scanning the ports and identifying the connected
device 5. Click on the desired setup or adjustment mode from the main PCS10 menu on the left. Follow the online
instructions of the PCS10 which are displayed when clicking the "Tutorial" button. 6. Changes are uploaded to the probe by pressing the "Sync" button.

Humidity and Temperature Room Sensor | 10

User Manual HTS201
NOTICE The HTS201 may not be connected to any additional power supply when using the USB configuration adapter HA011066.

PC

HA011066

Fig. 1 HTS201 connected to a PC running PCS10

5.2 RS485 Digital Interface
5.2.1. Hardware Bus Termination E+E room sensors with digital interface feature an internal 120  resistor for bus termination HTS201 which can be activated using the jumper on the electronics board (see also chapter 3.3 Electrical Connection for details).

Jumper not mounted, (right position = factory setup) Bus is not terminated

Jumper mounted, (left position) Bus is terminated

Fig. 2 Jumper position for RS485 bus termination resistor
5.2.2. Device Address
Address setting via PCS10 Product Configuration Software All DIP switches at position 0  address has to be set via PCS10 Modbus (slave device): factory setting 45 (permitted values: 1...247). BACnet (master device): factory setting 45 (permitted values: 0...127). Example: Address is set via configuration software = factory setting.
Address setting via DIP switch Modbus (slave device): Setting the DIP switches to any other address than 0, overrules the Modbus address set via PCS10 (permitted values: 1...247). BACnet (master device): Setting the DIP switches to any other address than 0, overrules the BACnet address set via configuration software. BACnet note: permitted values are 0...127. The 8th bit of the DIP switches is ignored (ID 127 = 0111 111). To set address 0 via DIP switches, the 8th bit shall be set to 1 (ID 0 = 1000 0000). Example: Address set to 11 (= 0000 1011 binary).

Humidity and Temperature Room Sensor | 11

User Manual HTS201

5.2.3. BACnet Protocol Settings

Baud rate Data bits Parity Stop bits BACnet address

Factory settings As ordered via order code 8 None 1 45

Tab. 2 BACnet protocol settings

User selectable values (via EE-PCS) 9600, 19200, 38400, 57600, 76800, 115200 8 None 1 0...127

PLEASE NOTE The recommended settings for multiple devices in a BACnet MS/TP network are 38400, 8, none, 1.

The HTS201 PICS (Product Implementation Conformance Statement) is available on the E+E website at www.epluse.com/hts201.

BACnet address and baud rate can be set via:
 PCS10 Product Configuration Software and the USB configuration adapter HA011066.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
 BACnet protocol, see the PICS.

5.2.4. Modbus RTU Protocol Settings

Baud rate Data bits

Factory settings As ordered via order code1) 8

User selectable values (PCS10) 9600, 19200, 38400, 57600, 76800, 115200 8

Parity

Even

None, odd, even

Stop bits

1

1, 2

Modbus address

45

1...247

1) Please refer to datasheet; not all user selectable values are available ex works.

Tab. 3 Modbus RTU protocol settings

PLEASE NOTE The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.
Device address, baud rate, parity and stop bits can be set via:
 EE-PCS Product Configuration Software and the USB configuration adapter HA011066.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
 Modbus protocol in the register 1 (0x00) and 2 (0x01).
See Application Note Modbus AN0103 (available at www.epluse.com/hts201). The serial number as ASCII-code is located in read-only registers 1 - 8 (0x00 - 0x07, 16 bits per register). The firmware version is located in register 9 (0x08) (bit 15...8 = major release; bit 7...0 = minor release). The sensor name is located in registers 10 - 17 (16 bits per register).
NOTICE When reading the serial number or the sensor name, it is always necessary to read all 8 registers, even if the desired information requires less.
NOTICE For obtaining the correct floating point values, both registers have to be read within the same reading cycle. The measured value can change between two Modbus requests, exponent and mantissa may get inconsistent then.
Humidity and Temperature Room Sensor | 12

