Aldes 11057255 Parking Ventilation and Smoke Extraction Control Box
Accessoire ventilateur hélicoïde
11057255 Coffret parking 6A / 1.6A DAH
Control box for ventilation and smoke extraction for collective housing parking facilities. Allows for the control of 2-speed helical fan units for ventilation and smoke extraction.
Image description: A metal enclosure with various electrical components, wiring, and circuit breakers visible inside. It appears to be a control panel for an industrial or building system.
Product Highlights
- Programmable weekly clock to manage ventilation needs while saving energy.
Product Description
The Aldes 11057255 parking control box features an integrated clock that allows for the programming of the fan (Low Speed / High Speed / Stop) in anticipation of vehicle traffic in the parking garage. This control box is particularly suited for collective housing parking facilities. It manages manual smoke extraction activation and smoke extraction shutdown upon request from the fire department.
Application Areas
- Collective residential buildings, New construction, Renovation, Tertiary premises
Installation
- Fixing of the smoke extraction control box to the wall.
Reference Features
- Plastic enclosure, IP 55 rated.
- Dimensions: Width x Height x Depth = 375 x 375 x 200 mm.
- Secured weekly programming clock.
- Motor protection for High Speed (GV) and Low Speed (PV) via thermal-magnetic circuit breakers, with current rating selected based on the motors used.
- Suitable for 2-speed Dahlander motors, three-phase 400V.
- Input/output terminals for manual smoke extraction triggers (normally closed contact).
- Connection possible for a key-operated fire department stop (normally closed contact).
- Manual and wiring diagrams available from your local Aldes agency.
Main Features
- Plastic enclosure, IP 55 rated.
- Dimensions for models 4 to 32A: Width x Height x Depth = 375 x 375 x 180 mm.
- Dimensions for models 40 to 57A: Width x Height x Depth = 375 x 500 x 230 mm.
- Dimensions for 2-fan models: Width x Height x Depth = 375 x 750 x 230 mm.
- Secured weekly programming clock.
- Motor protection for High Speed (GV) and Low Speed (PV) via thermal-magnetic circuit breakers, with current rating selected based on the motors used.
- Suitable for 2-speed Dahlander motors, three-phase 400V.
- Input/output terminals for manual smoke extraction triggers (normally closed contact).
- Connection possible for a key-operated fire department stop (normally closed contact).
- Manual and wiring diagrams available from your local Aldes agency.
Dimensional Data
Reference | H (mm) | L (mm) | P (mm) |
---|---|---|---|
11057255 | 375 | 375 | 180 |
Diagram shows a rectangular box with dimensions labeled L (Length), H (Height), and P (Depth), with four circular connection points indicated.
Principle of Operation
Fire Department Stop
Smoke Extraction Trigger(s)
Clock
PV/GV
NF Contact
NF Contact
PV/GV (thermal-magnetic)
XC
U1 V1 W1 U2 V2 W2
XM
Proximity Switch 2V
Low Speed / High Speed
3-Phase 2V-Dahlander Motor
Diagram description: A wiring diagram illustrating the connections for a smoke extraction system. It shows inputs for fire department stop, manual triggers, and a clock, connected to motor protection and a 2-speed Dahlander motor. The diagram details the flow of control signals and power.
Accessories
Designation | References |
---|---|
Fire Department Stop Box NO + NF parking habitat | 11057251 |