User Manual HTS201

Communication settings (INT16) Parameter Write register: function code 0x06 Modbus address Modbus protocol settings3)

Register number1) [Dec]
1 2

Register address2) [Hex]
0x00 0x01

Device information (INT16) Parameter

Register number1) [Dec]

Register address2) [Hex]

Read register: function code 0x03 / 0x04

Serial number (as ASCII)

1

0x00

Firmware version

9

0x08

Sensor name (as ASCII)

10

Device status (bit decoded)4)

602

0x09 0x259

1) Register number starts from 1. 2) Protocol address starts from 0. 3) For Modbus protocol settings see Application Note Modbus AN0103 (available at www.epluse.com/hts201). 4) See chapter 5.5 Device Status Indication.

Tab. 4 HTS201 registers for device setup

5.2.5. Modbus Register Map
The measured data is saved as a 32 bit floating point values (data type FLOAT32) and as 16 bit signed integer values (data type INT16).

FLOAT32 Parameter

Unit1)

Read register: function code 0x03 / 0x04

°C

Temperature T

°F

K

Relative humidity RH, Uw

%

°C

Dew point temperature Td

°F

°K

Register number2) [DEC]
1003 1005 1009 1021 1105 1107 1147

Register address3) [HEX]
0x3EA 0x3EC 0x3F0 0x3FC 0x450 0x452 0x47A

INT16 Parameter

Unit1)

Scale4) Register number2) [DEC] Register address3) [HEX]

Read register: function code 0x03 / 0x04

°C

100

4002

0xFA1

Temperature T

°F

50

4003

0xFA2

°K

50

4005

0xFA4

Relative humidity RH, Uw

%RH

100

4011

0xFAA

°C

100

4053

0xFD4

Dew point temperature Td

°F

100

4054

0xFD5

°K

100

4074

0xFE9

1) The choice of measurement units (metric or non-metric) must be done according to the ordering guide, see HTS201 datasheet. Switching from metric to non-metric or vice versa by using the PCS10 is not possible.
2) Register number starts from 1 3) Register address starts from 0 4) Examples: For scale 100, the reading of 2550 means a value of 25.5. For scale 50, the reading of 2550 means a value of 51.

Tab. 5 HTS201 FLOAT32 and INT16 measured data registers

Humidity and Temperature Room Sensor | 13

User Manual HTS201

5.2.6. Freely Configurable Custom Modbus Map

It is possible to map measured value/status registers arbitrarily in a block with up to 20 registers provided for this purpose. This means that registers of interest may be mapped in an area with consecutive registers, so that important values can be queried with a single command in one block.

The custom map can be configured via:
 PCS10 Product Configuration Software and the Modbus configuration adapter HA011018.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
 Modbus protocol commands, refer to the example in chapter 5.2.8. ModBus RTU Examples.

The register block for the configuration of the customisable Modbus map consists of the registers 6001 (0x1770) to 6010 (0x1779). For the blockwise query of the measured values behind Modbus registers 3001 (0xBB8) to 3020 (0xBCB), the firmware accesses this configuration area and thus gets the information which measured value/status registers are to be output. A maximum of 10 user-defined registers can be mapped. The table below shows an example:

Registers ...

... with these assigned measurands ...

... map to registers ...

... mirrored from source registers

Dec

Hex

Meas.

Unit

Type

Dec

Hex

Dec

Hex

Function code 0x10

Function code 0x03/0x04

6001

0x1770

T

°C

FLOAT32

3001

0xBB8

1003

0x3EA

°C

FLOAT32

3002

0xBB9

6002

0x1771

T

°F

FLOAT32

3003

0xBBA

1005

0x3EC

°F

FLOAT32

3004

0xBBB

6003

0x1772

T

K

FLOAT32

3005

0xBBC

1009

0x3F0

K

FLOAT32

3006

0xBBD

6004

0x1773

RH

%

FLOAT32

3007

0xBBE

1021

0x3FC

%

FLOAT32

3008

0xBBF

6005

0x1774

T

°C

INT16

3009

0xBC0

4002

0xFA1

6006

0x1775

RH

%

INT16

3010

0xBC1

4011

0xFAA

3011

0xBC2

3012

0xBC3

3013

0xBC4

3014

0xBC5

3015

0xBC6

3016

0xBC7

3017

0xBC8

3018

0xBC9

3019

0xBCA

3020

0xBCB

Tab. 6 Custom Modbus map example

Humidity and Temperature Room Sensor | 14

User Manual HTS201

5.2.7. Device Status Indication and Error Monitoring
ModBus The HTS201 features a status register which contains all status and error information. It is possible to read it from Modbus register 602 (0x259).
If a critical error occurs, all Modbus values are set to NaN (according to IEEE754 for data type FLOAT32) or to 0x8000 (INT16). Errors are displayed in bit-coded form. If an event is present, the corresponding bit is set to 1.
Measured values outside the measuring range are limited with the corresponding limit value.

Error bits Bit 0

Description Temperature below lower limit

Bit 1

Temperature above upper limit

Bit 2 Bit 3

Temperature value = infinite Humidity below lower limit

Bit 4

Humidity above upper limit

Bit 5
Bit 6 Bit 7 Bit 8 Bit 9 Bit10 Bit 11

Humidity value = infinite
RH/T element not accessible Display communication broken

Tab. 7 Device status indication register

Recommended action 1. Check the actual temperature with the
temperature output scaling of the ordered sensor 2. Service recommended, check the repair possibilities with the E+E service 1. Check the actual temperature with the temperature output scaling of the ordered sensor 2. Service recommended, check the repair possibilities with the E+E service 1. Check the wiring 2. Service recommended, check the repair possibilities with the E+E service 1. Check the actual relative humidity with the humidity output scaling of the ordered sensor 2. Service recommended, check the repair possibilities with the E+E service 1. Check the actual relative humidity with the humidity output scaling of the ordered sensor 2. Service recommended, check the repair possibilities with the E+E service 1. Check the wiring 2. Service recommended, check the repair possibilities with the E+E service
Service recommended, check the repair possibilities with the E+E service
Service recommended, check the repair possibilities with the E+E service

PCS10 In the Information section, the PCS10 Product Configuration Software displays possible errors and states. Please refer to chapter 6.2.2. Error Messages in PCS10.

BACnet In the event of a serious error, the "Present Value" of each Analogue Input Object is set to NaN and "Reliability" is set to NO_SENSOR. The ,,Event State" Property is set to FAULT. Please refer to the HTS201 PICS (Product Implementation Conformance Statement) at www.epluse.com/hts201.

Humidity and Temperature Room Sensor | 15

User Manual HTS201

5.2.8. ModBus RTU Examples
The HTS201 Modbus address is 46 [0x2E].
Please refer to
 MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b3, chapter 6:
www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
 E+E Application Note Modbus AN0103 (available at www.epluse.com/hts201)
Read the temperature (FLOAT32) T = 23.4400005340576171875 °C from register address 0x3EA:

Master (e.g. PLC) Request [Hex]: Modbus Function address code

Starting address Hi

Starting

Qty. of

Qty. of

address Lo registers Hi registers Lo

CRC

2D

03

03

EA

00

02

12 53

HTS201

Response [Hex]: Modbus Function address code

2D

03

Byte count
04

Register 1 Register 1 Register 2 Register 2 value Hi value Lo value Hi value Lo

CRC

85

1F

41

BB

7F 18

Fig. 3 Example temperature query

Decoding of floating point values: Floating point values are stored according to IEEE754. The byte pairs 1, 2 and 3, 4 are transformed as follows (numbers taken from T reading Modbus request/response example above):

Modbus response [Hex] Byte 3 85 MMMMMMMM

Byte 4 1F MMMMMMMM

Byte 1 41 SEEEEEEE

Byte 2 BB EMMMMMMM

Tab. 8 Modbus response

IEEE754

Byte 1

Byte 2

41

BB

0100 0001

1011 1011

SEEE EEEE

EMMM MMMM

Decimal value: 23.4400005340576171875

Byte 3 85 1000 0101 MMMM MMMM

Byte 4 1F 0001 1111 MMMM MMMM

Tab. 9 Data representation according to IEEE754

Read register from unconfigured custom modbus map address 0xBB8-0xBB9:

Master (e.g. PLC) Request [Hex]: Modbus Function address code

Starting address Hi

Starting

Qty. of

Qty. of

address Lo registers Hi registers Lo

CRC

2D

03

0B

BB

00

02

41 A6

HTS201

Response [Hex]: Modbus Function address code

2D

03

Byte count
04

Register 1 Register 1 Register 2 Register 2 value Hi value Lo value Hi value Lo

CRC

FF

FF

FF

FF

16 65

Fig. 4 Query of an unconfigured custom Modbus map

Humidity and Temperature Room Sensor | 16

User Manual HTS201

Mapping a simple custom Modbus map assign RH [%] (address 0x3FC) and T [°C] (address 0x3EA) to the map, starting address 0xBB8:

Master (e.g. PLC)

Request [Hex]:

Modbus Function

address

code

Starting Starting

Qty. of

Qty. of

address Hi address Lo registers Hi registers Lo

Byte count

HTS201

2D

10

17

70

00

02

04

Register 1 Register 1 Register 2 Register 2 value Hi value Lo value Hi value Lo

CRC

03

FC

03

EA

CA E0

Response [Hex]:

Modbus Function

address

code

2D

10

Starting Starting

Qty. of

Qty. of

address Hi address Lo registers Hi registers Lo

CRC

17

70

00

02

42 0B

Fig. 5 Mapping a simple custom Modbus map

Query register address 0xBB8 (RH [%] mapped)

Master (e.g. PLC) Request [Hex]: Modbus Function address code

Starting address Hi

Starting

Qty. of

Qty. of

address Lo registers Hi registers Lo

CRC

2D

03

0B

B8

00

02

41 A6

HTS201

Response [Hex]: Modbus Function address code

2D

03

Byte count
04

Register 1 Register 1 Register 2 Register 2 value Hi value Lo value Hi value Lo

CRC

0A

3D

42

56

25 7B

Fig. 6 Read RH value

Query consecutive registers, addresses 0xBB8-0xBBD (RH [%] and T [°C] mapped, one register empty)

Master (e.g. PLC) Request [Hex]: Modbus Function address code

Starting address Hi

Starting

Qty. of

Qty. of

address Lo registers Hi registers Lo

CRC

2D

03

0B

B8

00

06

40 65

HTS201

Response [Hex]: Modbus Function address code

Byte count

Register 1 Register 1 Register 2 Register 2 Register 3 value Hi value Lo value Hi value Lo value Hi

2D

03

0C

14

7B

42

5D

33

Register 3 Register 4 Register 4 Register 5 Register 5 Register 6 Register 6 value Lo value Hi value Lo value HI value Lo value Hi value Lo

CRC

33

41

C1

FF

FF

FF

FF

74 63

Fig. 7 Read several values with a single query

Humidity and Temperature Room Sensor | 17

User Manual HTS201

6 Maintenance and Service

6.2.1. Basic Cleaning
If the response times are longer than specified, this may be due to contamination. In this case clean the ventilation slots by blowing from inside out.

6.2.2. Error Messages in PCS10
The PCS10 information section includes error messages from HTS201, if there are any errors present. The following table shows the error codes and their meaning. Please note that this table directly corresponds to Tab. 7 Device status indication register in chapter 5.2.7.

Error code Description

7.x

Temperature measurement incorrect

9.x

Humidity measurement incorrect

19.x

Sensing element not accessible

21.x

Display communication faulty

Recommended action
1. Check the actual temperature with the temperature output scaling of the ordered sensor, check the wiring
2. Service recommended, check the repair possibilities with the E+E service
1. Check the actual temperature with the temperature output scaling of the ordered sensor, check the wiring
2. Service recommended, check the repair possibilities with the E+E service
Service recommended, check the repair possibilities with the E+E service
Service recommended, check the repair possibilities with the E+E service

Tab. 10 Possible error messages for HTS201

6.2.3. Repairs
PLEASE NOTE Repairs may be carried out by the manufacturer only. The attempt of unauthorized repair excludes any warranty claims.

7 Accessories

Description
E+E Product Configuration Software (Free download from www.epluse.com/pcs10)
USB Configuration Adapter for HTS201 digital

Code
PCS10
HA011066

Humidity and Temperature Room Sensor | 18

User Manual HTS201

8 Technical Data

Measurands

Relative Humidity (RH)

Measuring range
Accuracy1) incl. hysteresis, non-linearity and repeatability
0...100 %RH

0...100 %RH, non-condensing
±(2 + 0.003 * mv) %RH mv = measured value

Temperature dependency of electronics, typ.

Factory calibration uncertainty2)

@ 23 °C (73 °F)

0...90 %RH

>90...100 %RH

0.008 % RH/°C (0.004 %RH/°F)
±(0.7 + 0.003 * mv) %RH mv = measured value ±1 %RH

1) Defined against E+E calibration reference at 23 °C (73 °F). With supply voltage 24 V DC, 0.2 m/s (39. 4 ft/min) medium flow and load
resistor 250  for version with current output. 2) Defined at with an enhancement factor k=2, corresponding to a confidence level of 95 %.

Temperature (T)

Measuring range Accuracy1)

-30...+60 °C (-22...+140 °F)
0- 10 V, RS485 ±0,25 °C (±0.14 °F) 4 - 20 mA (2-wire) ±0,38 °C (±0.21 °F)

Temperature dependency of electronics, typ.
Factory calibration uncertainty2) @ 23 °C (73 °F)

0.006 K/K ±0.1 °C

1) Defined @ 23 °C (73 °F) against E+E calibration reference. With supply voltage 24 V DC, 0.2 m/s (39. 4 ft/min) medium flow and load
resistor 250  for version with current output. 2) Defined with an enhancement factor k=2, corresponding to a confidence level of 95 %.

Calculated Physical Quantity

Dew point temperature

Td

Outputs Analogue
T: acc. to ordering guide RH: 0...100 %

Digital
Digital interface
Protocol Factory settings
Supported Baud rates1) Measured data type
Protocol Factory settings Supported Baud rates1)
1) Ex works: see ordering guide.

from -30 (-22)

up to 60 (140)

unit °C (°F)

0 - 10 V 4 - 20 mA (2-wire)

-1 mA < IL < 1 mA RL < (V+ - 10) / 0.02 < 500 

IL = load current RL = load resistance

RS485 (HTS201 = 1 unit load)
Modbus RTU Baud rate according to ordering guide, 8 data bits, parity even, 1 stop bit, Modbus address 45 9600, 19200 and 38400 FLOAT32 and INT16
BACnet MS/TP BACnet address 45 9600, 19200, 38400, 57600, 76800 and 115200

Humidity and Temperature Room Sensor | 19

User Manual HTS201

General

Power supply class III USA & Canada: Class 2 supply necessary, max. voltage 30 V DC
0 - 10 V, RS485 4 - 20 mA (2-wire)
Current consumption, typ.

15 - 35 V DC or 24 V AC ±20 % 10 + 0.02 x RL < V+ < 35 V DC (RL < 500 )

@ 24 V DC

@ 24 V AC

RL = load resistance

0 - 10 V 4 - 20 mA

6 mA

14 mArms

Acc. to output current

Electrical connection

RS485

5 mA

12 mArms

Push-in spring terminals max. 1.5 mm2 (AWG 16)

Display

1.8" LCD, dot-matrix, 2 lines, visible area 38 x 31 mm (1.5" x 1.2")

Humidity range

Operation 0...100 %RH non-condensing Storage 0...95 %RH non-condensing

Temperature range, operation and storage without display with display

-30...+60 °C (-22...+140 °F) -20...+60 °C (-4...+140 °F)

Enclosure

Material PC (Polycarbonate), RAL 9003 (signal white), UL94 HB approved Protection rating IP30

Electromagnetic compatibility

EN 61326-1

EN 61326-2-3

FCC Part15 Class B ICES-003 Class B

Industrial environment

Shock and vibration

Tested according to EN 60068-2-64 and EN 60068-2-27

Conformity

Configuration1) 1) With digital versions only.

PCS10 Product Configuration Software (free download) and optional configuration adapter

Accuracy of E+E Humidity and Temperature Sensors
The measurement accuracy depends both on the performance of the measuring instrument and on the correct installation in the application.
For best accuracy, every E+E RH and T sensing element is factory adjusted and calibrated in a highly stable RH/T reactor. Using a high-precision reference, the overall uncertainty of the factory calibration Ucal is minimal.
The total measurement uncertainty Utotal for E+E sensors is calculated in accordance with EA-4/02 (European Accreditation, Evaluation of the Measurement Uncertainty in Calibration) and with GUM (Guide to the Expression of Uncertainty in Measurement) as follows:

 Utotal = k 



Ucal 2

2
+



uaccuracy 3

2


Utotal .....................total accuracy incl. factory calibration Ucal .......................the uncertainty of the factory calibration uaccuracy.................the accuracy of the measurement device k...........................enhancement factor k=2, corresponding to a confidence level of 95 %.

For external calibrations, Utotal is to be used as the evaluation criterion. The calculation does not include effects due to long-term drift or chemical exposure.

As designated laboratory (NMI) responsible for maintaining the National Standard for humidity and temperature in Austria, E+E Elektronik represents the highest instance in humidity and temperature calibration.

Humidity and Temperature Room Sensor | 20

User Manual HTS201

9 Conformity

9.1 Declarations of Conformity
E+E Elektronik Ges.m.b.H. hereby declares that the product complies with the respective regulations listed below: European directives and standards.
and
UK statutory instruments and designated standards.

Please refer to the product page at www.epluse.com/hts201 for the Declarations of Conformity.

9.2

FCC Part 15 Compliance Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
 Reorient or relocate the receiving antenna.  Increase the separation between the equipment and receiver.  Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.  Consult the dealer or an experienced radio/TV technician for help.

9.3 ICES-003 Compliance Statement
This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

Humidity and Temperature Room Sensor | 21

Company Headquarters & Production Site
E+E Elektronik Ges.m.b.H. Langwiesen 7 4209 Engerwitzdorf | Austria T +43 7235 605-0 F +43 7235 605-8 info@epluse.com www.epluse.com
Subsidiaries
E+E Sensor Technology (Shanghai) Co., Ltd. T +86 21 6117 6129 info@epluse.cn
E+E Elektronik France SARL T +33 4 74 72 35 82 info.fr@epluse.com
E+E Elektronik Deutschland GmbH T +49 6171 69411-0 info.de@epluse.com
E+E Elektronik India Private Limited T +91 990 440 5400 info.in@epluse.com
E+E Elektronik Italia S.R.L. T +39 02 2707 86 36 info.it@epluse.com
E+E Elektronik Korea Ltd. T +82 31 732 6050 info.kr@epluse.com
E+E Elektronik Corporation T +1 847 490 0520 info.us@epluse.com
Version v1.0 | 10-2023 © Copyright E+E Elektronik Ges.m.b.H. | Modification rights reserved.

